Permit Application Status

PRCOM20192841


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20192841
Building Permit - Commercial
Certificate of Occupancy
TOWNSEND SUMMIT LLC
NEW TENANT FINISH
TENANT FINISH FOR RETAIL
10/01/2019
03/10/2020
04/19/2020
09/02/2020
Locations
Contacts
VCC LLC, Address:1 INFORMATION WAY, STE 300, Phone:(501) 376-0017  
B & C MECHANICAL SERVICES LLC, Address:2008 E SPRUCE CIR STE B, Phone:(913) 681-0088  
STACO ELECTRIC CONSTRUCTION COMPANY INC, Address:11030 HICKMAN MILLS DR, Phone:(816) 765-7112  
RIVER OAK MECHANICAL LLC, Address:7800 NIEMAN ROAD, Phone:(573) 289-9207  
CASCO + R5, Address:12 SUNNEN DR, SUITE 100, Phone:(314) 821-1100  
TOWNSEND SUMMIT LLC, Address:1311 MCCORMICK RD STE 470, Phone:(303) 947-2044  
SLAGGIE ARCHITECTS INC, Address:4600 MADISON AVE STE 350, Phone:(816) 756-1958 Ext:243  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 04/17/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
04/17/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule alarm testing.
Sprinkler Plan Review Released for Construction 03/23/2020
Michael Weissenbach
Licensed Contractors Approved 12/03/2019 02/28/2020
Joe Frogge
LC - MEP Subs
Resolved
02/28/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/17/19 - acknowledged in letter
Misc
Resolved
02/28/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 10/17/19 - acknowledged in letter
Fire Plan Review Approved with Conditions 12/03/2019 11/22/2019
Joe Frogge
Construction documents for fire alarm systems
Corrective Action Required
11/22/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide three sets of PE stamped shop drawings.
Address numbers required
Corrective Action Required
11/22/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
11/22/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
11/22/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Building Plan Review Approved with Conditions 12/03/2019 11/22/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
11/22/2019

This tenant finish permit is tied to a shell permit. Action required: Comment is for informational purposes. Occupancy will not be granted for the tenant prior to completion of shell permit. 10/17/19 - acknowledged in letter
IBC 1606.2 Design dead load - structural
Resolved
11/22/2019

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that roof structure will support additional load. 10/17/19 - Unable to locate required information in shell package.
Fire Plan Review Approved with Conditions 10/24/2019 11/12/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
11/12/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide three sets of PE stamped shop drawings.
Address numbers required
Corrective Action Required
11/12/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
11/12/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
11/12/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Fire Plan Review Approved with Conditions 10/24/2019 10/21/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
10/17/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide three sets of PE stamped shop drawings.
Address numbers required
Corrective Action Required
10/17/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
10/17/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
10/17/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Building Plan Review Rejected 10/24/2019 10/17/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
10/17/2019

This tenant finish permit is tied to a shell permit. Action required: Comment is for informational purposes. Occupancy will not be granted for the tenant prior to completion of shell permit. 10/17/19 - acknowledged in letter
Suite address
Resolved
10/17/2019

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: This tenant suite has been assigned the address of 472 NW Chipman Rd. Please update your records.
Engineered truss package
Resolved
10/17/2019

Designs for exterior canopies were not provided at the time of permit application. Action required: Provide canopy designs or request deferral. 10/17/19 - part of shell package per architect
Accessibility - Turning space 603.2.1
Resolved
10/17/2019

ICC A117.1-2017 Section 304.3 Size. Turning spaces shall comply with Section 304.3.1 or 304.3.2. 304.3.1 Circular Space. 304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Modify design to show correct turning radii.
Accessibility - Lavatory clear floor space 606.2
Resolved
10/17/2019

ICC A117.1-2017 Section 305.3 Size. 305.3.1 New Buildings and facilities. In new buildings and facilities the clear floor space shall be 52 inches minimum in length and 30 inches minimum in width. Action required: Modify design to show correct turning clear floor spaces.
IBC 1606.2 Design dead load - structural
Corrective Action Required
10/17/2019

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that roof structure will support additional load. 10/17/19 - Unable to locate required information in shell package.
Miscellaneous Correction
Resolved
10/17/2019

Unable to locate natural gas piping specifications. Action required: Provide natural gas pipe material information.
Licensed Contractors Rejected 10/24/2019 10/17/2019
Joe Frogge
LC - MEP Subs
Corrective Action Required
10/17/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/17/19 - acknowledged in letter
Misc
Corrective Action Required
10/17/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 10/17/19 - acknowledged in letter
Building Plan Review Rejected 10/11/2019 10/09/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
10/09/2019

This tenant finish permit is tied to a shell permit. Action required: Comment is for informational purposes. Occupancy will not be granted for the tenant prior to completion of shell permit.
Suite address
Corrective Action Required
10/09/2019

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: This tenant suite has been assigned the address of 472 NW Chipman Rd. Please update your records.
Engineered truss package
Corrective Action Required
10/09/2019

