Permit Application Status

PRCOM20191460


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20191460
Building Permit - Commercial
Certificate of Occupancy
LS INVESTORS ONE LLC
CHANGE OF TENANT
TENANT FINISH FOR HAIR SALON
06/06/2019
07/16/2019
12/10/2019
10/24/2019
Locations
Contacts
LS INVESTORS ONE LLC, Address:1220 WASHINGTON ST PO BOX 411299  
3F30 ARCHITECTS, Address:7501 NW TIFFANY SPRINGS PARKWAY STE 240, Phone:(816) 801-7070  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
EMPOWERED ELECTRIC , Address:110 E 13TH AVE, Phone:(816) 401-8949  
STEVE THE PLUMBER INC, Address:601 S STELLA, Phone:(913) 226-6140  
3F30 ARCHITECTS, Address:7501 NW TIFFANY SPRINGS PARKWAY STE 240, Phone:(816) 801-7070  
EVARDY CONSTRUCTION LLC, Address:7111 W 151ST ST STE 375, Phone:(816) 729-5780  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 08/21/2019
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
08/21/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing for the fire alarm. Testing must be complete before a final occupancy inspection can take place.
Sprinkler Plan Review Released for Construction 08/14/2019
Michael Weissenbach
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
08/14/2019

2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. (Action Required) Maintain sprinkler system during construction. Current annual tag on riser.
Licensed Contractors Approved 06/26/2019 07/16/2019
Development Center
LC - MEP Subs
Corrective Action Required
06/19/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved 06/26/2019 06/21/2019
Joe Frogge
Bldg - Construction classification 602.1
Resolved
06/20/2019

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update code analysis to show correct construction type which is 5B.
Bldg - Occupant load calculations - Increased 1004.2
Resolved
06/20/2019

2018 IBC 1004.5.1 - Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are also met based on such modified number and the occupant load does not exceed one occupant per 7 square feet of occupiable floor space. Where required by the building official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building official, such diagram shall be posted. Action required: Update occupant load calculation to show at least 2 occupants per station plus waiting if applicable.
Plumb - Minimum number of fixtures 403.1
Resolved
06/21/2019

2018 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Action required: Provide additional water closet for males. 6/20/19 - waiting on CMR 6/21/19 - CMR approved
Accessibility - Turning space 603.2.1
Resolved
06/20/2019

ICC A117.1-2017 Section 304.3 Size. Turning spaces shall comply with Section 304.3.1 or 304.3.2. 304.3.1 Circular Space. 304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) 304.3.1.2 Existing buildings and facilities. In existing buildings and facilities, the turning space shall be a circular space with a 60-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Provide minimum 67" radius turning space in new restrooms and spaces. (existing restrooms may still use the 60")
Miscellaneous Correction
Resolved
06/20/2019

2018 IBC 1008.2.3 Exit discharge. Illumination shall be provided along the path of travel for the exit discharge from each exit to the public way. (see code for exceptions) 2018 IBC 1008.3 – Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior side of exits.
Miscellaneous Correction
Resolved
06/20/2019

2018 IMC 501.2 Independent system required. Single or combined mechanical exhaust systems for environmental air shall be independent of all other exhaust systems. (see code for additional information) Action required: Restroom exhaust fans must have backflow dampers.
Fire Plan Review Approved with Conditions 06/26/2019 06/20/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
06/19/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide shop drawings for any modifications to the fire alarm system.
Tenant identification
Corrective Action Required
06/19/2019

2018 IFC 403.11.1.5 - Tenant identification. Each occupied tenant space provided with a secondary exit to the exterior or exit corridor shall be provided with tenant identification by business name and/or address. Letters and numbers shall be posted on the corridor side of the door, be plainly legible and shall contrast with their background. (Verified At Inspection)
Address numbers required
Corrective Action Required
06/19/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address exterior doors with 1160.
Construction documents - Fire protection systems
Corrective Action Required
06/19/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide shop drawings for any modifications to the fire sprinkler system
Installation acceptance testing
Corrective Action Required
06/19/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call 969-1300 to schedule testing.
Portable fire extinguishers - general
Corrective Action Required
06/19/2019

