Permit Application Status

PRCOM20183043


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20183043
Building Permit - Commercial
Certificate of Occupancy
HIBE HOLDINGS LLC
CHANGE OF TENANT
TENANT FINISH FOR ARCADE WITH FULL SERVICE BAR AND SOME FOOD SERVICE **invite planner to final to verify screening of rooftop equipment
09/11/2018
10/02/2018
03/16/2019
05/24/2019
Locations
Contacts
HIBE HOLDINGS LLC, Address:2601 W 68TH ST  
MAIN SLICE, Address:235 SE MAIN ST, Phone:(816) 600-5184  
COLLINS|WEBB ARCHITECTURE, Address:13A SW 3RD STREET, Phone:(816) 249-2270  
MJ INTERIORS, Address:7915 HEMLOCK ST, Phone:(913) 313-6565  
NORTH STAR HOUSING, LLC - ANDREW DANNER, Address:31711 E PINK HILL RD, Phone:(816) 612-5191  
A BRIGHT PLUMBING LLC, Address:201 NE WOODBURY DR, Phone:(816) 867-4540  
AFFINITY CONSTRUCTION & CONTRACTING LLC, Address:32003 E FRISTOE RD, Phone:(816) 785-4090  
MJ INTERIORS, Address:7915 HEMLOCK ST, Phone:(913) 313-6565  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 04/15/2019
Joe Dir
Installation acceptance testing
Corrective Action Required
04/15/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the fire alarm system will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Sprinkler Plan Review Released for Construction 03/15/2019
Joe Dir
Installation acceptance testing
Corrective Action Required
03/15/2019

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) All required field and acceptance testing is required to be completed prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Licensed Contractors Approved 09/24/2018 10/02/2018
Development Center
LC - General Contractor
Resolved
09/24/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
10/02/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 9/24/18 - acknowledged
Fire Plan Review Approved with Conditions 10/01/2018 09/27/2018
Joe Dir
Posting of occupant load
Corrective Action Required
09/24/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(veriifed at inspecrtion) Post the occupant load numbers in the folllowing rooms. Upper Arcade-48, Event Space-55, Arcade-70 Upper Arcade-48
Construction documents for fire alarm systems
Corrective Action Required
09/24/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of the fire alarm system to be installed.
Address numbers required
Corrective Action Required
09/24/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (veriifed at inspection) Address shall be readable from the roadway.
Knox box required
Corrective Action Required
09/24/2018

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. ACTION REQUIRED:(information purposes) Knox Box can be obtained on line at knox.box.com ACTION REQUIRED: (veriifed at inspection) the Knox box is to mounted on a outside wall over the FDC or as close as possible to the Fire Department Connection.
Construction documents - Fire protection systems
Resolved
09/27/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED: (information purposes) Have the fire sprinkler system contractor provide shop drawings of the fire sprinkler system to be installed.
Installation acceptance testing
Resolved
09/27/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Field tests and acceptance testing will be required of the Type-1 kitchen hood, fire alarm and fire sprinkler systems prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
09/24/2018

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ACTION REQUIRED: (veriifed at inspection) Provide one K-class fire extinguisher for the kitchen area. To be mounted according to the description above.
Portable fire extinguishers - general
Corrective Action Required
09/24/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide a minimum of three 2A-10BC fire extinguishers. Fire extinguihsers are to mounted on a wall close to an exit.
Misc
Resolved
09/27/2018

(FDC) Fire Department Connection ACTION REQUIRED: (will be deferred) Relocate the location of the FDC off of the egress ramp. Reference NFPA 13 A8.17.2, A8.17.2.1 903.3.7 Fire department connections. The location of fire department connections shall be approved by the fire code official. the connection shall be a 4 inch Stroz type fitting and located within 100 feet of a fire hydrant
Misc
Resolved
09/27/2018

