Permit Application Status

PRCOM20191907


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20191907
Building Permit - Commercial
Final Completion
NEW OTHER (COMMERCIAL)
RESTROOM BUILDING
07/17/2019
09/12/2019
01/14/2020
07/02/2020
Locations
Contacts
AMAI ARCHITECTURE, Address:1510 WALNUT, Phone:(816) 994-5900  
KELLY CONSTRUCTION GROUP INC, Address:4021 E 143RD ST, Phone:(816) 621-7600  
METRO AIR CONDITIONING , Address:8151 MCCOY ST, Phone:(913) 888-3991  
PALMER ELECTRIC CO, Address:6600 ROYAL ST, BLDG B, Phone:(816) 479-2587  
STINE-NICHOLS PLUMBING INC, Address:318 E 16TH AVE, Phone:(816) 348-3481  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 07/26/2019 09/12/2019
Joe Frogge
Final Development Plan
Resolved
08/20/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 7/19/19 - acknowledged in letter
Bldg - Toilet room wall finish 1210.2.2
Resolved
07/19/2019

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 1209.2.2 Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish materials. If paint is used it must be epoxy based.
Bldg - Premises identification/address 501.2
Corrective Action Required
07/19/2019

2018 IBC 502.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be a minimum of 4 inches high with a minimum stroke width of ½ inch. Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure. Address identification shall be maintained. Action required: The address for this structure has been assigned as 1901 NW Lowenstein Dr. Please update your records. 7/19/19 - acknowledged in letter
Licensed Contractors Approved 07/19/2019 09/12/2019
Joe Frogge
LC - General Contractor
Resolved
08/22/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 7/19/19 - acknowledged in letter
LC - MEP Subs
Resolved
09/12/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 7/19/19 - acknowledged in letter
Final Development Plan Review Approved 08/20/2019
Joe Frogge
Fire Plan Review Approved with Conditions 07/26/2019 07/19/2019
Joe Frogge
Address numbers required
Corrective Action Required
07/19/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Licensed Contractors Rejected 07/18/2019
Joe Frogge
LC - General Contractor
Corrective Action Required
07/18/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
07/18/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Rejected 07/31/2019 07/18/2019
Joe Frogge
Final Development Plan
Corrective Action Required
07/18/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
07/18/2019

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 1209.2.2 Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish materials. If paint is used it must be epoxy based.
Bldg - Premises identification/address 501.2
Corrective Action Required
07/18/2019

2018 IBC 502.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be a minimum of 4 inches high with a minimum stroke width of ½ inch. Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure. Address identification shall be maintained. Action required: The address for this structure has been assigned as 1901 NW Lowenstein Dr. Please update your records.
Fire Plan Review Approved with Conditions 07/18/2019
Michael Weissenbach
Address numbers required
Corrective Action Required
07/18/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Other $450.00 $450.00 Paid Not payable online 09/12/2019
8331507-Sewer Connection Fee $120.00 $120.00 Paid Not payable online 09/12/2019
Outstanding Fees Amount Paid Owing Date Paid
9110080-Not Ready Inspection Fee $50.00 $0.00 $50.00 Not Paid


