Permit Application Status

PRCOM20193195


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20193195
Building Permit - Commercial
Certificate of Occupancy
VAAP RAINTREE LLC
CHANGE OF TENANT
RESTAURANT EXPANSION INTO ADJACENT SPACE
10/30/2019
11/27/2019
05/04/2020
07/02/2020
Locations
Contacts
BENNETT HOME IMPROVEMENT & BUILDING INC, Address:708 NW R D MIZE RD STE J , Phone:(816) 229-4711  
COMFORT SYSTEMS HTG/CLG, Address:17232 BEL-RAY PL, Phone:(816) 322-1013  
PORTER ELECTRICAL, Address:114 VETERANS PKWY, Phone:(816) 540-3271  
RITEWAY PLUMBING LLC, Address:2101 SW OSAGE DR, Phone:(816) 813-9849  
CL ARCHITECTURE (CRAIG LUEBBERT), Address:396 SW WINTERGARDEN, Phone:(816) 536-3472  
  
VAAP RAINTREE LLC, Address:5007 W 147TH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 12/18/2019
Michael Weissenbach
Misc
Corrective Action Required
12/18/2019

(Informational Purposes) Current inspection tag needed on riser.
Licensed Contractors Approved 11/21/2019 11/27/2019
Development Center
LC - General Contractor
Resolved
11/27/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 11/15/19 - Acknowledged in letter.
LC - MEP Subs
Resolved
11/27/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 11/15/19 - Acknowledged in letter.
Building Plan Review Approved with Conditions 11/21/2019 11/20/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
11/14/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 11/15/19 - Acknowledged in letter.
Health Dept Review
Resolved
11/20/2019

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 11/15/19 - Acknowledged in letter.
Health Dept Inspection
Corrective Action Required
11/14/2019

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 11/15/19 - Acknowledged in letter.
IBC 602.1 Type of Construction - general
Resolved
11/15/2019

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update code analysis. This building is a 5B.
IBC 1010.1.2 Door swing - direction of swing egress travel
Resolved
11/15/2019

2018 IBC 1010.1.2 Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for exceptions.) 2018 IBC 1010.1.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. Action required: Sliding doors not allowed as egress component. Given that there is adequate egress without the barn door it will be acceptable if all references to it are changed to "sliding partition" or similar.
IBC 1606.2 Design dead load - structural
Corrective Action Required
11/14/2019

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of new roof top equipment is less than or equal to original equipment or provide engineer’s report to verify that existing roof structure will support additional load. Action required: Provide verification that roof can support new dead load imposed by make-up air unit. 11/15/19 - Deferred to construction at request by architect.
IMC 507.2.6 Clearances for Type I hood
Corrective Action Required
11/14/2019

2018 IMC 507.2.6 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. Exceptions: 1. Clearance shall not be required from gypsum wallboard or ½ inch or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches in all directions from the hood. 2. Type I hoods listed and labeled for clearances less than 18 inches in accordance with UL 710 shall be installed with the clearances specified by such listings. Action required: Given that this is a 5B building, provide verification that wall at new hood is constructed with noncombustible materials. 11/15/19 - Acknowledged in letter. - To be field verified.
IPC 802.1 Indirect/special waste
Resolved
11/15/2019

2018 IPC 802.1 Where required. Food-handling equipment, in other than dwelling units, clear-water waste, humidifiers, dish-washing machines and utensils, pots, pans and dish washing sinks shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. Fixtures not required to be indirectly connected by this section and the exception to Section 301.6 shall be directly connected to the plumbing system in accordance with Chapter 7. Action required: Indirect drain required at 3-compartment sink. Modify detail.
NEC Article 210.8 (B) Other than dwelling units GFCI
Resolved
11/15/2019

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles in kitchen will be GFCI protected.
IBC 1016.2 Egress through intervening spaces
Resolved
11/15/2019

2018 IBC 1016.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. Item 5. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. (See code section for additional items and exceptions) Action required: Egress through kitchen not allowed. Remove exit light.
Fire Plan Review Approved with Conditions 11/21/2019 11/20/2019
Michael Weissenbach
Posting of occupant load
Corrective Action Required
11/14/2019

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post Occupant Load at 173
Construction documents for fire alarm systems
Corrective Action Required
11/14/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide three sets of PE stamped shop drawings. NOTE: Type 1 hood to be integrated into the fire alarm system
Address numbers required
Corrective Action Required
11/14/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address all exterior doors.
Type I hood - Where required
Resolved
11/20/2019

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. (Action Required) Show placement of manual pull on plans. Between 10 and 20 feet from hood system.
Construction documents - Fire protection systems
Corrective Action Required
11/14/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications done to the fire sprinkler system, provide three sets of PE stamped shop drawings. NOTE: Overhead doors will need sprinkler coverage underneath.
Installation acceptance testing
Corrective Action Required
11/14/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing. Alarm system and Type 1 hood will need to pass before a final occupancy inspection can be scheduled.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
11/14/2019