Egress Ramps ACTION REQUIRED: (will be deferred) Relocate the FDC away from the egress ramp. [B] 1003.3.3 Horizontal projections. Structural elements, fixtures or furnishings shall not project horizontally from either side more than 4 inches (102 mm) over any walking surface between the heights of 27 inches (686 mm) and 80 inches (2032 mm) above the walking surface [B] 1008.1.1.1 Projections into clear width. There shall not be projections into the required clear width lower than 34 inches (864 mm) above the floor or ground. Projections into the clear opening width between 34 inches (864 mm) and 80 inches (2032 mm) above the floor or ground shall not exceed 4 inches (102 mm [B] 1010.6.3 Restrictions. Means of egress ramps shall not reduce in width in the direction of egress travel. Projections into the required ramp and landing width are prohibited. Doors opening onto a landing shall not reduce the clear width to less than 42 inches (1067 mm).
Misc
Resolved
09/27/2018

Exit sign ACTION REQUIRED: (verified at inspection) An additional (exit sign) needed for the Event Spaces required second exit.
Misc
Corrective Action Required
09/27/2018

Exterior exit illumination ACTION REQUIRED: (veriifed at inspection) Provide exterior egress illumination at all exits
Misc
Corrective Action Required
09/24/2018

Exterior ramp illumination ACTION REQUIRED: (verified at inspection) Provide exterior illumination for all exterior egress ramps
Building Plan Review Approved with Conditions 10/01/2018 09/24/2018
Joe Frogge
License Tax Application
Corrective Action Required
09/24/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 9/24/18 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
09/24/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 9/24/18 - acknowledged in letter
Code analysis required
Resolved
09/24/2018

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: This building was originally built as a VB, not IIB as shown. We can reclassify if that is your intention. Clarify.
Misc
Corrective Action Required
09/24/2018

Unified Development Ordinance Section 7.440. Development and Renovation within the Downtown Core Area A) Preliminary and Final Development Plans. Applications for new development or redevelopment of any commercial or mixed use property in the Downtown Core Area shall be reviewed through the preliminary development plan and final development plan application, modification and appeal processes as set forth in Article 4, Applications and Procedures, of this Chapter. B) Exterior Renovation Permit. An Exterior Renovation Permit is required for all exterior work in the Downtown Core Area when the Design Standards of this Division apply, but the preliminary and final development plan review processes of Article 4 do not apply, and as otherwise provided herein. The applicability of the Design Standards is described in detail in sections 7.450(A) and 7.460(A) of this Division. 1 ) Requirements a) For example, an Exterior Renovation Permit shall be required prior to any rehabilitation, remodeling, or construction of a building addition, for any exterior work on any building located in the Downtown Core Area, as defined herein. (refer to the Unified Development Ordinance for additional information) Action required: Contact Shannon McGuire for information regarding exterior renovation permits and approval. Shannon.McGuire@CityofLS.net 816.969.1600 9/24/18 - acknowledged in letter
Plumb - Fixture calculations 403.1.1
Resolved
09/24/2018

2012 IPC 403.1.1 Fixture calculations. To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table 403.1. Fractional numbers resulting from applying the fixture ratios of Table 403.1 shall be rounded up to the next whole number. For calculations involving multiple occupancies, such fractional numbers for each occupancy shall be first be summed and then rounded up to the next whole number. (see code section for exception) Action required: Factor used for lavatory calcs incorrect. Should be 75, not 200.
Misc
Resolved
09/24/2018

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide verification that rooftop equipment is accessible or provide permanent access. 9/24/18 - per architect, portion of roof edge is less than 16" high
Misc
Resolved
09/24/2018

2012 IMC 501.3.1 Location of exhaust outlets. The termination point of exhaust outlets and ducts discharging to the outdoors shall be located with the following minimum distances: (see code for items 1, 2, 4, & 5) 3. For all environmental air exhaust: 3 feet from property lines; 3 feet from operable openings into building for all occupancies other than Group U, and 10 feet from mechanical air intakes. Such exhaust shall not be considered hazardous or noxious. Action required: Kitchen hood exhaust fan to be minimum 10' from makeup air unit intake.
Misc
Resolved
09/24/2018

A new 1-1/2" water meter has been requested but there is no mention of the existing meters. This site is currently served by (1) 1" and (1) 5/8" meter. Action required: Clarify. Water Department will allow the (2) meters to remain if requested.
Bldg - Illumination required 1006.1
Resolved
09/24/2018

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide emergency lighting at exterior side of exits.
Misc
Resolved
09/24/2018

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide convenience power on roof to comply.
Plan Submittal 2012 Codes
Resolved
09/24/2018

