Permit Application Status

PRCOM20193623


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20193623
Building Permit - Commercial
Certificate of Occupancy
TOWNSEND SUMMIT LLC
NEW COMMERCIAL
LION'S CHOICE - NEW FAST FOOD RESTAURANT WITH DRIVE-THRU
12/16/2019
02/28/2020
08/22/2020
07/08/2020
Locations
Contacts
PHILLCO CONSTRUCTION LLC, Address:1440 ERIE ST #C, Phone:(816) 844-9401  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
FIVE STAR MECHANICAL CONTRACT INC, Address:P O BOX 11964, Phone:(816) 358-4444  
OCULUS INC, Address:1 S MEMORIAL DR, STE 1500, Phone:(314) 367-6100  
TOWNSEND SUMMIT LLC, Address:1311 MCCORMICK RD STE 470, Phone:(303) 947-2044  
TOBY WILBORN, Address:PHILLCO CONSTRUCTION, LLC, Phone:(913) 333-8055  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 02/28/2020
Joe Frogge
Building Plan Review Approved with Conditions 03/06/2020 02/28/2020
Joe Frogge
Final Development Plan
Resolved
02/28/2020

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is for informational purposes. 2/24/20 - acknowledged in letter.
Health Dept Inspection
Corrective Action Required
02/28/2020

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 2/24/20 - acknowledged in letter.
Engineered truss package
Corrective Action Required
02/28/2020

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral. 2/24/20 - deferred
Misc
Corrective Action Required
02/28/2020

Irrigation piping conflicts with civil plans. Civil plans call for separate irrigation meter while plumbing plans show irrigation piping routed from inside building. Action required: Resolve conflict. 2/24/20 - conflict still exists. Field verify.
IPC 1003.3.1 Grease interceptors
Resolved
02/28/2020

Grease interceptor design not found in submittal. Action required: Provide grease interceptor installation details. (not provided on civil drawings) 2/24/20 - detail is illegible. Reprint.
Gen - Design professional seals
Resolved
02/28/2020

**comment added on 2/24/20** Missouri Board for Architects, Professional Engineers, Professional Land Surveyors and Professional Landscape Architects – Board Rules, Division 2030 – Chapter 3, 20 CSR 2030-3.060 Licensees Seal Documents must bear design professionals original seal with signature and date. (relevant portion paraphrased – reference original document for additional information) Action required: All drawings are to bear dated seal and signature from architect/engineer of record. The following sheets have illegible seals/signatures. A1.3 A4.1 thru A6.1 All MEP
Licensed Contractors Approved 02/28/2020 02/28/2020
Joe Frogge
Fire Plan Review Approved with Conditions 03/06/2020 02/28/2020
Joe Frogge
Posting of occupant load
Corrective Action Required
02/28/2020

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load sign at 76.
Address numbers required
Corrective Action Required
02/28/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Installation acceptance testing
Corrective Action Required
02/28/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a hood and duct detection test.
Duct smoke detectors
Corrective Action Required
02/28/2020

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Verified At Inspection)
Building Plan Review Rejected 02/25/2020 02/24/2020
Joe Frogge
Final Development Plan
Corrective Action Required
02/18/2020

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is for informational purposes. 2/24/20 - acknowledged in letter.
Health Dept Inspection
Corrective Action Required
02/18/2020

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 2/24/20 - acknowledged in letter.
Engineered truss package
Corrective Action Required
02/18/2020

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral. 2/24/20 - deferred
IMC 306.5 Equipment on roofs
Resolved
02/24/2020

2018 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide side rail extender at roof hatch ladder.
ICC A117.1 304.3 Turning Space
Resolved
02/24/2020

ICC A117.1 Section 304.3 Size. Turning spaces shall comply with Section 304.3.1 or 304.3.2. 304.3.1 Circular Space. 304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Modify design to comply with larger turning radii.
ICC A117.1 305.3 Clear Floor Space
Resolved
02/24/2020

ICC A117.1 Section 305.3 Size. 305.3.1 New Buildings and facilities. In new buildings and facilities the clear floor space shall be 52 inches minimum in length and 30 inches minimum in width. Action required: Modify design to comply with longer clear floor space.
IMC 508.1.1 Makeup air temperature
Resolved
02/24/2020