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. (Verified At Inspection)
Duct smoke detectors
Corrective Action Required
06/19/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Verified At Inspection)
Door operations
Corrective Action Required
06/19/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Verified At Inspection)
Illumination required
Corrective Action Required
06/19/2019

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Verified At Inspection) Provide exterior emergency lighting at exits if not existing.
Building Plan Review Rejected 06/18/2019 06/13/2019
Joe Frogge
Bldg - Construction classification 602.1
Corrective Action Required
06/13/2019

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update code analysis to show correct construction type which is 5B.
Bldg - Occupant load calculations - Increased 1004.2
Corrective Action Required
06/13/2019

2018 IBC 1004.5.1 - Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are also met based on such modified number and the occupant load does not exceed one occupant per 7 square feet of occupiable floor space. Where required by the building official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building official, such diagram shall be posted. Action required: Update occupant load calculation to show at least 2 occupants per station plus waiting if applicable.
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
06/13/2019

2018 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Action required: Provide additional water closet for males.
Accessibility - Turning space 603.2.1
Corrective Action Required
06/13/2019

ICC A117.1-2017 Section 304.3 Size. Turning spaces shall comply with Section 304.3.1 or 304.3.2. 304.3.1 Circular Space. 304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) 304.3.1.2 Existing buildings and facilities. In existing buildings and facilities, the turning space shall be a circular space with a 60-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Provide minimum 67" radius turning space in new restrooms and spaces. (existing restrooms may still use the 60")
Miscellaneous Correction
Corrective Action Required
06/13/2019

2018 IBC 1008.2.3 Exit discharge. Illumination shall be provided along the path of travel for the exit discharge from each exit to the public way. (see code for exceptions) 2018 IBC 1008.3 – Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior side of exits.
Miscellaneous Correction
Corrective Action Required
06/13/2019

2018 IMC 501.2 Independent system required. Single or combined mechanical exhaust systems for environmental air shall be independent of all other exhaust systems. (see code for additional information) Action required: Restroom exhaust fans must have backflow dampers.
Licensed Contractors Rejected 06/18/2019 06/13/2019
Joe Frogge
LC - MEP Subs
Corrective Action Required
06/13/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 06/18/2019 06/12/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
06/12/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide shop drawings for any modifications to the fire alarm system.
Tenant identification
Corrective Action Required
06/12/2019

2018 IFC 403.11.1.5 - Tenant identification. Each occupied tenant space provided with a secondary exit to the exterior or exit corridor shall be provided with tenant identification by business name and/or address. Letters and numbers shall be posted on the corridor side of the door, be plainly legible and shall contrast with their background. (Verified At Inspection)
Address numbers required
Corrective Action Required
06/12/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Action Required) Address exterior doors with 1160.
Construction documents - Fire protection systems
Corrective Action Required
06/12/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide shop drawings for any modifications to the fire sprinkler system
Installation acceptance testing
Corrective Action Required
06/12/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Action Required) Call 969-1300 to schedule testing.
Portable fire extinguishers - general
Corrective Action Required
06/12/2019

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. (Informational Purposes)
Duct smoke detectors
Corrective Action Required
06/12/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Informational Purposes)
Door operations
Corrective Action Required
06/12/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Informational Purposes)
Illumination required
Corrective Action Required
06/12/2019