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Update code reference at kitchen fan KEF-1 schedule to comply. (we are on 2011 NEC)
Health Department Review Approved 09/17/2018
Joe Frogge
Fire Plan Review Rejected 09/21/2018 09/13/2018
Joe Dir
Posting of occupant load
Corrective Action Required
09/13/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(veriifed at inspecrtion) Post the occupant load numbers in the folllowing rooms. Upper Arcade-48, Event Space-55, Arcade-70 Upper Arcade-48
Construction documents for fire alarm systems
Corrective Action Required
09/13/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of the fire alarm system to be installed.
Address numbers required
Corrective Action Required
09/13/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(veriifed at inspection) Address shall be readable from the roadway.
Knox box required
Corrective Action Required
09/13/2018

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. ACTION REQUIRED:(information purposes) Knox Box can be obtained on line at knox.box.com ACTION REQUIRED:(veriifed at inspection) the Knox box is to mounted on a outside wall over the FDC or as close as possible to the Fire Department Connection.
Construction documents - Fire protection systems
Corrective Action Required
09/13/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings of the fire sprinkler system to be installed.
Installation acceptance testing
Corrective Action Required
09/13/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Field tests and acceptance testing will be required of the Type-1 kitchen hood, fire alarm and fire sprinkler systems prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
09/13/2018

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ACTION REQUIRED:(veriifed at inspection) Provide one K-class fire extinguisher for the kitchen area. To be mounted according to the description above.
Portable fire extinguishers - general
Corrective Action Required
09/13/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide a minimum of three 2A-10BC fire extinguishers. Fire extinguihsers are to mounted on a wall close to an exit.
Misc
Corrective Action Required
09/13/2018

(FDC) Fire Department Connection ACTION REQUIRED:Relocate the location of the FDC off of the egress ramp. Reference NFPA 13 A8.17.2, A8.17.2.1 903.3.7 Fire department connections. The location of fire department connections shall be approved by the fire code official. the connection shall be a 4 inch Stroz type fitting and located within 100 feet of a fire hydrant
Misc
Corrective Action Required
09/13/2018

Egress Ramps ACTION REQUIRED: Relocate the FDC away from the egress ramp. [B] 1003.3.3 Horizontal projections. Structural elements, fixtures or furnishings shall not project horizontally from either side more than 4 inches (102 mm) over any walking surface between the heights of 27 inches (686 mm) and 80 inches (2032 mm) above the walking surface [B] 1008.1.1.1 Projections into clear width. There shall not be projections into the required clear width lower than 34 inches (864 mm) above the floor or ground. Projections into the clear opening width between 34 inches (864 mm) and 80 inches (2032 mm) above the floor or ground shall not exceed 4 inches (102 mm [B] 1010.6.3 Restrictions. Means of egress ramps shall not reduce in width in the direction of egress travel. Projections into the required ramp and landing width are prohibited. Doors opening onto a landing shall not reduce the clear width to less than 42 inches (1067 mm).
Misc
Corrective Action Required
09/13/2018

Exit sign ACTION REQUIRED:An additional (exit sign) needed for the Event Spaces required second exit. [B] 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit or the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Misc
Corrective Action Required
09/13/2018

Exterior exit illumination ACTION REQUIRED:Provide exterior egress illumination at all exits [B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
Misc
Corrective Action Required
09/13/2018

Exterior ramp illumination ACTION REQUIRED: Provide exterior illumination for all exterior egress ramps [B] 1006.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits.
Building Plan Review Rejected 09/21/2018 09/12/2018
Joe Frogge
License Tax Application
Corrective Action Required
09/12/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Resolved
09/17/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
09/12/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Code analysis required
Corrective Action Required
09/12/2018

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: This building was originally built as a VB, not IIB as shown. We can reclassify if that is your intention. Clarify.
Misc
Corrective Action Required
09/12/2018

