Permit Application Status

PRCOM20193321


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20193321
Building Permit - Commercial
Final Completion
TOWNSEND SUMMIT LLC
ALTERATION COMMERCIAL
TENANT FINISH FOR CLOTHING SALES ROSS DRESS FOR LESS
11/08/2019
03/10/2020
05/11/2020
09/30/2020
Locations
Contacts
TOWNSEND SUMMIT LLC, Address:1311 MCCORMICK RD STE 470, Phone:(303) 947-2044  
SLAGGIE ARCHITECTS INC, Address:4600 MADISON AVE STE 350, Phone:(816) 756-1958 Ext:243  
VCC LLC, Address:1 INFORMATION WAY, STE 300, Phone:(501) 376-0017  
B & C MECHANICAL SERVICES LLC, Address:2008 E SPRUCE CIR STE B, Phone:(913) 681-0088  
STACO ELECTRIC CONSTRUCTION COMPANY INC, Address:11030 HICKMAN MILLS DR, Phone:(816) 765-7112  
RIVER OAK MECHANICAL LLC, Address:7800 NIEMAN ROAD, Phone:(573) 289-9207  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 08/21/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
08/21/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Misc
Corrective Action Required
08/21/2020

1. Provide outside horn/strobe to monitor water flow for Ross. Placement to be made on the Northwest corner of Homegoods facing the FDC. Provide signage above the horn/strobe stating 480. Horn/strobe to only activate with water flow. 2. Horn/strobes on the interior to terminate when silenced.
Sprinkler Plan Review Released for Construction 03/23/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
03/13/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Miscellaneous Correction
03/23/2020

Alarm Plan Review Released for Construction 03/13/2020
Michael Weissenbach
Miscellaneous Correction
Resolved
04/17/2020

(ACTION REQUIRED) Provide one horn/strobe in each space for notification.
Installation acceptance testing
Corrective Action Required
03/13/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Licensed Contractors Approved 12/03/2019 02/28/2020
Joe Frogge
LC - General Contractor
Resolved
02/28/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 11/27/19 - acknowledged in letter
LC - MEP Subs
Resolved
02/28/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 11/27/19 - acknowledged in letter
Building Plan Review Approved with Conditions 12/03/2019 11/27/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
11/22/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 11/27/19 - acknowledged in letter
IBC 502.1 - Address Identification
Resolved
11/27/2019

2018 IBC 502.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be a minimum of 4 inches high with a minimum stroke width of ½ inch. Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure. Address identification shall be maintained. Action required: This suite has been assigned the address of 480 NW Chipman Rd. Please update your records and inform your client.
IBC 1606.2 Design dead load - structural
Resolved
11/22/2019

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of new roof top equipment is less than or equal to original equipment or provide engineer’s report to verify that existing roof structure will support additional load. Action required: Provide verification that roof is capable of carrying new roof loads imposed by hvac equipment.
Miscellaneous Correction
Corrective Action Required
11/22/2019

This permit is tied to a shell building permit. Action required: Comment is for informational purposes. Occupancy for tenant cannot be granted prior to complete of shell permit. 11/27/19 - acknowledged in letter
ICC A117.1 304.3 Turning Space
Resolved
11/27/2019

ICC A117.1 Section 304.3 Size. Turning spaces shall comply with Section 304.3.1 or 304.3.2. 304.3.1 Circular Space. 304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Update designs to show minimum 67" turning radii.
IBC 1103.1 Where required - accessibility
Corrective Action Required
11/22/2019

2018 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Comment is for informational purposes. Accessibility of checkout aisles to be verified during inspections. 11/27/19 - acknowledged in letter
IBC 1209.2 Urinal partitions - privacy
Resolved
11/27/2019

2018 IBC 1209.3.2 Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal not less than 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measures from the finished back wall surface, whichever is greater. Exceptions: 1. Urinal partitions shall not be required in a single-occupant or family or assisted-use toilet room with a lockable door. 2. Toilet rooms located in child day care facilities containing two or more urinals shall be permitted to have one urinal without partitions. Action required: Provide partitions on both sides of urinal.
IPC 605.4 Water distribution pipe
Resolved
11/27/2019