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide exterior emergency lighting at exits if not existing.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $1,620.00 $1,620.00 Paid 07/16/2019
$0.00
7232302-Commercial License Tax Fee $4,905.00 $4,905.00 Paid 06/11/2019
$4,905.00
8331507-Sewer Connection Fee $1,020.00 $1,020.00 Paid 07/16/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 7/17/2019 7/17/2019 at 8:15 AM 07/17/2019
Misc
Corrective Action Required
07/17/2019
PERMIT PRINTS NOT ON SITE
Underslab Plumbing Inspection - Commercial Partial 7/18/2019 7/18/2019 at 8:55 AM 07/18/2019
Misc
Partial Correction
07/18/2019
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING EXCEPT AT SPACES 113; 115; 116 REVISED ENGINEER DRAWING TO BE SUBMITTED TO REFLECT SIGNIFICANT MODIFICATION OF BUILDING DRAIN CONFIGURATION ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Underslab Plumbing Inspection - Commercial Partial 7/19/2019 7/19/2019 at 7:45 AM 07/19/2019
Misc
Partial Correction
07/18/2019
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING EXCEPT AT SPACES 113; 115; 116 REVISED ENGINEER DRAWING TO BE SUBMITTED TO REFLECT SIGNIFICANT MODIFICATION OF BUILDING DRAIN CONFIGURATION ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Underslab Plumbing Inspection - Commercial Passed 7/19/2019 at 10:10 AM 07/19/2019
Misc
Resolved
07/19/2019
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING EXCEPT AT SPACES 113; 115; 116 REVISED ENGINEER DRAWING TO BE SUBMITTED TO REFLECT SIGNIFICANT MODIFICATION OF BUILDING DRAIN CONFIGURATION ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
In-wall Inspection Partial 8/7/2019 8/7/2019 at 8:50 AM 08/07/2019
Misc
Partial Correction
08/07/2019
AFTER MC CABLE IS SECURED WITHIN 12" OF BOXES OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 101-103; 105; 107-108; 110; 119-128;
In-wall Inspection Partial 8/9/2019 8/9/2019 at 10:10 AM 08/09/2019
Misc
Partial Correction
08/07/2019
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL & BULKHEAD FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: LOBBY; 101-103; 105; 107-108; 110; 119-128; [104; 106; 109; 111-113; 115; 116; COLOR PROCESS; LAUN/BRK/UTIL
Above Ceiling Inspection Partial 8/21/2019 8/21/2019 at 2:20 PM 08/21/2019
Misc
Partial Correction
08/21/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS AT THE FOUR CORNERS OF CORRIDOR;
Above Ceiling Inspection Partial 8/22/2019 at 7:00 AM 08/22/2019
Misc
Partial Correction
08/21/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS AT THE FOUR CORNERS OF CORRIDOR; SOFFITS AT VESTIBULE;
Gas Piping Inspection - Commercial Partial 8/26/2019 8/26/2019 at 9:50 AM 08/26/2019
Misc
Corrective Action Required
08/26/2019
LSCO 7-608: GAS PIPING PRESSURE TEST BELOW LEE'S SUMMIT 10 PSI REQUIRED MINIMUM
Misc
Partial Correction
08/26/2019
NO ISSUES FOUND WITH NEW ROOFTOP PIPING EXCEPT CONNECTION TO UNIT YET TO BE COMPLETED
Gas Service Inspection - Commercial Passed 8/28/2019 8/28/2019 at 9:35 AM 08/28/2019
Above Ceiling Inspection Partial 9/6/2019 9/6/2019 at 7:05 AM 09/06/2019
Misc
Partial Correction
08/22/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS AT THE FOUR CORNERS OF CORRIDOR; SOFFITS AT VESTIBULE;
Misc
Partial Correction
09/06/2019
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: CORRIDORS;
Misc
Corrective Action Required
09/06/2019
REMOVE ABANDONED MATERIAL SUCH AS ROD AND STRAP HANGERS
Misc
Corrective Action Required