Unified Development Ordinance Section 7.440. Development and Renovation within the Downtown Core Area A) Preliminary and Final Development Plans. Applications for new development or redevelopment of any commercial or mixed use property in the Downtown Core Area shall be reviewed through the preliminary development plan and final development plan application, modification and appeal processes as set forth in Article 4, Applications and Procedures, of this Chapter. B) Exterior Renovation Permit. An Exterior Renovation Permit is required for all exterior work in the Downtown Core Area when the Design Standards of this Division apply, but the preliminary and final development plan review processes of Article 4 do not apply, and as otherwise provided herein. The applicability of the Design Standards is described in detail in sections 7.450(A) and 7.460(A) of this Division. 1 ) Requirements a) For example, an Exterior Renovation Permit shall be required prior to any rehabilitation, remodeling, or construction of a building addition, for any exterior work on any building located in the Downtown Core Area, as defined herein. (refer to the Unified Development Ordinance for additional information) Action required: Contact Shannon McGuire for information regarding exterior renovation permits and approval. Shannon.McGuire@CityofLS.net 816.969.1600
Plumb - Fixture calculations 403.1.1
Corrective Action Required
09/12/2018

2012 IPC 403.1.1 Fixture calculations. To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table 403.1. Fractional numbers resulting from applying the fixture ratios of Table 403.1 shall be rounded up to the next whole number. For calculations involving multiple occupancies, such fractional numbers for each occupancy shall be first be summed and then rounded up to the next whole number. (see code section for exception) Action required: Factor used for lavatory calcs incorrect. Should be 75, not 200.
Misc
Corrective Action Required
09/12/2018

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide verification that rooftop equipment is accessible or provide permanent access.
Misc
Corrective Action Required
09/12/2018

2012 IMC 501.3.1 Location of exhaust outlets. The termination point of exhaust outlets and ducts discharging to the outdoors shall be located with the following minimum distances: (see code for items 1, 2, 4, & 5) 3. For all environmental air exhaust: 3 feet from property lines; 3 feet from operable openings into building for all occupancies other than Group U, and 10 feet from mechanical air intakes. Such exhaust shall not be considered hazardous or noxious. Action required: Kitchen hood exhaust fan to be minimum 10' from makeup air unit intake.
Misc
Corrective Action Required
09/12/2018

A new 1-1/2" water meter has been requested but there is no mention of the existing meters. This site is currently served by (1) 1" and (1) 5/8" meter. Action required: Clarify. Water Department will allow the (2) meters to remain if requested.
Bldg - Illumination required 1006.1
Corrective Action Required
09/12/2018

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide emergency lighting at exterior side of exits.
Misc
Corrective Action Required
09/12/2018

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide convenience power on roof to comply.
Plan Submittal 2012 Codes
Corrective Action Required
09/12/2018