Unable to verify plumbing pipe materials. Action required: Provide pipe material schedule.
Fire Plan Review Approved with Conditions 12/03/2019 11/22/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
11/22/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide three sets of PE stamped shop drawings.
Address numbers required
Corrective Action Required
11/22/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
11/22/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
11/22/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Building Plan Review Rejected 11/20/2019 11/13/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
11/13/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
IBC 502.1 - Address Identification
Corrective Action Required
11/13/2019

2018 IBC 502.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be a minimum of 4 inches high with a minimum stroke width of ½ inch. Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure. Address identification shall be maintained. Action required: This suite has been assigned the address of 480 NW Chipman Rd. Please update your records and inform your client.
IBC 1606.2 Design dead load - structural
Corrective Action Required
11/13/2019

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of new roof top equipment is less than or equal to original equipment or provide engineer’s report to verify that existing roof structure will support additional load. Action required: Provide verification that roof is capable of carrying new roof loads imposed by hvac equipment.
Miscellaneous Correction
Corrective Action Required
11/13/2019

This permit is tied to a shell building permit. Action required: Comment is for informational purposes. Occupancy for tenant cannot be granted prior to complete of shell permit.
ICC A117.1 304.3 Turning Space
Corrective Action Required
11/13/2019

ICC A117.1 Section 304.3 Size. Turning spaces shall comply with Section 304.3.1 or 304.3.2. 304.3.1 Circular Space. 304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Update designs to show minimum 67" turning radii.
IBC 1103.1 Where required - accessibility
Corrective Action Required
11/13/2019

2018 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Comment is for informational purposes. Accessibility of checkout aisles to be verified during inspections.
IBC 1209.2 Urinal partitions - privacy
Corrective Action Required
11/13/2019

2018 IBC 1209.3.2 Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal not less than 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measures from the finished back wall surface, whichever is greater. Exceptions: 1. Urinal partitions shall not be required in a single-occupant or family or assisted-use toilet room with a lockable door. 2. Toilet rooms located in child day care facilities containing two or more urinals shall be permitted to have one urinal without partitions. Action required: Provide partitions on both sides of urinal.
IPC 605.4 Water distribution pipe
Corrective Action Required
11/13/2019