09/06/2019
REMOVE TEMPORARY ELECTRICAL WIRING
Misc
Corrective Action Required
09/06/2019
SPRINKLER HEAD DROPS TO BE IN POSITION
Misc
Corrective Action Required
09/06/2019
COMPLETE MAKE-UP OF WIRING AT ELECTRICAL BOXES. REMOVE UNUSED BOX CONNECTORS. PLUG UNUSED OPENINGS IN BOXES. CLOSE BOXES. ENSURE BOXES ARE SUPPORTED.
Misc
Corrective Action Required
09/06/2019
SECURE MC CABLE WITHIN ~12" OF BOX ENTRY - EXCEPT FIXTURE WHIPS NOT LONGER THAN 6'
Misc
Corrective Action Required
09/06/2019
PERMANENT CAP ABANDONED WATER LINE BRANCH
Misc
Corrective Action Required
09/06/2019
Misc
Corrective Action Required
09/06/2019
ENSURE ALL LOW-VOLTAGE WIRING IS SUPPORTED MINIMUM 18" ABOVE GRID
Above Ceiling Inspection Partial 9/10/2019 9/10/2019 at 11:15 AM 09/10/2019
Misc
Partial Correction
09/06/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS AT THE FOUR CORNERS OF CORRIDOR; SOFFITS AT VESTIBULE; BORDERS LESS THAN 2' IN ROOMS EXCEPT AT COLOR PROCESSING, RESTROOMS, AND UTILITY CLOSET
Misc
Partial Correction
09/06/2019
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: CORRIDORS;
Misc
Corrective Action Required
09/06/2019
REMOVE ABANDONED MATERIAL SUCH AS ROD AND STRAP HANGERS
Misc
Corrective Action Required
09/06/2019
REMOVE TEMPORARY ELECTRICAL WIRING
Misc
Corrective Action Required
09/06/2019
SPRINKLER HEAD DROPS TO BE IN POSITION
Misc
Corrective Action Required
09/06/2019
COMPLETE MAKE-UP OF WIRING AT ELECTRICAL BOXES. REMOVE UNUSED BOX CONNECTORS. PLUG UNUSED OPENINGS IN BOXES. CLOSE BOXES. ENSURE BOXES ARE SUPPORTED.
Misc
Corrective Action Required
09/06/2019
SECURE MC CABLE WITHIN ~12" OF BOX ENTRY - EXCEPT FIXTURE WHIPS NOT LONGER THAN 6'
Misc
Corrective Action Required
09/06/2019
PERMANENT CAP ABANDONED WATER LINE BRANCH
Misc
Corrective Action Required
09/06/2019
Misc
Corrective Action Required
09/06/2019
ENSURE ALL LOW-VOLTAGE WIRING IS SUPPORTED MINIMUM 18" ABOVE GRID
Above Ceiling Inspection Partial 9/12/2019 9/12/2019 at 11:15 AM 09/12/2019
Misc
Partial Correction
09/10/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS AT THE FOUR CORNERS OF CORRIDOR; SOFFITS AT VESTIBULE;
Misc
Partial Correction
09/10/2019
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: CORRIDORS; ALL ROOMS EXCEPT COLOR PROCESSING, RESTROOMS, UTILITY CLOSET, AND 123
Misc
Resolved
09/12/2019
REMOVE ABANDONED MATERIAL SUCH AS ROD AND STRAP HANGERS
Misc
Corrective Action Required
09/10/2019
REMOVE REMAINING TEMPORARY ELECTRICAL WIRING. LEAVE OUT TILES FOR VERIFICATION.
Misc
Resolved
09/12/2019
SPRINKLER HEAD DROPS TO BE IN POSITION
Misc
Resolved
09/12/2019
COMPLETE MAKE-UP OF WIRING AT ELECTRICAL BOXES. REMOVE UNUSED BOX CONNECTORS. PLUG UNUSED OPENINGS IN BOXES. CLOSE BOXES. ENSURE BOXES ARE SUPPORTED.
Misc
Resolved
09/12/2019
SECURE MC CABLE WITHIN ~12" OF BOX ENTRY - EXCEPT FIXTURE WHIPS NOT LONGER THAN 6'
Misc
Resolved
09/12/2019
PERMANENT CAP ABANDONED WATER LINE BRANCH
Misc
Resolved
09/12/2019
Misc
Resolved
09/12/2019
ENSURE ALL LOW-VOLTAGE WIRING IS SUPPORTED MINIMUM 18" ABOVE GRID
In-wall Inspection Passed 09/12/2019
Misc
Resolved
09/12/2019
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL & BULKHEAD FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: LOBBY; 101-103; 105; 107-108; 110; 119-128; [104; 106; 109; 111-113; 115; 116; COLOR PROCESS; LAUN/BRK/UTIL
Miscellaneous Inspection Partial 9/23/2019 at 7:30 AM 09/23/2019
Above Ceiling Inspection Passed 9/24/2019 9/24/2019 at 7:15 AM 09/24/2019