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Update code reference at kitchen fan KEF-1 schedule to comply. (we are on 2011 NEC)
Licensed Contractors Rejected 09/21/2018 09/12/2018
Joe Frogge
LC - General Contractor
Corrective Action Required
09/12/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
09/12/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $1,000.00 $1,000.00 Paid 10/02/2018
8331507-Sewer Connection Fee $450.00 $450.00 Paid 10/02/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 11/14/2018 11/14/2018 at 8:10 AM 11/14/2018
Misc
Corrective Action Required
11/14/2018
DRAIN LINE DIRECTION AT RESTROOMS NOT PER APPROVED DRAWING.
Misc
Corrective Action Required
11/14/2018
LEAVE ALL NEW PIPING EXPOSED FOR INSPECTION -- INCLUDING CONNECTIONS TO EXISTING BUILDING DRAIN.
Underslab Plumbing Inspection - Commercial Partial 11/16/2018 11/16/2018 11/16/2018
Misc
Resolved
11/16/2018
DRAIN LINE DIRECTION AT RESTROOMS NOT PER APPROVED DRAWING.
Misc
Partial Correction
11/16/2018
KITCHEN AND RESTROOMS APPROVED TO COVER. BAR AREA NOT COMPLETE
Hood/Duct Inspection Partial 1/4/2019 1/4/2019 at 10:40 AM 01/04/2019
Misc
Partial Correction
01/04/2019
HOOD SECTION LIGHT TESTED ON THE GROUND AND APPROVED
Hood/Duct Inspection Partial 1/10/2019 at 11:10 AM 01/10/2019
Misc
Partial Correction
01/04/2019
HOOD SECTION LIGHT TESTED ON THE GROUND AND APPROVED; JOINT WELD AT TOP OF HOOD LIGHT-TESTED OK;
Hood/Duct Inspection Partial 1/17/2019 1/17/2019 at 11:20 AM 01/17/2019
Misc
Partial Correction
01/10/2019
HOOD SECTION LIGHT TESTED ON THE GROUND AND APPROVED; JOINT WELD AT TOP OF HOOD LIGHT-TESTED OK; 1ST LAYER DUCT WRAP OK TO COVER;
Gas Piping Inspection - Commercial Failed 1/31/2019 1/31/2019 at 3:20 PM 01/31/2019
Misc
Corrective Action Required
01/31/2019
LSCO 7-608: GAS PIPING TEST PRESSURE DECREASED DURING MONITORING PERIOD. CORRECT AND PRESSURIZE PIPING SYSTEM TO HOLD STEADY AT MINIMUM 10 PSI
Gas Piping Inspection - Commercial Failed 2/1/2019 2/1/2019 at 11:40 AM 02/01/2019
Misc
Resolved
02/01/2019
LSCO 7-608: GAS PIPING TEST PRESSURE DECREASED DURING MONITORING PERIOD. CORRECT AND PRESSURIZE PIPING SYSTEM TO HOLD STEADY AT MINIMUM 10 PSI
Misc
Corrective Action Required
02/01/2019
PAINT GAS PIPE 100% PER IFGC. COMPLETE INSTALLATION OF PIPE CLAMPS AT SUPPORT BLOCKS.
Gas Service Inspection - Commercial Passed 2/1/2019 at 1:10 PM 02/01/2019
Underslab Plumbing Inspection - Commercial Passed 2/21/2019 2/1/2019 at 1:25 PM 02/01/2019
Misc
Resolved
02/01/2019
KITCHEN AND RESTROOMS APPROVED TO COVER. BAR AREA NOT COMPLETE
In-wall Inspection Failed 2/15/2019 2/15/2019 at 8:20 AM 02/15/2019
Misc
Corrective Action Required
02/15/2019
IPC 305 PROTECTION OF COPPER PIPING AT POTENTIAL CONTACT WITH STEEL OR OTHER DISSIMILAR METALS: ELIMINATE CONTACT; THEN INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL.
Misc
Corrective Action Required
02/15/2019
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE BOCA PLATES). COMPLETE INSTALLATION OF SHIELD PLATES. CHECK ALL.
Misc
Corrective Action Required
02/15/2019
NEC 334-10 SECURING OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES.
Misc
Corrective Action Required
02/15/2019
PONY WALL AT BAR NOT YET READY FOR INSPECTION
Above Ceiling Inspection Failed 2/15/2019 at 8:55 AM 02/15/2019
Misc
Corrective Action Required
02/15/2019
COMPLETE HVAC DUCTWORK
Misc
Corrective Action Required
02/15/2019
