Permit Application Status

PRCOM20181511


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20181511
Building Permit - Commercial
Certificate of Occupancy
VAAP CHAPEL RIDGE LLC
NEW TENANT FINISH
JUICE BAR WITH SEATING
05/17/2018
06/12/2018
11/17/2018
07/11/2018
Locations
Contacts
VAAP CHAPEL RIDGE LLC, Address:5007 W 147TH ST  
SCHARHAG ARCHITECTS, Address:6247 BROOKSIDE BLVD STE 204, Phone:(816) 656-5055  
PHOENIX CONSTRUCTION INC, Address:1305 HOLLY CT, Phone:(816) 716-8208  
4SIGHT GROUP LLC, Address:7920 WARD PKWY, Phone:(816) 802-8400  
DAVID BALES, Address:17505 E 163RD, Phone:(816) 537-7511  
TRADEMARK PLUMBING LLC, Address:611 NW 105TH RD, Phone:(816) 824-5846  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 06/01/2018 06/18/2018
Joe Dir
Posting of occupant load
Corrective Action Required
06/18/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(veriifed at inspection) Post the occupant of 94 in the area of the front entrance
Construction documents for fire alarm systems
Corrective Action Required
06/18/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Fire alarm notification devices if not existing shall be installed in the suite. Have the fire alarm system contractor provide shop drawings of any needed modifications to be done to the fire alarm system.
Address numbers required
Corrective Action Required
06/18/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(veriifed at inspection) suite designation 136 shall be readable from the roadway on both front and rear doors.
Construction documents - Fire protection systems
Corrective Action Required
06/18/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(infromation purposes) Have the fire sprinkler system contractor provide shop drawings of any modifications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
06/18/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) If any fire alarm system devices are dissconnected, relocated or new installation an acceptance test of the fire alarm system will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300.
Misc
Corrective Action Required
06/18/2018

Door operation ACTION REQUIRED:No keyed locks on the egress side of an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Licensed Contractors Approved 05/24/2018 06/11/2018
Joe Frogge
LC - General Contractor
Resolved
06/11/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
06/11/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved with Conditions 06/01/2018 06/11/2018
Joe Frogge
License Tax Application
Corrective Action Required
05/24/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 5/25/18 - acknowledged
Health Dept Inspection
Corrective Action Required
05/24/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 5/25/18 - acknowledged
Health Dept Review
Resolved
06/11/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 5/25/18 - acknowledged
Bldg - Occupant load calculations - Areas without fixed seating 1004.1.2
Resolved
05/25/2018

2012 IBC 1004.1.2 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as described in Table 1004.1.2. For areas without fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant load factor assigned to the function of the space as set forth in Table 1004.1.2. Where an intended function is not listed in Table 1004.1.2, the building official shall establish a function based on a listed function that most nearly resembles the intended function. Action required: Occupant load calculation is correct. Recalc with 1 person per 15 square feet. (this will place you over 50 occupants)
Plumb - Minimum number of fixtures 403.1
Resolved
05/25/2018

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: 2 restrooms are required. this design does not qualify for the mercantile exception.
Code analysis required
Resolved
05/25/2018

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Revise code analysis to show that this tenant is an Assembly, not Mercantile.
Misc
Resolved
05/25/2018

2012 IBC 1014.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. Item 4. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. (See code section for additional items and exceptions) Action required: Exit not allowed through kitchen. 2 exits required out of seating area.
Mech - Outdoor air required 403.2
Resolved
05/25/2018

2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space. Action required: Revise drawings to show outside air calculations as well as method of delivery.
Plumb - Indirect/Special Waste - Where required 802.1
Resolved
05/25/2018

