Permit Application Status

PRCOM20211884


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20211884
Building Permit - Commercial
Certificate of Occupancy
GALE COMMUNITIES INC
CHANGE OF TENANT
TENANT FINISH FOR CONSTRUCTION AND DESIGN OFFICE
04/19/2021
05/18/2021
10/20/2021
09/23/2021
Locations
Contacts
ELEVATE DESIGN & BUILD LLC, Address:350 SW LONGVIEW BLVD, Phone:(816) 622-8826  
R-MECH HEATING COOLING PLUMBING/RHODES HEATING COOLING PLUMBING AND ROOTER, Address:1425 AGNES AVE, Phone:(816) 920-5955  
Midwest Custom Electric, Address:20236 w 224th terr, Phone:(913) 938-7625  
CENTURY PLUMBING, Address:14001 CENTURY LN, Phone:(816) 765-6066  
ELEVATE DESIGN & BUILD LLC, Address:350 SW LONGVIEW BLVD, Phone:(816) 622-8826  
gtrkcr@aol.com, Address:gtrkcr@aol.com  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 105  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 05/20/2021 05/20/2021
Michael Weissenbach
Building Plan Review Approved 05/25/2021 05/18/2021
Joe Frogge
Misc
Resolved
05/18/2021

Inadequate information to complete review. Action required: Provide complete MEP designs or detailed scopes of work.
Licensed Contractors Approved 05/25/2021 05/18/2021
Joe Frogge
Fire Plan Review Approved with Conditions 05/25/2021 05/18/2021
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
05/18/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Construction documents - Fire protection systems
Corrective Action Required
05/18/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
05/18/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing if applicable.
Misc
Resolved
05/18/2021

(Informational Purposes) Existing emergency/exit lighting to be fully operational during the occupancy inspection.
Building Plan Review Rejected 04/29/2021 04/23/2021
Joe Frogge
Misc
Corrective Action Required
04/23/2021

Inadequate information to complete review. Action required: Provide complete MEP designs or detailed scopes of work.
Fire Plan Review Approved with Conditions 04/29/2021 04/22/2021
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
04/22/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Construction documents - Fire protection systems
Corrective Action Required
04/22/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
04/22/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing if applicable.
Misc
Corrective Action Required
04/22/2021