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. (Verified At Inspection) Mount K-Class extinguisher by the manual pull.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
11/14/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC extinguisher in new work area.
Miscellaneous Correction
Resolved
11/20/2019

Door Swing IFC 1005.7.1 (Action Required) Door to Storage Room 104 swings into the path of egress travel.
Egress through intervening spaces.
Resolved
11/20/2019

2018 IFC 1016.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. (Action Required) Remove exit sign leading into kitchen area from dining room.
Panic and fire exit hardware
Resolved
11/20/2019

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. (Action Required) Provide panic hardware on exit doors.
Health Department Review Approved 11/20/2019
Joe Frogge
Building Plan Review Rejected 11/11/2019 11/06/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
11/06/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Corrective Action Required
11/06/2019

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
11/06/2019

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
IBC 602.1 Type of Construction - general
Corrective Action Required
11/06/2019

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update code analysis. This building is a 5B.
IBC 1010.1.2 Door swing - direction of swing egress travel
Corrective Action Required
11/06/2019

2018 IBC 1010.1.2 Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for exceptions.) 2018 IBC 1010.1.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. Action required: Sliding doors not allowed as egress component. Given that there is adequate egress without the barn door it will be acceptable if all references to it are changed to "sliding partition" or similar.
IBC 1606.2 Design dead load - structural
Corrective Action Required
11/06/2019

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of new roof top equipment is less than or equal to original equipment or provide engineer’s report to verify that existing roof structure will support additional load. Action required: Provide verification that roof can support new dead load imposed by make-up air unit.
IMC 507.2.6 Clearances for Type I hood
Corrective Action Required
11/06/2019

2018 IMC 507.2.6 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. Exceptions: 1. Clearance shall not be required from gypsum wallboard or ½ inch or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches in all directions from the hood. 2. Type I hoods listed and labeled for clearances less than 18 inches in accordance with UL 710 shall be installed with the clearances specified by such listings. Action required: Given that this is a 5B building, provide verification that wall at new hood is constructed with noncombustible materials.
IPC 802.1 Indirect/special waste
Corrective Action Required
11/06/2019

2018 IPC 802.1 Where required. Food-handling equipment, in other than dwelling units, clear-water waste, humidifiers, dish-washing machines and utensils, pots, pans and dish washing sinks shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. Fixtures not required to be indirectly connected by this section and the exception to Section 301.6 shall be directly connected to the plumbing system in accordance with Chapter 7. Action required: Indirect drain required at 3-compartment sink. Modify detail.
NEC Article 210.8 (B) Other than dwelling units GFCI
Corrective Action Required
11/06/2019

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles in kitchen will be GFCI protected.
IBC 1016.2 Egress through intervening spaces
Corrective Action Required
11/06/2019

2018 IBC 1016.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. Item 5. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. (See code section for additional items and exceptions) Action required: Egress through kitchen not allowed. Remove exit light.
Licensed Contractors Rejected 11/11/2019 11/06/2019
Joe Frogge
LC - General Contractor
Corrective Action Required
11/06/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
11/06/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 11/11/2019 11/06/2019
Michael Weissenbach
Posting of occupant load
Corrective Action Required
11/06/2019

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post Occupant Load at 173
Construction documents for fire alarm systems
Corrective Action Required
11/06/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide three sets of PE stamped shop drawings. NOTE: Type 1 hood to be integrated into the fire alarm system
Address numbers required
Corrective Action Required
11/06/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address all exterior doors.
Type I hood - Where required
Corrective Action Required
11/06/2019

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. (Action Required) Show placement of manual pull on plans. Between 10 and 20 feet from hood system.
Construction documents - Fire protection systems
Corrective Action Required
11/06/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications done to the fire sprinkler system, provide three sets of PE stamped shop drawings. NOTE: Overhead doors will need sprinkler coverage underneath.
Installation acceptance testing
Corrective Action Required
11/06/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing. Alarm system and Type 1 hood will need to pass before a final occupancy inspection can be scheduled.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
11/06/2019

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. (Verified At Inspection) Mount K-Class extinguisher by the manual pull.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
11/06/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Action Required) Provide one 2A10BC extinguisher in new work area.
Miscellaneous Correction
Corrective Action Required
11/06/2019

Door Swing IFC 1005.7.1 (Action Required) Door to Storage Room 104 swings into the path of egress travel.
Egress through intervening spaces.
Corrective Action Required
11/06/2019

2018 IFC 1016.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. (Action Required) Remove exit sign leading into kitchen area from dining room.
Panic and fire exit hardware
Corrective Action Required
11/06/2019