2012 IPC 802.1 Where required. Food-handling equipment and clear-water waste shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. All health-care related fixtures, devices and equipment shall discharge to the drainage system through an indirect waste pipe by means of an air gap in accordance with this chapter and section 713.3. Fixtures not required by this section to be indirectly connected shall be directly connected to the plumbing system in accordance with Chapter 7. Action required: Modify drawings to show that 3-compartment sink and ice machine will have compliant indirect wastes.
Health Department Review Approved 06/11/2018
Joe Frogge
Fire Plan Review Approved with Conditions 06/01/2018 05/25/2018
Joe Dir
Posting of occupant load
Corrective Action Required
05/24/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(veriifed at inspection) Post the occupant of 94 in the area of the front entrance
Construction documents for fire alarm systems
Corrective Action Required
05/24/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Fire alarm notification devices if not existing shall be installed in the suite. Have the fire alarm system contractor provide shop drawings of any needed modifications to be done to the fire alarm system.
Address numbers required
Corrective Action Required
05/24/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(veriifed at inspection) suite designation 136 shall be readable from the roadway on both front and rear doors.
Construction documents - Fire protection systems
Corrective Action Required
05/24/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(infromation purposes) Have the fire sprinkler system contractor provide shop drawings of any modifications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
05/24/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) If any fire alarm system devices are dissconnected, relocated or new installation an acceptance test of the fire alarm system will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300.
Misc
Corrective Action Required
05/24/2018

Door operation ACTION REQUIRED:No keyed locks on the egress side of an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Building Plan Review Rejected 05/30/2018 05/21/2018
Joe Frogge
License Tax Application
Corrective Action Required
05/21/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
05/21/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Review
Corrective Action Required
05/21/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Bldg - Occupant load calculations - Areas without fixed seating 1004.1.2
Corrective Action Required
05/21/2018

2012 IBC 1004.1.2 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as described in Table 1004.1.2. For areas without fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant load factor assigned to the function of the space as set forth in Table 1004.1.2. Where an intended function is not listed in Table 1004.1.2, the building official shall establish a function based on a listed function that most nearly resembles the intended function. Action required: Occupant load calculation is correct. Recalc with 1 person per 15 square feet. (this will place you over 50 occupants)
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
05/21/2018

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: 2 restrooms are required. this design does not qualify for the mercantile exception.
Code analysis required
Corrective Action Required
05/21/2018

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Revise code analysis to show that this tenant is an Assembly, not Mercantile.
Misc
Corrective Action Required
05/21/2018

2012 IBC 1014.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. Item 4. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. (See code section for additional items and exceptions) Action required: Exit not allowed through kitchen. 2 exits required out of seating area.
Mech - Outdoor air required 403.2
Corrective Action Required
05/21/2018

2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space. Action required: Revise drawings to show outside air calculations as well as method of delivery.
Plumb - Indirect/Special Waste - Where required 802.1
Corrective Action Required
05/21/2018

2012 IPC 802.1 Where required. Food-handling equipment and clear-water waste shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. All health-care related fixtures, devices and equipment shall discharge to the drainage system through an indirect waste pipe by means of an air gap in accordance with this chapter and section 713.3. Fixtures not required by this section to be indirectly connected shall be directly connected to the plumbing system in accordance with Chapter 7. Action required: Modify drawings to show that 3-compartment sink and ice machine will have compliant indirect wastes.
Licensed Contractors Rejected 11/22/2018 05/21/2018
Joe Frogge
LC - General Contractor
Corrective Action Required
05/21/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
05/21/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 05/30/2018 05/18/2018
Joe Dir
Posting of occupant load
Corrective Action Required
05/18/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(veriifed at inspection) Post the occupant of 48 in the area of the front entrance
Construction documents for fire alarm systems
Corrective Action Required
05/18/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Fire alarm notification devices if not existing shall be installed in the suite. Have the fire alarm system contractor provide shop drawings of any needed modifications to be done to the fire alarm system.
Address numbers required
Corrective Action Required
05/18/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(veriifed at inspection) suite designation 136 shall be readable from the roadway on both front and rear doors.
Construction documents - Fire protection systems
Corrective Action Required
05/18/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(infromation purposes) Have the fire sprinkler system contractor provide shop drawings of any modifications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
05/18/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) If any fire alarm system devices are dissconnected, relocated or new installation an acceptance test of the fire alarm system will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300.
Misc
Corrective Action Required
05/18/2018