Unable to verify plumbing pipe materials. Action required: Provide pipe material schedule.
Licensed Contractors Rejected 11/20/2019 11/13/2019
Joe Frogge
LC - General Contractor
Corrective Action Required
11/13/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
11/13/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 11/20/2019 11/12/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
11/12/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide three sets of PE stamped shop drawings.
Address numbers required
Corrective Action Required
11/12/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
11/12/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
11/12/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Tenent Finish $3,520.00 $3,520.00 Paid 03/10/2020
8331507-Sewer Connection Fee $270.00 $270.00 Paid 03/10/2020
Commercial Excise Tax Fee $40,035.00 $40,035.00 Paid 03/10/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 4/1/2020 04/01/2020
Underslab Plumbing Inspection - Commercial Partial 4/2/2020 04/02/2020
Misc
Corrective Action Required
04/02/2020
Partial for tenant finish.
Underslab Plumbing Inspection - Commercial Partial 4/8/2020 4/8/2020 04/08/2020
Misc
Corrective Action Required
04/02/2020
Partial for tenant finish.
All Rough Inspection - Commercial Partial 5/13/2020 5/13/2020 05/13/2020
Misc
Corrective Action Required
05/13/2020
PARTIAL- secure and protect DWV in wall mid story and above ceiling.
All Rough Inspection - Commercial Passed 5/15/2020 5/15/2020 05/15/2020
Above Ceiling Inspection Partial 5/28/2020 5/28/2020 05/28/2020
Misc
Corrective Action Required
05/28/2020
HARD CEILING AREAS COMPLETE;
Sprinkler - Hydrostatic Test Passed 6/15/2020 06/15/2020
Gas Piping Inspection - Commercial Passed 6/25/2020 6/25/2020 06/25/2020
Gas Service Inspection - Commercial Passed 5/15/2020 6/25/2020 06/25/2020
Above Ceiling Inspection Passed 7/8/2020 07/08/2020
Misc
Informational
07/08/2020
HARD CEILING AREAS COMPLETE;
Misc
Informational
07/08/2020
SUSPENDED CEILING AREAS COMPLETE
Electrical Service Inspection Passed 5/15/2020 7/8/2020 07/08/2020
Rough Electrical Inspection - Commercial Partial 7/8/2020 7/8/2020 07/08/2020
Misc
Informational
07/08/2020
- EXTERIOR CANOPY LIGHTS -
Alarm Test Passed 7/28/2020 07/28/2020
Sprinkler - Flow Test Passed 7/28/2020 07/28/2020
Occupancy Inspection - Fire Temporary C of O 8/12/2020 8/12/2020 08/11/2020
Occupancy Inspection - Codes Commercial Temporary C of O 8/12/2020 8/12/2020 08/12/2020
Misc
Corrective Action Required
08/12/2020
- RESTROOM SIGNS TO BE INSTALLED BY ROSS -
Alarm Test Failed 9/9/2020 09/09/2020
Occupancy Inspection - Fire Failed 9/9/2020 09/09/2020
Alarm Test Passed 9/30/2020 09/30/2020
Occupancy Inspection - Fire Passed 9/30/2020 09/30/2020
Occupancy Inspection - Codes Commercial Full C of O 9/9/2020 9/9/2020 09/30/2020
Misc
Corrective Action Required
09/30/2020
All City of Lee's Summit requirements associated with this permit have been met. An additional permit will be required for the point of sale and overall setup of the store. An application for this work will need to be submitted for review, approval and inspections prior to opening.
Final Inspection - Commercial Passed 09/30/2020
Miscellaneous Correction
Corrective Action Required
09/30/2020
All City of Lee's Summit requirements associated with this permit have been met. An additional permit will be required for the point of sale and overall setup of the store. An application for this work will need to be submitted for review, approval and inspections prior to opening.
Documents & Images
Date Uploaded File Type Document Name
11/12/2019 Letter Fire Building Plan Review
11/13/2019 Letter DS P/R Corrections Document
11/22/2019 RE Summit Orchard Lot 4 Structural changes
11/22/2019 Letter Fire Building Plan Review
02/28/2020 Letter License Tax Bill
03/10/2020 Receipt Receipt for transaction: 2020-001080
03/10/2020 Letter DS Building Permit
03/13/2020 Letter Fire (Alarm) Plan Review Notice
03/23/2020 Letter Fire (Sprinkler) Plan Review
04/01/2020 Letter INSPECTION SUMMARY
04/02/2020 Letter INSPECTION SUMMARY
04/02/2020 Letter Fire (Alarm) Plan Review Notice
04/02/2020 Letter Codes Plan Review Conditions
04/08/2020 Letter INSPECTION SUMMARY
04/17/2020 Letter Fire (Alarm) Plan Review Notice
05/13/2020 Letter INSPECTION SUMMARY
05/15/2020 Letter INSPECTION SUMMARY
05/28/2020 Letter INSPECTION SUMMARY
06/25/2020 Letter INSPECTION SUMMARY
06/25/2020 Letter INSPECTION SUMMARY
07/08/2020 Letter INSPECTION SUMMARY
07/08/2020 Letter INSPECTION SUMMARY
07/08/2020 Letter INSPECTION SUMMARY
08/12/2020 Letter Codes Temporary Certificate of Occupancy
08/21/2020 Ross Dress for Less FA 1&2
08/21/2020 Letter Fire (Alarm) Plan Review Notice
09/28/2020 Plans 2313.ROSS.FIXTURE.PermitSubmittal.09.25.2020
09/30/2020 Letter INSPECTION SUMMARY
09/30/2020 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home