Permit Application Status

PRCOM20191560


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20191560
Building Permit - Commercial
Final Completion
TRENT OVERHUE
ALTERATION COMMERCIAL
WHITE BOX FOR FUTURE TENANT
06/14/2019
07/10/2019
12/17/2019
11/19/2019
Locations
Contacts
TRENT OVERHUE, Address:601 E SOUTH ST, Phone:(402) 659-3540  
HORIZON CONTRACTING LLC, Address:221 S SECOND STREET, Phone:(816) 565-2173  
FOX ARCHITECTS, Address:1 MEMORIAL DR, SUITE 1800, Phone:(314) 621-4343  
RODINA COMPANY INC, Address:1204 N 59TH ST, Phone:(913) 334-5336  
RODINA COMPANY INC, Address:1204 N 59TH ST, Phone:(913) 334-5336  
RODINA COMPANY INC, Address:1204 N 59TH ST, Phone:(913) 334-5336  
  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 07/11/2019 07/09/2019
Joe Frogge
LC - General Contractor
Resolved
07/09/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 7/9/19 - Acknowledged in letter.
LC - MEP Subs
Resolved
07/09/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 7/9/19 - Acknowledged in letter.
Building Plan Review Approved with Conditions 07/11/2019 07/09/2019
Joe Frogge
Plan Submittal 2012 Codes
Resolved
07/09/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update code references.
Suite address
Resolved
07/09/2019

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: This suite as submitted is addressed 300 SW Blue Pkwy, Unit:B & Unit:C. Update your files. (FYI - Harbor Freight is Unit:A & Planet Fitness is Unit:D & Unit:E)
License Tax Application
Resolved
07/09/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Miscellaneous Correction
Resolved
07/09/2019

Neighboring tenants are both designated as Occupancy Classification B. Action required: Update references. Planet Fitness is an A3. Harbor Freight is an M.
Miscellaneous Correction
Resolved
07/09/2019

2017 NEC Article 230.2 Number of Services. A building or other structure served shall be supplied by only one service unless permitted in 230.2(A) through (D). For the purpose of 230.40, exception No. 2 only, underground sets of conductors, 1/0 AWG and larger, running to the same location and connected together at their supply end but not connected together at their load end shall be considered to be one service. (see code for specific conditions) Action required: Provide verification that new service is appropriately grouped with building electrical services and that the maximum number of disconnects is not exceeded.
Screening - Rooftop equipment
Corrective Action Required
07/03/2019

Unified Development Ordinance Article 8, Section 8.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Comment is for informational purposes. To be field verified.
Miscellaneous Correction
Corrective Action Required
07/03/2019

This review is for a white box only. Action required: Comment is for informational purposes. This review does not establish any type of occupancy or evaluate code compliance in regard to any type of occupancy.
Fire Plan Review Approved with Conditions 07/11/2019 07/08/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
07/03/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of stamped shop drawings for any modifications to the alarm system.
Address numbers required
Corrective Action Required
07/03/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address front and back exit doors.
Construction documents - Fire protection systems
Corrective Action Required
07/03/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of stamped shop drawings for any modifications to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
07/03/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
07/03/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Mount fire extinguishers per sheet LS-0.1
Misc
Resolved
07/08/2019

(Informational Purposes) Follow 2018 IFC Codes
Duct smoke detectors
Corrective Action Required
07/03/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Action Required) Provide duct detection with units over 2000 CFM.
Door operations
Corrective Action Required
07/03/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Informational Purposes)
Illumination required
Corrective Action Required
07/03/2019

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Verified At Inspection) Provide exterior emergency lighting at all exits and exit ramps or stairwells.
Building Plan Review Rejected 06/26/2019 06/20/2019
Joe Frogge
Plan Submittal 2012 Codes
Corrective Action Required
06/20/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update code references.
Suite address
Corrective Action Required
06/20/2019

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: This suite as submitted is addressed 300 SW Blue Pkwy, Unit:B & Unit:C. Update your files. (FYI - Harbor Freight is Unit:A & Planet Fitness is Unit:D & Unit:E)
License Tax Application
Corrective Action Required
06/20/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Miscellaneous Correction
Corrective Action Required
06/20/2019

Neighboring tenants are both designated as Occupancy Classification B. Action required: Update references. Planet Fitness is an A3. Harbor Freight is an M.
Miscellaneous Correction
Corrective Action Required
06/20/2019