$50.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 9/19/2019 9/19/2019 09/19/2019
Misc
Partial Correction
09/19/2019
Restroom footing approved to poor, also approved by 3rd party inspector
Underslab Plumbing Inspection - Commercial Passed 9/24/2019 9/24/2019 at 2:40 PM 09/24/2019
Footing Inspection - Commercial Passed 9/26/2019 9/19/2019 09/26/2019
Misc
Resolved
09/26/2019
Restroom footing approved to poor, also approved by 3rd party inspector
Underslab Electrical Inspection - Commercial Passed 9/26/2019 at 1:15 PM 09/26/2019
In-wall Inspection Partial 11/14/2019 11/14/2019 at 1:35 PM 11/14/2019
Misc
Partial Correction
11/14/2019
CMU EXTERIOR WALLS BEING LAID WITH CELLS AT 4' INTERVALS RECEIVING VERTICAL #5 RE-BAR AND GROUT.
All Rough Inspection - Commercial Failed 11/25/2019 at 9:50 AM 11/25/2019
Misc
Corrective Action Required
11/25/2019
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS.
Misc
Corrective Action Required
11/25/2019
RIDGE BEAM IS NOT CONTINUOUS -- WITH NO SUPPORT AT BUTT JOINT.
All Rough Inspection - Commercial Passed 11/26/2019 11/26/2019 at 9:55 AM 11/26/2019
Misc
Resolved
11/26/2019
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS.
Misc
Resolved
11/26/2019
RIDGE BEAM IS NOT CONTINUOUS -- WITH NO SUPPORT AT BUTT JOINT.
Underground Electrical Inspection - Commercial Failed 11/26/2019 11/26/2019 at 10:10 AM 11/26/2019
Underground Electrical Inspection - Commercial Passed 11/27/2019 11/27/2019 at 1:00 PM 11/27/2019
Misc
Resolved
11/27/2019
GROUNDING NOT PER APPROVED DRAWINGS. NOT READY FOR INSPECTION UNTIL GROUNDING PER DRAWINGS.
In-wall Inspection Passed 11/27/2019
Misc
Resolved
11/27/2019
CMU EXTERIOR WALLS BEING LAID WITH CELLS AT 4' INTERVALS RECEIVING VERTICAL #5 RE-BAR AND GROUT.
Underground Electrical Inspection - Commercial Partial 12/11/2019 12/11/2019 at 1:35 PM 12/11/2019
Misc
Partial Correction
12/11/2019
THREE LIGHT POLE BASES APPROVED FOR POUR -- ONE ADDITIONAL AND TWO REPLACEMENTS -- FOR TOTAL OF SEVEN. OK TO POUR WHEN READY.
Misc
Partial Correction
12/11/2019
TRENCHED CONDUIT OK TO COVER: ONE 2" SECONDARY FROM BUILDING TO 25' EAST ONE 1-1/2" FROM BUILDING TO 30' NORTH FOR SITE LIGHTING FEED.
Electrical Service Inspection Partial 12/19/2019 12/19/2019 at 1:25 PM 12/19/2019
Misc
Partial Correction
12/19/2019
NO ISSUES FOUND ON INSTALLED SERVICE EQUIPMENT AND GROUNDING. SECONDARY NOT IN PLACE FOR INSPECTION.
Electrical Service Inspection Failed 5/22/2020 5/22/2020 at 10:40 AM 05/22/2020
Misc
Partial Correction
12/19/2019
NO ISSUES FOUND ON INSTALLED SERVICE EQUIPMENT AND GROUNDING. SECONDARY NOT IN PLACE FOR INSPECTION.
Misc
Corrective Action Required
05/22/2020
-PROVIDE ACCESS TO VERIFY GROUNDING TO METAL WATER SERVICE, IF PRESENT, WITH #2 COPPER GROUNDING ELECTRODE CONDUCTOR (GEC) SIZED PER 250.66 -VERIFY GROUNDING TO UFER, WHICH IS PRESENT, WITH #4 COPPER GEC -GROUNDING ELECTRODE CONDUCTORS SHALL CONNECT TO THE BUS BAR THAT THE SERVICE GROUNDED CONDUCTOR IS CONNECTED TO; OR INSTALL A BONDING JUMPER SIZED PER 250.66 TO THE BUS BAR THAT THE GECs ARE CONNECTED TO. NEC 250.24(A)(1) AND (4) -BOND THE RACEWAY ENCLOSING THE SERVICE CONDUCTORS PER 250.92 BY: REMOVE ENAMEL AT SERVICE DISCONNECT ENCLOSURE CONNECTION OF RACEWAY ENCLOSING THE SERVICE CONDUCTORS FOR DIRECT METAL-METAL CONTACT; OR INSTALL BONDING BUSHING WITH JUMPER SIZED PER 250.66.
Underground Electrical Inspection - Commercial Passed 6/4/2020 06/04/2020