(Informational Purposes) Existing emergency/exit lighting to be fully operational during the occupancy inspection.
Licensed Contractors Approved 04/19/2021 04/19/2021
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $100.00 $100.00 Paid 05/18/2021
$0.00
7232302-Commercial License Tax Fee $6,322.50 $6,322.50 Paid 04/23/2021
$6,322.50
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 5/25/2021 5/25/2021 05/25/2021
Underslab Plumbing Inspection - Commercial Passed 05/25/2021
In-wall Inspection Partial 5/28/2021 5/28/2021 05/28/2021
Misc
Informational
05/28/2021
occupancy separation wall approved, ok to insulate and rock this rated assembly
Rated Assembly Inspection Partial 6/14/2021 6/14/2021 05/28/2021
Misc
Informational
05/28/2021
partial approval of rated assembly between occupancies. screw pattern approved on 340 side of assembly except in front office area where window was removed. ok to rock 350 side of assembly and complete fireblocking as discussed onsite with contractor.
Above Ceiling Inspection Failed 6/3/2021 6/3/2021 06/03/2021
Misc
Corrective Action Required
06/03/2021
-install covers on outlet boxes -close unused holes in outlet boxes
In-wall Inspection Failed 6/3/2021 6/3/2021 06/03/2021
Misc
Informational
05/28/2021
occupancy separation wall approved, ok to insulate and rock this rated assembly
Misc
Corrective Action Required
06/03/2021
-Ensure metallic outlet boxes are grounded -complete electrical installation -Fireblock Plate Penetrations in wood frame construction
Above Ceiling Inspection Passed 6/4/2021 6/4/2021 06/04/2021
Misc
Resolved
06/04/2021
-install covers on outlet boxes -close unused holes in outlet boxes
In-wall Inspection Passed 6/4/2021 6/4/2021 06/04/2021
Misc
Resolved
06/04/2021
occupancy separation wall approved, ok to insulate and rock this rated assembly
Misc
Resolved
06/04/2021
-Ensure metallic outlet boxes are grounded -complete electrical installation -Fireblock Plate Penetrations in wood frame construction
Rated Assembly Inspection Partial 06/14/2021
Misc
Informational
05/28/2021
Partial approval of rated assembly between occupancies. -Srew pattern approved on 340 side of assembly except in front office area where window was removed. -Screw pattern approved on 350 side of assembly -complete fireblocking at roof deck and at all through/membrane penetrations of assembly
Rated Assembly Inspection Partial 6/18/2021 6/18/2021 06/18/2021
Misc
Informational
06/14/2021
Partial approval of rated assembly between occupancies. -Screw pattern approved both sides of assembly -complete fireblocking at roof deck and at all through/membrane penetrations of assembly
Rated Assembly Inspection Passed 6/22/2021 6/22/2021 06/22/2021
Misc
Resolved
06/22/2021
Partial approval of rated assembly between occupancies. -Screw pattern approved both sides of assembly -complete fireblocking at roof deck and at all through/membrane penetrations of assembly
Occupancy Inspection - Fire Passed 9/22/2021 9/22/2021 09/22/2021
Corrective Action Required
09/22/2021
Fix or replace emergency light.
Occupancy Inspection - Codes Commercial Failed 9/22/2021 9/22/2021 09/22/2021
Misc
Corrective Action Required
09/22/2021
-Provide GFCI protection at dishwasher -Provide hammer arrestor at dishwasher -Label electrical panels
Occupancy Inspection - Codes Commercial Full C of O 9/23/2021 9/23/2021 09/23/2021
Misc
Resolved
09/23/2021
-Provide GFCI protection at dishwasher -Provide hammer arrestor at dishwasher -Label electrical panels
Documents & Images
Date Uploaded File Type Document Name
04/19/2021 Application Form 21-04-19 - 350 Longview - Tenant Fit Out - Commercial Permit Application
04/19/2021 Application Form 21-04-19 - 350 Longview - Tenant Fit Out - License_Tax_Application
04/19/2021 Plans 21-04-19 - 350 Longview - Tenant Fit Out - Permit Set
04/22/2021 Letter License Tax Bill
04/22/2021 Letter Fire Building Plan Review
04/23/2021 Letter DS P/R Corrections Document
05/18/2021 Plans 21-05-18 - 350 Longview - Tenant Fit Out - Add 001
05/18/2021 Letter 20210518- 350 Longview - Tenant Fit Out - Code Comment Response
05/18/2021 Letter Fire Building Plan Review
05/18/2021 Approved Plans approved - 21-05-18 - 350 Longview - Tenant Fit Out - Add 001
05/18/2021 Receipt Receipt for transaction:2021-003159
05/18/2021 Letter DS Building Permit
05/20/2021 Letter Fire (Sprinkler) Plan Review
05/25/2021 Letter INSPECTION SUMMARY
05/25/2021 Letter INSPECTION SUMMARY
05/28/2021 Letter INSPECTION SUMMARY
05/28/2021 Letter INSPECTION SUMMARY
06/03/2021 Letter INSPECTION SUMMARY
06/03/2021 Letter INSPECTION SUMMARY
06/04/2021 Letter INSPECTION SUMMARY
06/04/2021 Letter INSPECTION SUMMARY
06/14/2021 Letter INSPECTION SUMMARY
06/18/2021 Letter INSPECTION SUMMARY
06/22/2021 Letter INSPECTION SUMMARY
06/22/2021 Letter INSPECTION SUMMARY
09/22/2021 Letter Fire Loss Reduction Form
09/22/2021 Letter INSPECTION SUMMARY
09/23/2021 Letter Codes Final Certificate of Occupancy
09/23/2021 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home