Misc
Resolved
09/24/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS AT THE FOUR CORNERS OF CORRIDOR; SOFFITS AT VESTIBULE;
Misc
Resolved
09/24/2019
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: CORRIDORS; ALL ROOMS EXCEPT COLOR PROCESSING, RESTROOMS, UTILITY CLOSET, AND 123
Misc
Resolved
09/24/2019
REMOVE REMAINING TEMPORARY ELECTRICAL WIRING. LEAVE OUT TILES FOR VERIFICATION.
Miscellaneous Inspection Partial 9/27/2019 at 11:20 AM 09/27/2019
Miscellaneous Inspection Partial 9/30/2019 at 3:05 PM 09/30/2019
Miscellaneous Inspection Partial 10/7/2019 at 7:05 AM 10/07/2019
Miscellaneous Inspection Partial 10/8/2019 at 10:15 AM 10/08/2019
Miscellaneous Inspection Partial 10/9/2019 at 7:20 AM 10/09/2019
Alarm Test Failed 10/9/2019 10/09/2019
Gas Piping Inspection - Commercial Passed 8/28/2019 10/09/2019
Misc
Resolved
10/09/2019
LSCO 7-608: GAS PIPING PRESSURE TEST BELOW LEE'S SUMMIT 10 PSI REQUIRED MINIMUM
Misc
Resolved
10/09/2019
NO ISSUES FOUND WITH NEW ROOFTOP PIPING EXCEPT CONNECTION TO UNIT YET TO BE COMPLETED
Miscellaneous Inspection Passed 10/9/2019 10/09/2019
Occupancy Inspection - Codes Commercial Failed 10/10/2019 10/10/2019 at 9:05 AM 10/10/2019
Misc
Corrective Action Required
10/10/2019
OBTAIN FIRE DEPARTMENT APPROVAL.
Misc
Corrective Action Required
10/10/2019
FLOOR SINK TO BE SEALED TO FLOOR.
Misc
Corrective Action Required
10/10/2019
GLAZING AT DOOR AT UNIT 108 NOT ETCHED TEMPERED.
Occupancy Inspection - Fire Failed 10/10/2019 10/10/2019 10/10/2019
Alarm Test Failed 10/10/2019 10/10/2019
Occupancy Inspection - Codes Commercial Temporary C of O 10/10/2019 at 10:25 AM 10/10/2019
Misc
Resolved
10/10/2019
OBTAIN FIRE DEPARTMENT APPROVAL.
Misc
Corrective Action Required
10/10/2019
FLOOR SINK TO BE SEALED TO FLOOR.
Misc
Corrective Action Required
10/10/2019
GLAZING AT DOOR AT UNIT 108 NOT ETCHED TEMPERED.
Occupancy Inspection - Fire Passed 10/10/2019 10/10/2019
Alarm Test Passed 10/10/2019 10/10/2019
Occupancy Inspection - Codes Commercial Full C of O 10/24/2019 10/24/2019 at 2:05 PM 10/24/2019
Misc
Resolved
10/24/2019
FLOOR SINK TO BE SEALED TO FLOOR.
Misc
Resolved
10/24/2019
GLAZING AT DOOR AT UNIT 108 NOT ETCHED TEMPERED.
Documents & Images
Date Uploaded File Type Document Name
06/11/2019 Letter License Tax Bill
06/12/2019 Letter Fire Building Plan Review
06/13/2019 Letter DS P/R Corrections Document
06/20/2019 Letter Fire Building Plan Review
06/21/2019 approved CMR
07/08/2019 change of GC
07/16/2019 Letter Codes Plan Review Conditions
07/16/2019 Receipt Receipt for transaction: 2019-004797
07/16/2019 Letter DS Building Permit
07/18/2019 Letter INSPECTION SUMMARY
07/19/2019 Letter INSPECTION SUMMARY
07/19/2019 Letter INSPECTION SUMMARY
08/07/2019 Letter INSPECTION SUMMARY
08/09/2019 Letter INSPECTION SUMMARY
08/14/2019 Letter Fire (Sprinkler) Plan Review
08/21/2019 Letter INSPECTION SUMMARY
08/21/2019 Letter Fire (Alarm) Plan Review Notice
08/22/2019 Letter INSPECTION SUMMARY
08/26/2019 Letter INSPECTION SUMMARY
08/28/2019 Letter INSPECTION SUMMARY
08/28/2019 Letter INSPECTION SUMMARY
09/10/2019 Letter INSPECTION SUMMARY
09/12/2019 Letter INSPECTION SUMMARY
09/12/2019 Letter INSPECTION SUMMARY
09/24/2019 Letter INSPECTION SUMMARY
10/10/2019 Letter INSPECTION SUMMARY
10/10/2019 Letter Codes Temporary Certificate of Occupancy
10/24/2019 Letter Field Certificate of Occupancy
10/25/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home