Summary
PRCOM20192786
Building Permit - Commercial
Certificate of Occupancy
LANGSFORD DEVELOPMENT INC
CHANGE OF TENANT
CHANGE OF TENANT FOR HEARING AID SALES
09/26/2019
10/04/2019
04/14/2020
11/07/2019
Locations
Contacts
ZIPCO CONTRACTING INC, Address:4110 N CORRINGTON AVE, Phone:(816) 471-3797  
MORSE ELECTRIC, Address:815 NORTH ST, Phone:(816) 785-2385  
HAMPTON PLUMBING INC, Address:P O BOX 552, Phone:(816) 628-5069  
SCHARHAG ARCHITECTS, Address:6247 BROOKSIDE BLVD STE 204, Phone:(816) 656-5055  
  
LANGSFORD DEVELOPMENT INC, Address:616 SW 3RD ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 10/24/2019 10/21/2019
Michael Weissenbach
Address numbers required
Corrective Action Required
10/17/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address front and back doors
Door operations
Corrective Action Required
10/17/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Verified At Inspection)
Building Plan Review Approved with Conditions 10/24/2019 10/17/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
10/17/2019

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: All circuits in patient care areas shall have redundant ground system. (to be field verified)
Licensed Contractors Approved 10/17/2019 10/17/2019
Dylan Eppert
Miscellaneous Correction
Corrective Action Required
10/17/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Miscellaneous Correction
Corrective Action Required
10/17/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Mechanical contractor.
Building Plan Review Approved with Conditions 10/08/2019 10/02/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
10/02/2019