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. (Action Required) Provide panic hardware on exit doors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $228.00 $228.00 Paid 11/27/2019
$0.00
8331504-EFHB Middle Big Creek, Full $167.40 $167.40 Paid 11/27/2019
8331507-Sewer Connection Fee $150.00 $150.00 Paid 11/27/2019
Outstanding Fees Amount Paid Owing Date Paid
7232302-Commercial License Tax Fee $7,605.00 $1,635.00 $5,970.00 Not Paid
$1,635.00



(None of the fees owing can be paid online)
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 3/5/2020 3/5/2020 03/05/2020
Misc
Corrective Action Required
03/05/2020
missing vent and sink east side of batroom.
Underslab Plumbing Inspection - Commercial Passed 3/6/2020 3/6/2020 03/06/2020
Misc
Resolved
03/06/2020
In-wall Inspection Partial 3/27/2020 3/27/2020 03/27/2020
Informational
03/27/2020
partial in old pet grooming space: - metal studs, -plumbing in bath, 2 sinks, ice maker, - electrical approved
Hood/Duct Inspection Partial 4/3/2020 4/3/2020 04/03/2020
Misc
Informational
04/03/2020
- HOOD DUCT WELDS APPROVED -
Hood/Duct Inspection Partial 4/6/2020 4/6/2020 04/06/2020
Misc
Informational
04/06/2020
1ST LAYER WRAP ON HOOD EXHAUST OK
In-wall Inspection Partial 4/6/2020 4/6/2020 04/06/2020
Misc
Informational
04/06/2020
METAL STUD FRAMING : PARTITION WALLS IN EXISTING SPACE, METAL STUD FRAMING IN EXPANSION SPACE -
In-wall Inspection Partial 5/13/2020 5/13/2020 05/13/2020
Misc
Informational
04/06/2020
METAL STUD FRAMING : PARTITION WALLS IN EXISTING SPACE, METAL STUD FRAMING IN EXPANSION SPACE -
Misc
Corrective Action Required
05/13/2020
- IN WALL @ SERVING COUNTER OK TO COVER -
Gas Service Inspection - Commercial Passed 5/19/2020 5/19/2020 05/19/2020
Gas Piping Inspection - Commercial Passed 5/19/2020 05/19/2020
Above Ceiling Inspection Partial 5/29/2020 5/29/2020 05/29/2020
Misc
Corrective Action Required
05/29/2020
- COMPLETE DRYWALL REPAIR ABOVE CEILING BOTH SIDES OF HOOD - - PROVIDE ACCESS TO REPAIR 1 TILE EACH SIDE OF HOOD -
Alternate Protection Systems Inspection Passed 6/30/2020 06/30/2020
Alarm Test Passed 6/30/2020 06/30/2020
Occupancy Inspection - Fire Passed 7/1/2020 7/1/2020 07/01/2020
Occupancy Inspection - Codes Commercial Failed 7/1/2020 7/1/2020 07/01/2020
Misc
Corrective Action Required
07/01/2020
--paint exterior gas line on south side of building and rooftop. --change door swing to plans, from new addition to existing area. --install safety devises or cooking appliances. --move mirror in women's restroom to no more than 40" to reflective edge. --cut drain to 2" above floor sink on grease container drain.
Occupancy Inspection - Codes Commercial Full C of O 7/2/2020 7/2/2020 07/02/2020
Misc
Resolved
07/02/2020
Documents & Images
Date Uploaded File Type Document Name
11/06/2019 Letter Fire Building Plan Review
11/06/2019 Letter DS P/R Corrections Document
11/20/2019 Food Establishment Remodel Plan Review - Approved FTG 0001599
11/20/2019 Letter Fire Building Plan Review
11/27/2019 Receipt Receipt for transaction: 2019-007493
11/27/2019 Letter DS Building Permit
11/27/2019 Letter License Tax Bill
12/18/2019 Letter Fire (Sprinkler) Plan Review
03/05/2020 Letter INSPECTION SUMMARY
03/06/2020 Letter INSPECTION SUMMARY
03/27/2020 Letter INSPECTION SUMMARY
04/03/2020 Letter INSPECTION SUMMARY
04/06/2020 Letter INSPECTION SUMMARY
04/06/2020 Letter INSPECTION SUMMARY
05/13/2020 Letter INSPECTION SUMMARY
05/19/2020 Letter INSPECTION SUMMARY
05/19/2020 Letter INSPECTION SUMMARY
05/29/2020 Letter INSPECTION SUMMARY
07/01/2020 Letter INSPECTION SUMMARY
07/02/2020 Letter Field Certificate of Occupancy
07/02/2020 Letter Codes Final Certificate of Occupancy
07/02/2020 Activity Document DOC070220
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home