2018 IMC 508.1 Makeup air. Makeup air shall be supplied during the operation of commercial kitchen exhaust systems that are provided for commercial cooking appliances. The amount of makeup air supplied to the building from all sources shall be approximately equal to the amount of exhaust air for all exhaust systems for the building. The makeup air shall not reduce the effectiveness of the exhaust system. Makeup air shall be provided by gravity or mechanical means or both. Mechanical makeup air systems shall be automatically controlled to start and operate simultaneously with the exhaust system. Makeup air intake opening locations shall comply with Section 401.1. Action required: Provide makeup air to compensate for hood exhaust.
Misc
Corrective Action Required
02/18/2020

Irrigation piping conflicts with civil plans. Civil plans call for separate irrigation meter while plumbing plans show irrigation piping routed from inside building. Action required: Resolve conflict. 2/24/20 - conflict still exists. Field verify.
NEC Article 250.50 Grounding electrode system
Resolved
02/24/2020

2017 NEC Article 250.50 Grounding Electrode System. All Grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at each building or structure served shall be bonded together to form the grounding electrodes system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52(A)(4) through (A)(8) shall be installed and used. (see code section for exception) Action required: Provide detailed grounding diagram that includes all connections or modify riser diagram to comply.
IPC 1003.3.1 Grease interceptors
Corrective Action Required
02/18/2020

Grease interceptor design not found in submittal. Action required: Provide grease interceptor installation details. (not provided on civil drawings) 2/24/20 - detail is illegible. Reprint.
Gen - Design professional seals
Corrective Action Required
02/24/2020

**comment added on 2/24/20** Missouri Board for Architects, Professional Engineers, Professional Land Surveyors and Professional Landscape Architects – Board Rules, Division 2030 – Chapter 3, 20 CSR 2030-3.060 Licensees Seal Documents must bear design professionals original seal with signature and date. (relevant portion paraphrased – reference original document for additional information) Action required: All drawings are to bear dated seal and signature from architect/engineer of record. The following sheets have illegible seals/signatures. A1.3 A4.1 thru A6.1 All MEP
Licensed Contractors Approved 02/24/2020
Joe Frogge
LC - General Contractor
Resolved
02/24/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - General Contractor
Resolved
02/24/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
02/24/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
LC - MEP Subs
Resolved
02/24/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 02/25/2020 02/21/2020
Michael Weissenbach
Posting of occupant load
Corrective Action Required
02/18/2020

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load sign at 76.
Address numbers required
Corrective Action Required
02/18/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Type I hood - Where required
Resolved
02/21/2020

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. (Verified At Inspection) Manual pull mounted no less than 10 feet and not greater than 20 feet from hood system.
Installation acceptance testing
Corrective Action Required
02/18/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a hood and duct detection test.
Portable fire extinguishers for commercial cooking equipment.
Resolved
02/21/2020

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. (Verified At Inspection)
Misc
Resolved
02/21/2020

(Action Required) Provide specs and quantity for the CO2 tank. IFC 2018 5307.3 will apply with tank quantities exceeding 100 pounds.
Duct smoke detectors
Corrective Action Required
02/18/2020

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Verified At Inspection)
Panic and fire exit hardware
Resolved
02/21/2020

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. (Action Required) Provide panic hardware on exit doors.
Health Department Review Approved 01/02/2020
Joe Frogge
Fire Plan Review Rejected 01/02/2020 12/18/2019
Michael Weissenbach
Posting of occupant load
Corrective Action Required
12/18/2019

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load sign at 76.
Address numbers required
Corrective Action Required
12/18/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Type I hood - Where required
Corrective Action Required
12/18/2019

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. (Verified At Inspection) Manual pull mounted no less than 10 feet and not greater than 20 feet from hood system.
Installation acceptance testing
Corrective Action Required
12/18/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a hood and duct detection test.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
12/18/2019

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. (Verified At Inspection)
Misc
Corrective Action Required
12/18/2019

(Action Required) Provide specs and quantity for the CO2 tank. IFC 2018 5307.3 will apply with tank quantities exceeding 100 pounds.
Duct smoke detectors
Corrective Action Required
12/18/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Action Required) Duct detection required with CFM greater than 2000.
Panic and fire exit hardware
Corrective Action Required
12/18/2019

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. (Action Required) Provide panic hardware on exit doors.
Building Plan Review Rejected 01/02/2020 12/18/2019
Joe Frogge
Final Development Plan
Corrective Action Required
12/18/2019