Door operation ACTION REQUIRED:No keyed locks on the egress side of an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $41.76 $41.76 Paid 06/12/2018
8331506-EFHB Maybrook, Full $213.05 $213.05 Paid 06/12/2018
8331507-Sewer Connection Fee $150.00 $150.00 Paid 06/12/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 6/18/2018 6/18/2018 06/18/2018
In-wall Inspection Passed 6/18/2018 6/18/2018 at 12:40 PM 06/18/2018
Occupancy Inspection - Fire Passed 7/2/2018 07/02/2018
Occupancy Inspection - Codes Commercial Temporary C of O 7/2/2018 7/2/2018 at 1:05 PM 07/02/2018
Misc
Corrective Action Required
07/02/2018
OPEN J-BOX ABOVE UTILITY CLOSET. INSTALL BOX EXTENSION IF BOX FILL REQUIRES. CLOSE BOX.
Misc
Corrective Action Required
07/02/2018
SEAL JANITOR SINK TO WALL AND FLOOR
Misc
Corrective Action Required
07/02/2018
ELECT RECEPT NEAR JAN SINK MUST BE GFCI PROTECTED
Misc
Corrective Action Required
07/02/2018
VERTICAL GRAB BARS MUST BE 39" TO 41" FROM REAR WALL TO CENTER AND 39" TO 41" FROM FLOOR TO CENTER OF BOTTOM.
Misc
Corrective Action Required
07/02/2018
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF
Misc
Corrective Action Required
07/02/2018
ACCESSIBLE RESTROOMS MUST HAVE "ACCESSIBLE" SIGNS
Misc
Corrective Action Required
07/02/2018
NEC 600.3 UL LISTING OF EXTERIOR LIGHTED SIGNS / DECORATIVE ELEMENTS: IF INTERNALLY LIGHTED, MUST BE UL SHOP-LABELED AS INDICATION OF LISTING.
Occupancy Inspection - Codes Commercial Full C of O 7/11/2018 7/11/2018 at 8:05 AM 07/11/2018
Misc
Resolved
07/11/2018
OPEN J-BOX ABOVE UTILITY CLOSET. INSTALL BOX EXTENSION IF BOX FILL REQUIRES. CLOSE BOX.
Misc
Resolved
07/11/2018
SEAL JANITOR SINK TO WALL AND FLOOR
Misc
Resolved
07/11/2018
ELECT RECEPT NEAR JAN SINK MUST BE GFCI PROTECTED
Misc
Resolved
07/11/2018
VERTICAL GRAB BARS MUST BE 39" TO 41" FROM REAR WALL TO CENTER AND 39" TO 41" FROM FLOOR TO CENTER OF BOTTOM.
Misc
Resolved
07/11/2018
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF
Misc
Resolved
07/11/2018
ACCESSIBLE RESTROOMS MUST HAVE "ACCESSIBLE" SIGNS
Misc
Resolved
07/11/2018
NEC 600.3 UL LISTING OF EXTERIOR LIGHTED SIGNS / DECORATIVE ELEMENTS: IF INTERNALLY LIGHTED, MUST BE UL SHOP-LABELED AS INDICATION OF LISTING.
Documents & Images
Date Uploaded File Type Document Name
05/18/2018 Letter Fire Building Plan Review
05/21/2018 Letter Codes P/R Corrections Document
05/25/2018 Letter Fire Building Plan Review
06/11/2018 Berry Inspire
06/11/2018 Letter Codes Plan Review Conditions
06/12/2018 Receipt Receipt for transaction: 2018-003742
06/12/2018 Letter Codes Building Permit
06/14/2018 New Food Establishment Plan Review - Approved FTG 0001905
06/18/2018 Letter Inspection Summary
06/18/2018 Letter Fire Building Plan Review
07/02/2018 Letter Codes Temporary Certificate of Occupancy
07/11/2018 Letter Field Certificate of Occupancy
07/12/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home