IPC 305 PROTECTION OF COPPER PIPING AT POTENTIAL CONTACT WITH STEEL OR OTHER DISSIMILAR METALS: ELIMINATE CONTACT; THEN INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL.
Misc
Corrective Action Required
02/15/2019
IPC 905.2; IRC P3104.2 GRADING OF VENT PIPING TO DRAIN. MAY NOT BE RUN LEVEL.
In-wall Inspection Partial 2/19/2019 2/19/2019 at 8:40 AM 02/19/2019
Misc
Resolved
02/19/2019
IPC 305 PROTECTION OF COPPER PIPING AT POTENTIAL CONTACT WITH STEEL OR OTHER DISSIMILAR METALS: ELIMINATE CONTACT; THEN INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL.
Misc
Resolved
02/19/2019
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE BOCA PLATES). COMPLETE INSTALLATION OF SHIELD PLATES. CHECK ALL.
Misc
Resolved
02/19/2019
NEC 334-10 SECURING OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES.
Misc
Corrective Action Required
02/15/2019
PONY WALL AT BAR NOT YET READY FOR INSPECTION
Above Ceiling Inspection Passed 2/19/2019 at 9:00 AM 02/19/2019
Misc
Resolved
02/19/2019
COMPLETE HVAC DUCTWORK
Misc
Resolved
02/19/2019
IPC 305 PROTECTION OF COPPER PIPING AT POTENTIAL CONTACT WITH STEEL OR OTHER DISSIMILAR METALS: ELIMINATE CONTACT; THEN INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL.
Misc
Resolved
02/19/2019
IPC 905.2; IRC P3104.2 GRADING OF VENT PIPING TO DRAIN. MAY NOT BE RUN LEVEL.
Underslab Plumbing Inspection - Commercial Passed 2/21/2019 2/21/2019 at 8:35 AM 02/21/2019
Underslab Electrical Inspection - Commercial Passed 2/21/2019 at 8:50 AM 02/21/2019
Rough Electrical Inspection - Commercial Partial 2/21/2019 at 9:00 AM 02/21/2019
Misc
Corrective Action Required
02/21/2019
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. CHECK ALL.
Misc
Corrective Action Required
02/21/2019
NEC 314.16; IRC E3905.13 ELECTRICAL BOX FILL: CHECK ALL ELECTRICAL BOXES FOR BOX FILL RESTRICTIONS -- CORRECT AS NEEDED
Misc
Corrective Action Required
02/21/2019
OK TO DEVICE RECEPTACLES AND SWITCHES AND INSTALL LIGHT FIXTURES AT SPACE 107 -- EXCEPT AT WEST WALLS WHERE SPARK RINGS ARE REQUIRED.
Rough Electrical Inspection - Commercial Passed 2/26/2019 2/26/2019 at 10:30 AM 02/26/2019
Misc
Resolved
02/26/2019
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. CHECK ALL.
Misc
Resolved
02/26/2019
NEC 314.16; IRC E3905.13 ELECTRICAL BOX FILL: CHECK ALL ELECTRICAL BOXES FOR BOX FILL RESTRICTIONS -- CORRECT AS NEEDED
Misc
Resolved
02/26/2019
OK TO DEVICE RECEPTACLES AND SWITCHES AND INSTALL LIGHT FIXTURES AT SPACE 107 -- EXCEPT AT WEST WALLS WHERE SPARK RINGS ARE REQUIRED.
Footing Inspection - Commercial Failed 3/1/2019 3/1/2019 at 9:10 AM 03/01/2019
Misc
Corrective Action Required
03/01/2019
RE-BAR NOT IN PLACE
Footing Inspection - Commercial Failed 3/1/2019 at 2:30 PM 03/01/2019
Misc
Corrective Action Required
03/01/2019
RE-BAR NOT IN PLACE
Footing Inspection - Commercial Passed 3/1/2019 at 4:05 PM 03/01/2019
Misc
Resolved
03/01/2019
RE-BAR NOT IN PLACE
In-wall Inspection Passed 3/21/2019 at 7:05 AM 03/21/2019
Misc
Resolved
03/21/2019
PONY WALL AT BAR NOT YET READY FOR INSPECTION
Rough Electrical Inspection - Commercial Passed 4/8/2019 04/08/2019
Misc
Informational
04/08/2019
ROUGH ELECT -electrical behind bar
Above Ceiling Inspection Passed 4/16/2019 4/16/2019 at 1:45 PM 04/16/2019
Miscellaneous Inspection Partial 3/20/2019 4/19/2019 at 11:00 AM 04/19/2019
Miscellaneous Inspection Partial 4/23/2019 at 2:40 PM 04/23/2019
Miscellaneous Inspection Partial 4/30/2019 at 1:10 PM 04/30/2019