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is for informational purposes.
Health Dept Review
Resolved
01/02/2020

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
12/18/2019

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Engineered truss package
Corrective Action Required
12/18/2019

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral.
IMC 306.5 Equipment on roofs
Corrective Action Required
12/18/2019

2018 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide side rail extender at roof hatch ladder.
ICC A117.1 304.3 Turning Space
Corrective Action Required
12/18/2019

ICC A117.1 Section 304.3 Size. Turning spaces shall comply with Section 304.3.1 or 304.3.2. 304.3.1 Circular Space. 304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Modify design to comply with larger turning radii.
ICC A117.1 305.3 Clear Floor Space
Corrective Action Required
12/18/2019

ICC A117.1 Section 305.3 Size. 305.3.1 New Buildings and facilities. In new buildings and facilities the clear floor space shall be 52 inches minimum in length and 30 inches minimum in width. Action required: Modify design to comply with longer clear floor space.
IMC 508.1.1 Makeup air temperature
Corrective Action Required
12/18/2019

2018 IMC 508.1 Makeup air. Makeup air shall be supplied during the operation of commercial kitchen exhaust systems that are provided for commercial cooking appliances. The amount of makeup air supplied to the building from all sources shall be approximately equal to the amount of exhaust air for all exhaust systems for the building. The makeup air shall not reduce the effectiveness of the exhaust system. Makeup air shall be provided by gravity or mechanical means or both. Mechanical makeup air systems shall be automatically controlled to start and operate simultaneously with the exhaust system. Makeup air intake opening locations shall comply with Section 401.1. Action required: Provide makeup air to compensate for hood exhaust.
Misc
Corrective Action Required
12/18/2019

Irrigation piping conflicts with civil plans. Civil plans call for separate irrigation meter while plumbing plans show irrigation piping routed from inside building. Action required: Resolve conflict.
NEC Article 250.50 Grounding electrode system
Corrective Action Required
12/18/2019

2017 NEC Article 250.50 Grounding Electrode System. All Grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at each building or structure served shall be bonded together to form the grounding electrodes system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52(A)(4) through (A)(8) shall be installed and used. (see code section for exception) Action required: Provide detailed grounding diagram that includes all connections or modify riser diagram to comply.
IPC 1003.3.1 Grease interceptors
Corrective Action Required
12/18/2019