Misc
Resolved
06/04/2020
THREE LIGHT POLE BASES APPROVED FOR POUR -- ONE ADDITIONAL AND TWO REPLACEMENTS -- FOR TOTAL OF SEVEN. OK TO POUR WHEN READY.
Misc
Resolved
06/04/2020
TRENCHED CONDUIT OK TO COVER: ONE 2" SECONDARY FROM BUILDING TO 25' EAST ONE 1-1/2" FROM BUILDING TO 30' NORTH FOR SITE LIGHTING FEED.
Electrical Service Inspection Failed 6/4/2020 06/04/2020
Misc
Resolved
06/04/2020
NO ISSUES FOUND ON INSTALLED SERVICE EQUIPMENT AND GROUNDING. SECONDARY NOT IN PLACE FOR INSPECTION.
Misc
Corrective Action Required
05/22/2020
-***Color code bonding bushing wire to bus bar. **not installed--GROUNDING ELECTRODE CONDUCTORS SHALL CONNECT TO THE BUS BAR THAT THE SERVICE GROUNDED CONDUCTOR IS CONNECTED TO; OR INSTALL A BONDING JUMPER SIZED PER 250.66 TO THE BUS BAR THAT THE GECs ARE CONNECTED TO. -Dbl pole breakers connected together wwith ground wire, install approved breaker cap to connect the 2, not a peice of wire. -GROUNDING ELECTRODE CONDUCTORS SHALL CONNECT TO THE BUS BAR THAT THE SERVICE GROUNDED CONDUCTOR IS CONNECTED TO; OR INSTALL A BONDING JUMPER SIZED PER 250.66 TO THE BUS BAR THAT THE GECs ARE CONNECTED TO. NEC 250.24(A)(1) AND (4)
Electrical Service Inspection Not Ready 6/5/2020 6/5/2020 06/05/2020
Misc
Corrective Action Required
06/04/2020
-***Color code bonding bushing wire to bus bar. **not installed--GROUNDING ELECTRODE CONDUCTORS SHALL CONNECT TO THE BUS BAR THAT THE SERVICE GROUNDED CONDUCTOR IS CONNECTED TO; OR INSTALL A BONDING JUMPER SIZED PER 250.66 TO THE BUS BAR THAT THE GECs ARE CONNECTED TO. -Dbl pole breakers connected together wwith ground wire, install approved breaker cap to connect the 2, not a peice of wire. -GROUNDING ELECTRODE CONDUCTORS SHALL CONNECT TO THE BUS BAR THAT THE SERVICE GROUNDED CONDUCTOR IS CONNECTED TO; OR INSTALL A BONDING JUMPER SIZED PER 250.66 TO THE BUS BAR THAT THE GECs ARE CONNECTED TO. NEC 250.24(A)(1) AND (4)
Electrical Service Inspection Passed 6/18/2020 6/18/2020 06/18/2020
Misc
Corrective Action Required
06/05/2020
Final Inspection - Commercial Failed 7/1/2020 7/1/2020 06/18/2020
Misc
Corrective Action Required
06/18/2020
NOTE ONLY: LABEL MAIN PANEL , NO INTERIOR FINAL HAS BEEN PERFORMED.
Final Inspection - Commercial Passed 7/2/2020 7/2/2020 07/02/2020
Misc
Resolved
07/02/2020
NOTE ONLY: LABEL MAIN PANEL , NO INTERIOR FINAL HAS BEEN PERFORMED.
Documents & Images
Date Uploaded File Type Document Name
07/18/2019 Letter Fire Building Plan Review
07/18/2019 Letter DS P/R Corrections Document
07/18/2019 Letter DS P/R Corrections Document
09/12/2019 Receipt Receipt for transaction: 2019-006197
09/12/2019 Letter DS Building Permit
09/19/2019 Letter INSPECTION SUMMARY
09/24/2019 Letter INSPECTION SUMMARY
09/26/2019 Letter INSPECTION SUMMARY
11/25/2019 Letter INSPECTION SUMMARY
11/26/2019 Letter INSPECTION SUMMARY
11/26/2019 Letter INSPECTION SUMMARY
11/27/2019 Letter INSPECTION SUMMARY
12/03/2019 Letter DOC120319
12/11/2019 Letter INSPECTION SUMMARY
05/22/2020 Letter INSPECTION SUMMARY
06/05/2020 Letter INSPECTION SUMMARY
06/18/2020 Letter INSPECTION SUMMARY
06/18/2020 Letter INSPECTION SUMMARY
06/18/2020 Letter INSPECTION SUMMARY
06/18/2020 Letter INSPECTION SUMMARY
06/18/2020 Letter INSPECTION SUMMARY
06/18/2020 Letter INSPECTION SUMMARY
06/18/2020 Letter INSPECTION SUMMARY
07/02/2020 Letter INSPECTION SUMMARY
Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home