Summary
PRCOM20204589
Building Permit - Commercial
Certificate of Occupancy
DACUR INVESTMENT COMPANY INC
CHANGE OF TENANT
TENANT FINISH FOR HAIR SALON - WORK INCLUDES CONSTRUCTION OF PARTIAL HEIGHT PARTITIONS FOR SALON SUITES Anthony Henderson Plumbing pulled name off of permit because work performed by unknown party. Permit has been placed on hold. jdf 1/20/21 - released 2/5/20 when Taylor Mech added
12/03/2020
12/29/2020
06/09/2021
02/23/2021
Locations
Contacts
VERITASI DESIGN + BUILD, Address:4 SW 3RD ST, Phone:(816) 838-0100  
SHANE@THEPRIVATE.BAR, Address:SHANE@THEPRIVATE.BAR  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
sha110492@gmail.com, Address:sha110492@gmail.com  
TAYLOR MECHANICAL INC, Address:23700 E 189th st, Phone:(816) 743-9900  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 01/05/2021 12/29/2020
Joe Frogge
Misc
Resolved
12/29/2020

Plumber need business license
Fire Plan Review Approved with Conditions 01/05/2021 12/28/2020
Michael Weissenbach
Address numbers required
Corrective Action Required
12/28/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address all exterior doors with 196B.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
12/28/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher.
Building Plan Review Approved with Conditions 01/05/2021 12/28/2020
Joe Frogge
IBC 2902.3 Employee and public toilet facilities - access to public toilet
Corrective Action Required
12/28/2020

2018 IBC 2902.3 Employee and public toilet facilities. For structures and tenant spaces intended for public utilization, customers, patrons and visitors shall be provided with public toilet facilities. Employees associated with structures and tenant spaces shall be provided with toilet facilities. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902 for all users. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. (see code for exceptions) Action required: Comment is for informational purposes.
IPC 403.1 Minimum number of fixtures
Resolved
12/28/2020

2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Action required: Provide drinking fountains or approved alternate. (water bottles? Access to break room sink? Water cooler?) 12/11/20 - not addressed
Building Plan Review Rejected 12/18/2020 12/11/2020
Joe Frogge
Project cost
Resolved
12/16/2020

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes. 12/11/20 - not addressed
Miscellaneous Correction
Resolved
12/16/2020

Inadequate information to complete review. Provide the following: - - Specify all details of wall construction 12/11/20 - not addressed -
IBC 2902.3 Employee and public toilet facilities - access to public toilet
Corrective Action Required
12/11/2020

2018 IBC 2902.3 Employee and public toilet facilities. For structures and tenant spaces intended for public utilization, customers, patrons and visitors shall be provided with public toilet facilities. Employees associated with structures and tenant spaces shall be provided with toilet facilities. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902 for all users. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. (see code for exceptions) Action required: Comment is for informational purposes.
IPC 403.1 Minimum number of fixtures
Corrective Action Required
12/11/2020

2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Action required: Provide drinking fountains or approved alternate. (water bottles? Access to break room sink? Water cooler?) 12/11/20 - not addressed
Licensed Contractors Rejected 12/11/2020 12/11/2020
Joe Frogge
LC - General Contractor
Resolved
12/28/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact. 12/11/20 - not addressed
Fire Plan Review Approved with Conditions 12/18/2020 12/11/2020
Joe Frogge
Address numbers required
Corrective Action Required
12/11/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address all exterior doors with 196B.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
12/11/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher.
Fire Plan Review Approved with Conditions 12/15/2020 12/10/2020
Michael Weissenbach
Address numbers required
Corrective Action Required
12/10/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address all exterior doors with 196B.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
12/10/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher.
Licensed Contractors Rejected 12/10/2020
Joe Frogge
LC - General Contractor
Corrective Action Required
12/10/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact.
Building Plan Review Rejected 12/15/2020 12/10/2020
Joe Frogge
Project cost
Corrective Action Required
12/10/2020

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
Miscellaneous Correction
Corrective Action Required
12/10/2020

Inadequate information to complete review. Provide the following: - Label use of all areas including rear spaces and open spaces. - Specify all details of wall construction - Show locations of any new plumbing fixtures (shampoo bowls?)
IBC 2902.3 Employee and public toilet facilities - access to public toilet
Corrective Action Required
12/10/2020