Grease interceptor design not found in submittal. Action required: Provide grease interceptor installation details. (not provided on civil drawings)
Licensed Contractors Rejected 01/02/2020 12/18/2019
Joe Frogge
LC - General Contractor
Corrective Action Required
12/18/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
12/18/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Commercial $3,879.33 $3,879.33 Paid 02/25/2020
8331507-Sewer Connection Fee $270.00 $270.00 Paid 02/25/2020
Commercial Excise Tax Fee $25,402.50 $25,402.50 Paid 02/25/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 3/12/2020 3/13/2020 03/13/2020
Misc
Corrective Action Required
03/13/2020
Perimeter footing and ufer ground
Underslab Plumbing Inspection - Commercial Passed 3/27/2020 3/27/2020 at 10:55 AM 03/27/2020
Underslab Electrical Inspection - Commercial Passed 3/31/2020 3/31/2020 03/31/2020
Underground Plumbing Inspection - Commercial Partial 4/14/2020 4/14/2020 at 1:10 PM 04/14/2020
Misc
Informational
04/14/2020
- GREASE PIT, LINES & CLEANOUTS -
Rough Framing Inspection - Commercial Passed 4/27/2020 4/27/2020 04/27/2020
In-wall Inspection Failed 5/1/2020 5/1/2020 05/01/2020
Misc
Corrective Action Required
05/01/2020
- PROVIDE NAIL GUARDS PLUMBING & ELECTRICAL - - COMPLETE PLUMBING TO RESTROOMS -
In-wall Inspection Partial 5/4/2020 5/4/2020 05/04/2020
Misc
Resolved
05/04/2020
Piers/Caissons Inspection - Commercial Partial 5/6/2020 (1:00) 5/6/2020 05/06/2020
Misc
Informational
05/06/2020
- UNDERGROUND CONDUIT FOR 3 LIGHT POLE BASES & PHONE & FLAGPOLE EAST END FRONT LOT -
Underground Electrical Inspection - Commercial Partial 5/7/2020 05/07/2020
Misc
Corrective Action Required
05/07/2020
EXTERIOR CONDUIT : NE CORNER BUILDING TO PAST TRASH ENCLOSURE ; - UNDERGROUND CONDUIT FOR 3 LIGHT POLE BASES & PHONE & FLAGPOLE EAST END FRONT LOT; -
Underground Electrical Inspection - Commercial Partial 5/8/2020 5/8/2020 05/08/2020
Misc
Corrective Action Required
05/07/2020
EXTERIOR CONDUIT : NE CORNER BUILDING TO PAST TRASH ENCLOSURE; - UNDERGROUND CONDUIT FOR 3 LIGHT POLE BASES & PHONE & FLAGPOLE EAST END FRONT LOT; WEST 2 POLE LIGHTS;EAST SIDE. NOTE:BUILDING TO NW POLE BASE & MENU BOARD REMAINING.
Underground Electrical Inspection - Commercial Partial 5/11/2020 (A.M.) 5/11/2020 05/11/2020
Misc
Corrective Action Required
05/08/2020
EXTERIOR CONDUIT : NOTE: MENU BOARD REMAINING.
Underground Electrical Inspection - Commercial Passed 5/19/2020 5/19/2020 05/19/2020
Misc
Resolved
05/19/2020
EXTERIOR CONDUIT : NOTE: MENU BOARD REMAINING.
Hood/Duct Inspection Failed 5/26/2020 at 2:35 PM 05/26/2020
Misc
Corrective Action Required
05/26/2020
-NEED LADDER AND 100W LIGHT SOURCE TO DO THE LIGHT TEST FOR THE WELD PART OF THE DUCT
Gas Service Inspection - Commercial Passed 5/28/2020 05/28/2020
Gas Piping Inspection - Commercial Partial 5/28/2020 5/28/2020 05/28/2020
Misc
Informational
05/28/2020
- NEED TO CHECK GAS PIPE SUPPORT ON ROOF POURING RAIN 5/28/20 - - ABOVE CEILING APPROVED - Michael Harkins 05/28/2020 1:07 PM
Hood/Duct Inspection Partial 5/28/2020 5/28/2020 at 12:55 PM 05/28/2020
Misc
Informational
05/28/2020
-NEED LADDER AND 100W LIGHT SOURCE TO DO THE LIGHT TEST FOR THE WELD PART OF THE DUCT - - WELDS APPROVED OK FOR 1ST LAYER WRAP -
Electrical Service Inspection Passed 5/29/2020 5/29/2020 05/29/2020
Hood/Duct Inspection Partial 6/3/2020 6/3/2020 06/03/2020
Misc
Informational
05/28/2020
-NEED LADDER AND 100W LIGHT SOURCE TO DO THE LIGHT TEST FOR THE WELD PART OF THE DUCT - - WELDS APPROVED OK FOR 1ST LAYER WRAP - - 1ST LAYER WRAP APPROVED OK FOR 2ND LAYER -
Piers/Caissons Inspection - Commercial Passed 6/3/2020 (11:00) 6/3/2020 06/03/2020
Misc
Informational
05/06/2020
(6) REBAR AGES POLE BASES, (4) MENU BOARDS ALL PER PLAN 6/3/20 -
Above Ceiling Inspection Partial 6/10/2020 6/10/2020 06/10/2020
Misc
Partial Correction
06/10/2020
- LEAVE CEILING TILES OUT ABOVE SERVICE PANEL - -ALL OTHER AREAS APPROVED -
Verify Final Inspection (Final) Complete 06/17/2020