Designs for exterior canopies were not provided at the time of permit application. Action required: Provide canopy designs or request deferral.
Accessibility - Turning space 603.2.1
Corrective Action Required
10/09/2019

ICC A117.1-2017 Section 304.3 Size. Turning spaces shall comply with Section 304.3.1 or 304.3.2. 304.3.1 Circular Space. 304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Modify design to show correct turning radii.
Accessibility - Lavatory clear floor space 606.2
Corrective Action Required
10/09/2019

ICC A117.1-2017 Section 305.3 Size. 305.3.1 New Buildings and facilities. In new buildings and facilities the clear floor space shall be 52 inches minimum in length and 30 inches minimum in width. Action required: Modify design to show correct turning clear floor spaces.
IBC 1606.2 Design dead load - structural
Corrective Action Required
10/09/2019

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that roof structure will support additional load.
Miscellaneous Correction
Corrective Action Required
10/09/2019

Unable to locate natural gas piping specifications. Action required: Provide natural gas pipe material information.
Licensed Contractors Rejected 10/11/2019 10/09/2019
Joe Frogge
LC - MEP Subs
Corrective Action Required
10/09/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Misc
Corrective Action Required
10/09/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Fire Plan Review Approved with Conditions 10/11/2019 10/03/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
10/03/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide three sets of PE stamped shop drawings.
Address numbers required
Corrective Action Required
10/03/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
10/03/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
10/03/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Zoning Review Approved 10/11/2019 10/01/2019
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Tenent Finish $574.00 $574.00 Paid 03/10/2020
8331507-Sewer Connection Fee $180.00 $180.00 Paid 03/10/2020
Commercial Excise Tax Fee $15,435.00 $15,435.00 Paid 03/10/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 4/1/2020 4/1/2020 04/01/2020
Underslab Plumbing Inspection - Commercial Passed 4/9/2020 4/9/2020 04/09/2020
All Rough Inspection - Commercial Partial 5/15/2020 5/15/2020 05/15/2020
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
05/15/2020
FRONT SALES AREA ONLY; REAR AREAS AND OFFICE NOT INSPECTED
All Rough Inspection - Commercial Partial 5/21/2020 05/21/2020
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
05/15/2020
FRONT SALES AREA ONLY; REAR AREAS AND OFFICE ,REAR OFFICE AND OFFICE AREA COMPLETE.
Gas Piping Inspection - Commercial Passed 6/25/2020 6/25/2020 06/25/2020
Gas Service Inspection - Commercial Passed 6/25/2020 06/25/2020
Above Ceiling Inspection Passed 7/8/2020 07/08/2020
Electrical Service Inspection Passed 7/8/2020 07/08/2020
Alarm Test Passed 7/28/2020 07/28/2020
Sprinkler - Flow Test Passed 7/28/2020 07/28/2020
Occupancy Inspection - Fire Passed 8/11/2020 8/11/2020 08/11/2020
Sprinkler - Hydrostatic Test Passed 6/4/2020 08/11/2020
Occupancy Inspection - Codes Commercial Temporary C of O 8/11/2020 8/12/2020 08/12/2020
Misc
Resolved
09/02/2020
- OK FOR C of O WHEN SHELL C of O ISSUED -
Occupancy Inspection - Codes Commercial Full C of O 9/2/2020 09/02/2020
Misc
Resolved
09/02/2020
- OK FOR C of O WHEN SHELL C of O ISSUED -
Documents & Images
Date Uploaded File Type Document Name
10/03/2019 Letter Fire Building Plan Review
10/09/2019 Letter DS P/R Corrections Document
10/21/2019 Letter Fire Building Plan Review
10/22/2019 Letter DS P/R Corrections Document
11/12/2019 Letter Fire Building Plan Review
11/20/2019 RE Five Below design drawings - permit PRCOM20192841
11/20/2019 RE Five Below with Above One architect
11/22/2019 RE Summit Orchard Lot 4 Structural changes
02/28/2020 Letter License Tax Bill
03/10/2020 Receipt Receipt for transaction: 2020-001079
03/10/2020 Letter DS Building Permit
03/23/2020 Letter Fire (Sprinkler) Plan Review
04/01/2020 Letter INSPECTION SUMMARY
04/09/2020 Letter INSPECTION SUMMARY
04/09/2020 Letter Codes Plan Review Conditions
04/17/2020 Letter Fire (Alarm) Plan Review Notice
05/15/2020 Letter INSPECTION SUMMARY
05/15/2020 Letter INSPECTION SUMMARY
05/21/2020 Letter INSPECTION SUMMARY
06/25/2020 Letter INSPECTION SUMMARY
06/25/2020 Letter INSPECTION SUMMARY
07/08/2020 Letter INSPECTION SUMMARY
07/08/2020 Letter INSPECTION SUMMARY
08/12/2020 Letter Codes Temporary Certificate of Occupancy
09/02/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home