2018 IBC 2902.3 Employee and public toilet facilities. For structures and tenant spaces intended for public utilization, customers, patrons and visitors shall be provided with public toilet facilities. Employees associated with structures and tenant spaces shall be provided with toilet facilities. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902 for all users. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. (see code for exceptions) Action required: Comment is for informational purposes.
IPC 403.1 Minimum number of fixtures
Corrective Action Required
12/10/2020

2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Action required: Provide drinking fountains or approved alternate. (water bottles? Access to break room sink? Water cooler?)
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $50.00 $50.00 Paid 12/29/2020
$0.00
Commercial Excise Tax Fee $1,350.00 $1,350.00 Paid 12/29/2020
$1,350.00
8331507-Sewer Connection Fee $60.00 $60.00 Paid 12/29/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 1/5/2021 01/05/2021
Misc
Resolved
02/19/2021
- METAL STUD FRAMING APPROVED -
Rough Plumbing Inspection - Commercial Failed 1/21/2021 01/21/2021
Misc
Corrective Action Required
01/21/2021
- PROVIDE SUPPORT PEX WATER LINES - - PROVIDE PLUMBING PROTECTION PLATES PEX & DWV - - NO FURTHER INSPECTIONS UNTIL PLUMBER IS LISTED ON THE PERMIT -
Rough Plumbing Inspection - Commercial Failed 2/11/2021 2/11/2021 02/11/2021
Misc
Corrective Action Required
01/21/2021
- each plumbing fixture shall be separately trapped 2018 IPC 1002.1 - - provide wye and 1/8” bend or combo 2018 IPC 706.3 - - provide access panel for studor vent -
Rough Plumbing Inspection - Commercial Passed 2/16/2021 2/12/2021 02/12/2021
Misc
Resolved
02/12/2021
In-wall Inspection Passed 2/12/2021 02/19/2021
Occupancy Inspection - Codes Commercial Failed 2/19/2021 2/19/2021 02/19/2021
Misc
Corrective Action Required
02/19/2021
- SECURE & PROVIDE COVER PLATE RECEPTACLE BEHIND DOOR TO RESTROOMS - - REPLACE BUG LIGHT SOUTH WALL - - PROVIDE ADDRESS BACK DOOR - - ADD UNIT "B" TO ADDRESS FRONT DOOR -
Occupancy Inspection - Fire Passed 2/19/2021 2/19/2021 02/19/2021
Occupancy Inspection - Codes Commercial Full C of O 2/23/2021 2/23/2021 02/23/2021
Misc
Resolved
02/23/2021
Documents & Images
Date Uploaded File Type Document Name
12/03/2020 Application Form App
12/03/2020 Application Form LT
12/09/2020 Drawing D82CB6C3-23F7-4CA7-95E9-002D1D41BCF9
12/09/2020 Drawing Saphar
12/10/2020 Email architect requirement waiver
12/10/2020 Letter Fire Building Plan Review
12/10/2020 Letter DS P/R Corrections Document
12/11/2020 Drawing saphar
12/11/2020 Letter DS P/R Corrections Document
12/14/2020 Email RE Saphar pdf
12/28/2020 Drawing Saphar
12/28/2020 Letter Fire Building Plan Review
12/28/2020 Approved Plans approved - Saphar
12/29/2020 Receipt Receipt for transaction:2020-008266
12/29/2020 Letter DS Building Permit
01/05/2021 Letter INSPECTION SUMMARY
01/05/2021 Letter INSPECTION SUMMARY
01/05/2021 Letter INSPECTION SUMMARY
01/21/2021 Letter INSPECTION SUMMARY
01/21/2021 Letter INSPECTION SUMMARY
01/21/2021 Letter INSPECTION SUMMARY
02/11/2021 Letter INSPECTION SUMMARY
02/11/2021 Letter License Tax Bill
02/12/2021 Letter INSPECTION SUMMARY
02/12/2021 Letter INSPECTION SUMMARY
02/19/2021 Letter INSPECTION SUMMARY
02/19/2021 Letter INSPECTION SUMMARY
02/19/2021 Letter INSPECTION SUMMARY
02/19/2021 Letter Fire Loss Reduction Form
02/23/2021 Letter Codes Final Certificate of Occupancy
02/23/2021 Letter Field Certificate of Occupancy
02/23/2021 Letter INSPECTION SUMMARY
02/23/2021 Letter Codes Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home