Permit Application Status

PRCOM20190453


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20190453
Building Permit - Commercial
Final Completion
B & D BUSINESS HOLDINGS LLC
ALTERATION COMMERCIAL
ROOF MOUNTED SOLAR SYSTEM - 59.07kW
03/01/2019
03/11/2019
04/04/2019
Locations
Contacts
B & D BUSINESS HOLDINGS LLC, Address:24000 W 43RD STREET  
MC POWER COMPANIES INC, Address:510 NE 291 HWY, Phone:(816) 251-4700  
AHUFFMAN@MCPOWER.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Department Solar Review Approved 03/06/2019 03/05/2019
Joe Dir
Building Plan Review Approved with Conditions 03/06/2019 03/01/2019
Joe Frogge
Misc
Corrective Action Required
03/01/2019

Structural engineer has placed restrictions on panel installation locations. Action required: Obtain structural engineer's approval of actual installation.
Licensed Contractors Approved 03/01/2019 03/01/2019
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $304.03 $304.03 Paid 03/11/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Failed 3/29/2019 4/1/2019 04/01/2019
Misc
Corrective Action Required
04/01/2019
**SEE FINAL ELECTRICAL**
Final Electrical Inspection - Commercial Failed 3/29/2019 4/1/2019 at 1:15 PM 04/01/2019
Misc
Corrective Action Required
04/01/2019
-FIRE DEPT APPROVAL REQUIRED -BOND THE EAST SET OF PV MODULES TO THE SYSTEM -INSTALL 80 AMP PV BREAKER PER PLAN
Electrical Service Inspection Passed 4/4/2019 4/4/2019 04/04/2019
Misc
Resolved
04/04/2019
**SEE FINAL ELECTRICAL**
Final Electrical Inspection - Commercial Passed 4/4/2019 4/4/2019 at 2:50 PM 04/04/2019
Misc
Resolved
04/04/2019
-FIRE DEPT APPROVAL REQUIRED -BOND THE EAST SET OF PV MODULES TO THE SYSTEM -INSTALL 80 AMP PV BREAKER PER PLAN
Occupancy Inspection - Fire Passed 4/4/2019 04/04/2019
Documents & Images
Date Uploaded File Type Document Name
03/05/2019 Letter Fire Building Plan Review
03/11/2019 Letter Codes Plan Review Conditions
03/11/2019 Receipt Receipt for transaction: 2019-000789
03/11/2019 Letter Codes Building Permit
04/01/2019 Letter INSPECTION SUMMARY
04/04/2019 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home