Underground Plumbing Inspection - Commercial Passed 6/17/2020 06/17/2020
Misc
Informational
04/14/2020
- GREASE PIT, LINES & CLEANOUTS -
Hood/Duct Inspection Passed 6/10/2020 06/17/2020
Misc
Resolved
06/17/2020
-NEED LADDER AND 100W LIGHT SOURCE TO DO THE LIGHT TEST FOR THE WELD PART OF THE DUCT - - WELDS APPROVED OK FOR 1ST LAYER WRAP - - 1ST LAYER WRAP APPROVED OK FOR 2ND LAYER -
Above Ceiling Inspection Passed 06/17/2020
Misc
Resolved
06/17/2020
- LEAVE CEILING TILES OUT ABOVE SERVICE PANEL - -ALL OTHER AREAS APPROVED -
In-wall Inspection Passed 5/4/2020 06/17/2020
Gas Piping Inspection - Commercial Passed 5/27/2020 06/17/2020
Misc
Resolved
06/17/2020
- NEED TO CHECK GAS PIPE SUPPORT ON ROOF POURING RAIN 5/28/20 - - ABOVE CEILING APPROVED - Michael Harkins 05/28/2020 1:07 PM
Footing Inspection - Commercial Passed 06/17/2020
Misc
Corrective Action Required
03/13/2020
Perimeter footing and ufer ground
Alternate Protection Systems Inspection Passed 6/19/2020 06/19/2020
Occupancy Inspection - Fire Passed 6/19/2020 06/19/2020
Occupancy Inspection - Planning Passed 6/22/2020 06/22/2020
Occupancy Inspection - Engineering Passed 6/22/2020 06/22/2020
Occupancy Inspection - Codes Commercial Failed 6/22/2020 6/22/2020 06/22/2020
Misc
Corrective Action Required
06/17/2020
Obtain Health Department Approval
Miscellaneous Correction
Corrective Action Required
06/22/2020
Pending approval by Water Utilities
Miscellaneous Correction
Corrective Action Required
06/22/2020
Pay oustanding After Hours Inspection Fee on permit PRSITE20200323 of $330.00.
Miscellaneous Correction
Corrective Action Required
06/22/2020
The backflow device for the carbonated beverage machine may need to be changed. Staff will look into this and provide more information.
Occupancy Inspection - Health Passed 07/08/2020
Occupancy Inspection - Codes Commercial Full C of O 07/08/2020
Misc
Resolved
07/08/2020
Obtain Health Department Approval
Miscellaneous Correction
Resolved
06/24/2020
Pending approval by Water Utilities - Needs backflow information for the irrigation system.
Miscellaneous Correction
Resolved
06/23/2020
Pay oustanding After Hours Inspection Fee on permit PRSITE20200323 of $330.00. Paid 6-23-2020
Miscellaneous Correction
Resolved
06/29/2020
The backflow device for the carbonated beverage machine may need to be changed. Staff will look into this and provide more information. Mike Weisenborn 06/29/2020 2:03 PM - Correct backflows have been installed.
Occupancy Inspection - Water Utilities Passed 07/08/2020
Documents & Images
Date Uploaded File Type Document Name
12/18/2019 Letter Fire Building Plan Review
12/19/2019 Letter DS P/R Corrections Document
01/02/2020 New Food Establishment Plan Review - Approved FTG 0001141
02/21/2020 Letter Fire Building Plan Review
02/24/2020 Letter DS P/R Corrections Document
02/25/2020 Receipt Receipt for transaction: 2020-000827
02/28/2020 Letter License Tax Bill
02/28/2020 Letter DS Building Permit
03/13/2020 Letter INSPECTION SUMMARY
03/18/2020 Plans 52118-MO02 - Lee's Summit _Rev1-Arch_MEPS-Signed_2020-2-14
03/27/2020 Letter INSPECTION SUMMARY
03/31/2020 Letter INSPECTION SUMMARY
04/10/2020 Lion's Choice Lee's Summit Plumbing Modifications
04/14/2020 Letter INSPECTION SUMMARY
04/27/2020 Letter INSPECTION SUMMARY
05/01/2020 Letter INSPECTION SUMMARY
05/04/2020 Letter INSPECTION SUMMARY
05/06/2020 Letter INSPECTION SUMMARY
05/11/2020 Letter INSPECTION SUMMARY
05/19/2020 Letter INSPECTION SUMMARY
05/26/2020 Letter INSPECTION SUMMARY
05/28/2020 Letter INSPECTION SUMMARY
05/28/2020 Letter INSPECTION SUMMARY
05/28/2020 Letter INSPECTION SUMMARY
05/29/2020 Letter INSPECTION SUMMARY
06/03/2020 Letter INSPECTION SUMMARY
06/03/2020 Letter INSPECTION SUMMARY
06/10/2020 Letter INSPECTION SUMMARY
06/22/2020 Letter INSPECTION SUMMARY
06/22/2020 Letter INSPECTION SUMMARY
07/08/2020 Activity Document Health Department Approval
07/08/2020 Letter INSPECTION SUMMARY
07/08/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home