2017 NEC Article 230.2 Number of Services. A building or other structure served shall be supplied by only one service unless permitted in 230.2(A) through (D). For the purpose of 230.40, exception No. 2 only, underground sets of conductors, 1/0 AWG and larger, running to the same location and connected together at their supply end but not connected together at their load end shall be considered to be one service. (see code for specific conditions) Action required: Provide verification that new service is appropriately grouped with building electrical services and that the maximum number of disconnects is not exceeded.
Screening - Rooftop equipment
Corrective Action Required
06/20/2019

Unified Development Ordinance Article 8, Section 8.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Comment is for informational purposes. To be field verified.
Miscellaneous Correction
Corrective Action Required
06/20/2019

This review is for a white box only. Action required: Comment is for informational purposes. This review does not establish any type of occupancy or evaluate code compliance in regard to any type of occupancy.
Licensed Contractors Rejected 06/26/2019 06/20/2019
Joe Frogge
LC - General Contractor
Corrective Action Required
06/20/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
06/20/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 06/26/2019 06/19/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
06/19/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of stamped shop drawings for any modifications to the alarm system.
Address numbers required
Corrective Action Required
06/19/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Action Required) Address front and back exit doors.
Construction documents - Fire protection systems
Corrective Action Required
06/19/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of stamped shop drawings for any modifications to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
06/19/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/19/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Mount fire extinguishers per sheet LS-0.1
Misc
Corrective Action Required
06/19/2019

(Informational Purposes) Follow 2018 IFC Codes
Duct smoke detectors
Corrective Action Required
06/19/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Action Required) Provide duct detection with units over 2000 CFM.
Door operations
Corrective Action Required
06/19/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Informational Purposes)
Illumination required
Corrective Action Required
06/19/2019

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide exterior emergency lighting at all exits and exit ramps or stairwells.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $400.00 $400.00 Paid 07/10/2019
8331507-Sewer Connection Fee $240.00 $240.00 Paid 07/10/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 8/21/2019 at 3:25 PM 08/21/2019
Misc
Corrective Action Required
08/21/2019
CONFIGURATION OF RESTROOMS, AS BUILT, NOT PER APPROVED DRAWINGS ON SITE
In-wall Inspection Failed 9/11/2019 at 11:25 AM 09/11/2019
Misc
Corrective Action Required
08/21/2019
NO CITY-APPROVED DRAWINGS FOUND ON SITE FOR RESTROOMS INCLUDED IN THE SCOPE OF THIS PERMIT.
Electrical Service Inspection Failed 9/23/2019 at 11:15 AM 09/23/2019
Misc
Corrective Action Required
09/23/2019
CITY-STAMPED PERMIT PRINTS TO BE ON SITE FOR INSPECTION.
Misc
Corrective Action Required
09/23/2019
COMPLETE WIRING AT SERVICE EQUIPMENT BEFORE REQUESTING SERVICE INSPECTION.
Electrical Service Inspection Passed 9/24/2019 9/24/2019 at 1:05 PM 09/24/2019
Misc
Resolved
09/24/2019
CITY-STAMPED PERMIT PRINTS TO BE ON SITE FOR INSPECTION.
Misc
Resolved
09/24/2019
COMPLETE WIRING AT SERVICE EQUIPMENT BEFORE REQUESTING SERVICE INSPECTION.
In-wall Inspection Passed 11/18/2019
Misc
Resolved
11/18/2019
NO CITY-APPROVED DRAWINGS FOUND ON SITE FOR RESTROOMS INCLUDED IN THE SCOPE OF THIS PERMIT.
Final Inspection - Commercial Passed 11/19/2019 at 3:00 PM 11/19/2019
Documents & Images
Date Uploaded File Type Document Name
06/14/2019 Letter License Tax Not Applicable
06/19/2019 Letter Fire Building Plan Review
06/20/2019 Letter DS P/R Corrections Document
07/08/2019 Letter Fire Building Plan Review
07/09/2019 Letter Codes Plan Review Conditions
07/10/2019 Receipt Receipt for transaction: 2019-004689
07/10/2019 Letter Codes Building Permit
08/19/2019 design coordination
08/21/2019 Letter INSPECTION SUMMARY
09/23/2019 Letter INSPECTION SUMMARY
09/24/2019 Letter INSPECTION SUMMARY
11/19/2019 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home