Miscellaneous Inspection Partial 5/6/2019 at 2:10 PM 05/06/2019
Miscellaneous Inspection Passed 5/8/2019 05/08/2019
Sprinkler - Hydrostatic Test Passed 5/8/2019 05/08/2019
Alarm Test Passed 5/9/2019 05/09/2019
Occupancy Inspection - Fire Temporary C of O 5/9/2019 05/09/2019
Sprinkler - Flow Test Passed 5/9/2019 05/09/2019
Occupancy Inspection - Planning Passed 5/9/2019 05/09/2019
Gas Piping Inspection - Commercial Passed 5/9/2019 at 1:00 PM 05/09/2019
Misc
Resolved
05/09/2019
PAINT GAS PIPE 100% PER IFGC. COMPLETE INSTALLATION OF PIPE CLAMPS AT SUPPORT BLOCKS.
Occupancy Inspection - Codes Commercial Failed 5/9/2019 5/9/2019 at 1:15 PM 05/09/2019
Misc
Corrective Action Required
05/09/2019
-OBTAIN FIRE DEPARTMENT APPROVAL -REPAIR ASPHALT NEXT TO PATIO WHERE BACKFLOW VAULT IS LOCATED -COMPLETE RAIL AT EAST RAMP -PAY EXCISE TAX -PROTECT GLAZING FROM THE INSIDE NEXT TO D.J. STAIRS (CAN INSTALL LISTED PROTECTED FILM OVER WINDOWS THAT ARE REQUIRED TO BE TEMPERED.) -OBTAIN HEALTH DEPARTMENT APPROVAL OKAY TO STOCK AND TRAIN EMPLOYEES
Occupancy Inspection - Codes Commercial Failed 5/16/2019 at 3:50 PM 05/16/2019
Misc
Corrective Action Required
05/09/2019
- OBTAIN FIRE DEPARTMENT APPROVAL - PAY EXCISE TAX - PROTECT GLAZING NEXT TO EAST RAMP (CAN INSTALL LISTED PROTECTED FILM OVER WINDOWS THAT ARE REQUIRED TO BE TEMPERED.) OKAY TO STOCK AND TRAIN EMPLOYEES
Occupancy Inspection - Codes Commercial Temporary C of O 5/17/2019 at 3:35 PM 05/17/2019
Misc
Corrective Action Required
05/16/2019
- OBTAIN FIRE DEPARTMENT APPROVAL - PROTECT GLAZING NEXT TO EAST RAMP (CAN INSTALL LISTED PROTECTED FILM OVER WINDOWS THAT ARE REQUIRED TO BE TEMPERED.)
Occupancy Inspection - Codes Commercial Full C of O 5/24/2019 at 3:35 PM 05/24/2019
Misc
Resolved
05/24/2019
- OBTAIN FIRE DEPARTMENT APPROVAL - PROTECT GLAZING NEXT TO EAST RAMP (CAN INSTALL LISTED PROTECTED FILM OVER WINDOWS THAT ARE REQUIRED TO BE TEMPERED.)
Occupancy Inspection - Fire Passed 05/29/2019
Documents & Images
Date Uploaded File Type Document Name
09/13/2018 Letter Fire Building Plan Review
09/17/2018 Letter Codes P/R Corrections Document
09/17/2018 RE Water meter at 316 SE Douglas St
09/17/2018 New Food Establishment Plan Review - Approved FTG 0001237
09/27/2018 Letter Fire Building Plan Review
10/02/2018 Receipt Receipt for transaction: 2018-006667
10/02/2018 Letter Codes Building Permit
10/02/2018 Letter Codes Plan Review Conditions
11/14/2018 Letter INSPECTION SUMMARY
11/16/2018 Letter INSPECTION SUMMARY
01/04/2019 Letter INSPECTION SUMMARY
01/10/2019 Letter INSPECTION SUMMARY
01/17/2019 Letter INSPECTION SUMMARY
02/01/2019 Letter INSPECTION SUMMARY
02/01/2019 Letter INSPECTION SUMMARY
02/01/2019 Letter INSPECTION SUMMARY
02/15/2019 Letter INSPECTION SUMMARY
02/15/2019 Letter INSPECTION SUMMARY
02/19/2019 Letter INSPECTION SUMMARY
02/19/2019 Letter INSPECTION SUMMARY
02/21/2019 Letter INSPECTION SUMMARY
02/21/2019 Letter INSPECTION SUMMARY
02/21/2019 Letter INSPECTION SUMMARY
02/26/2019 Letter INSPECTION SUMMARY
03/01/2019 Letter INSPECTION SUMMARY
03/15/2019 Letter Fire (Sprinkler) Plan Review
03/21/2019 Letter INSPECTION SUMMARY
04/15/2019 Letter Fire (Alarm) Plan Review Notice
04/16/2019 Letter INSPECTION SUMMARY
05/09/2019 Letter INSPECTION SUMMARY
05/09/2019 Letter INSPECTION SUMMARY
05/24/2019 Letter Field Certificate of Occupancy
06/14/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home