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: All circuits in patient care areas shall have redundant ground system. (to be field verified)
Licensed Contractors Rejected 09/26/2019 10/02/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
10/02/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Miscellaneous Correction
Corrective Action Required
10/02/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Mechanical contractor.
Fire Plan Review Approved with Conditions 10/08/2019 09/30/2019
Michael Weissenbach
Address numbers required
Corrective Action Required
09/30/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address front and back doors
Door operations
Corrective Action Required
09/30/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Verified At Inspection)
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $149.35 $149.35 Paid 10/04/2019
$2,992.50
7232302-Commercial Excise Tax Fee $2,992.50 $2,992.50 Paid 09/26/2019
$2,992.50
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 10/11/2019 at 10:20 AM 10/11/2019
In-wall Inspection Passed 10/23/2019 at 10:15 AM 10/23/2019
Above Ceiling Inspection Failed 10/28/2019 10/28/2019 at 8:35 AM 10/28/2019
Misc
Corrective Action Required
10/28/2019
SUPPORT WIRES AT LAY-IN ELECTRICAL LUMINAIRES: PROVIDE TWO SLACK WIRE TIES PER FIXTURE FROM STRUCTURE TO TWO OPPOSITE DIAGONAL CORNERS. TIE BOTH ENDS WITH TWO FULL WRAPS MINIMUM.
Misc
Corrective Action Required
10/28/2019
LOW-VOLTAGE ELECTRICAL CABLE: - REMOVE ANY ABANDONED CABLE - STRAP ALL REMINING TO HARD LID
Misc
Corrective Action Required
10/28/2019
SUPPORT MC CABLE RUNS TO HARD LID.
Misc
Corrective Action Required
10/28/2019
NEC 110-12: PLUG ANY UNUSED OPENINGS AT FIXTURES AND JUNCTION BOXES.
Above Ceiling Inspection Passed 10/30/2019 10/30/2019 at 9:25 AM 10/30/2019
Misc
Resolved
10/30/2019
SUPPORT WIRES AT LAY-IN ELECTRICAL LUMINAIRES: PROVIDE TWO SLACK WIRE TIES PER FIXTURE FROM STRUCTURE TO TWO OPPOSITE DIAGONAL CORNERS. TIE BOTH ENDS WITH TWO FULL WRAPS MINIMUM.
Misc
Resolved
10/30/2019
LOW-VOLTAGE ELECTRICAL CABLE: - REMOVE ANY ABANDONED CABLE - STRAP ALL REMINING TO HARD LID
Misc
Resolved
10/30/2019
SUPPORT MC CABLE RUNS TO HARD LID.
Misc
Resolved
10/30/2019
NEC 110-12: PLUG ANY UNUSED OPENINGS AT FIXTURES AND JUNCTION BOXES.
Occupancy Inspection - Fire Passed 11/4/2019 11/04/2019
Occupancy Inspection - Codes Commercial Failed 11/4/2019 11/4/2019 at 10:30 AM 11/04/2019
Misc
Corrective Action Required
11/04/2019
NEC 380-10; 410-56(f) / IRC E3901.10; E3902.6 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: SECURE ONE LOOSE AT RECEPTION AREA SOUTH
Misc
Corrective Action Required
11/04/2019
FURNACE/WATER HEATER VENT PIPE IS OPEN AT FITTING. FAS SUPPLY TO BE SHUT OFF UNTIL APPROVED.
Misc
Corrective Action Required
11/04/2019
NEC 408.4 ELECTRICAL SERVICE PANEL SCHEDULE: ENSURE ALL CIRCUIT POSITIONS ARE PROPERLY LABELED. MUST BE LEGIBLE, COMPLETE, CURRENT, SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Corrective Action Required
11/04/2019
IPC 420.3: WATER CLOSET SEAT(S) MUST BE COMMERCIAL TYPE WITH OPEN FRONT.
Misc
Corrective Action Required
11/04/2019
LS CODE OF ORDINANCES 17-309: DISPLAY OF "NO SMOKING" SIGN(S) REQUIRED AT PUBLIC ENTRY(IES). SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY.
Misc
Corrective Action Required
11/04/2019
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. STAFFING, TRAINING, FIXTURING, STOCKING OK. NO PUBLIC/CUSTOMERS/PATIENTS PRIOR TO APPROVAL.
Occupancy Inspection - Codes Commercial Full C of O 11/7/2019 11/7/2019 at 7:10 AM 11/07/2019
Misc
Resolved
11/07/2019
NEC 380-10; 410-56(f) / IRC E3901.10; E3902.6 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: SECURE ONE LOOSE AT RECEPTION AREA SOUTH
Misc
Resolved
11/07/2019
FURNACE/WATER HEATER VENT PIPE IS OPEN AT FITTING. FAS SUPPLY TO BE SHUT OFF UNTIL APPROVED.
Misc
Resolved
11/07/2019
NEC 408.4 ELECTRICAL SERVICE PANEL SCHEDULE: ENSURE ALL CIRCUIT POSITIONS ARE PROPERLY LABELED. MUST BE LEGIBLE, COMPLETE, CURRENT, SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Resolved
11/07/2019
IPC 420.3: WATER CLOSET SEAT(S) MUST BE COMMERCIAL TYPE WITH OPEN FRONT.
Misc
Resolved
11/07/2019
LS CODE OF ORDINANCES 17-309: DISPLAY OF "NO SMOKING" SIGN(S) REQUIRED AT PUBLIC ENTRY(IES). SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY.
Misc
Resolved
11/07/2019
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. STAFFING, TRAINING, FIXTURING, STOCKING OK. NO PUBLIC/CUSTOMERS/PATIENTS PRIOR TO APPROVAL.
Documents & Images
Date Uploaded File Type Document Name
09/26/2019 Letter License Tax Bill
09/30/2019 Letter Fire Building Plan Review
10/03/2019 American Hearing
10/03/2019 Re American Hearing
10/04/2019 Receipt Receipt for transaction: 2019-006629
10/04/2019 Letter DS Building Permit
10/11/2019 Letter INSPECTION SUMMARY
10/21/2019 Letter Fire Building Plan Review
10/23/2019 Letter INSPECTION SUMMARY
10/28/2019 Letter INSPECTION SUMMARY
10/30/2019 Letter INSPECTION SUMMARY
11/04/2019 Letter INSPECTION SUMMARY
11/07/2019 Letter Field Certificate of Occupancy
11/14/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home