Permit Application Status

PRCOM20191276


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20191276
Building Permit - Commercial
Final Completion
Summit Development Co
ALTERATION COMMERCIAL
CONSTRUCTION OF A WALL TO SEPARATE EXISTING RETAIL SPACE INTO WHITE BOXES *drawing is in plan review file
05/17/2019
07/01/2019
07/16/2019
Locations
Contacts
Summit Development Co, Address:700 W 47th St Ste 200  
KESSINGER HUNTER & CO LC, Address:2600 GRAND #700, Phone:(816) 842-2690  
KIRK BOND ARCHITECT, Address:12300 EAST 46TH TERRACE SOUTH, Phone:(816) 808-9952  
DWATERS@KESSINGERHUNTER.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 05/30/2019 05/22/2019
Joe Frogge
Fire Plan Review Approved with Conditions 05/30/2019 05/20/2019
Joe Dir
Construction documents - Fire protection systems
Corrective Action Required
05/20/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings of any modification to be done to the fire sprinkler system.
Misc
Corrective Action Required
05/20/2019

Wall construction: ACTION REQUIRED: Wall construction shall not obstruct any fire sprinkler heads. 4" minimum clearnace from a sprinkler head is required. Consult a fire sprinkler system company to make sure proper coverage is maintained in both tenant spaces and if any heads are to be relocated.
Address numbers required
Corrective Action Required
05/20/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) The exterior of each door leading into each tenant space shall be posted with the tenant address. Addressing shall be readable from the roadway.
Portable fire extinguishers - general
Corrective Action Required
05/20/2019

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide a minimum of two 2A-10 BC fire extinguishers for the new tenant space. Extingusihers are to be mounted on a wall on a normal path of travel close to an exit.
Licensed Contractors Approved 05/30/2019 05/17/2019
Kim Brennan
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $30.00 $30.00 Paid 07/01/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Framing Inspection - Commercial Passed 7/2/2019 7/2/2019 at 9:00 AM 07/02/2019
Rated Assembly Inspection Partial 7/2/2019 7/2/2019 at 9:11 AM 07/02/2019
Miscellaneous Correction
Partial Correction
07/02/2019
201 unit screws every 6" on seams and 12" field. okay to tape mud 201 side only.
Rated Assembly Inspection Passed 7/5/2019 7/5/2019 at 9:05 AM 07/05/2019
Miscellaneous Correction
Resolved
07/05/2019
201 unit screws every 6" on seams and 12" field. okay to tape mud 201 side only.
Occupancy Inspection - Fire Passed 7/17/2019 07/17/2019
Final Inspection - Commercial Passed 7/17/2019 7/17/2019 07/17/2019
Documents & Images
Date Uploaded File Type Document Name
05/20/2019 Letter Fire Building Plan Review
05/22/2019 Letter Codes Plan Review Conditions
07/01/2019 Receipt Receipt for transaction: 2019-004407
07/01/2019 Letter Codes Building Permit
07/02/2019 Letter INSPECTION SUMMARY
07/02/2019 Letter INSPECTION SUMMARY
07/05/2019 Letter INSPECTION SUMMARY
07/17/2019 Letter INSPECTION SUMMARY
07/17/2019 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home