Summary
PRCOM20180697
Building Permit - Commercial
Closed
CITY OF LEES SUMMIT
PARTIAL COMMERCIAL
FOUNDATION AND UNDERSLAB PERMIT FOR NEW 2 STORY APARTMENT WITH PARKING GARAGES BENEATH FOUNDATION PERMIT - PRCOM20172503
03/16/2018
04/13/2018
03/26/2019
Locations
Contacts
CITYSCAPE CONSTRUCTION VIEW HIGH LLC, Address:10 W CARMEL DR STE 200, Phone:(317) 574-1600 Ext:100  
CITY OF LEES SUMMIT, Address:220 SE GREEN ST  
LATIMER SOMMERS & ASSOCIATES PA, Address:3639 SW SUMMERFIELD DR STE A, Phone:(785) 233-3232  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 11/29/2018
Joe Dir
Miscellaneous Correction
Resolved
11/29/2018

Riser diagram / NFPA symbols ACTION REQUIRED: Alarm system riser diagram and the NFPA symbol legend need to include the WP horn/strobe and the W-horn strobe, and NAC symbols and definition.
Miscellaneous Correction
Resolved
11/29/2018

NAC panel ACTION REQUIRED: Plans show NAC circuits but no NAC panel . Plans need to show the NAC panel locations.
Misc
Resolved
11/29/2018

Manual pull stations ACTION REQUIRED: Eliminate all but one manual pull station from all buildings including the clubhouse. The one manual pull station is to be mounted by the FAC.
Miscellaneous Correction
Resolved
11/29/2018

Battery Caclulations ACTION REQUIRED: Battery Calculations need to include the size and number of batteries to be installed in each buildings FAC and NAC panels.
Miscellaneous Correction
Resolved
11/29/2018

FAA location ACTION REQUIRED: Relocate the FAA from the corridor to the Front entry vestibule.
Miscellaneous Correction
Resolved
11/29/2018

Strobe notification devices ACTION REQUIRED: Replace the horn and horn/strobe notification devices with STROBE only notification in the following areas. Clubhouse: restrooms, dogwash room, massage room and breakroom
Miscellaneous Correction
Resolved
11/29/2018

Smoke detection ACTION REQUIRED: Plans need to show smoke detection in the following areas. Sheet FA1-16 Type V bldg. 2nd floor hallways Sheet FA1-18 Type VI bldg. 2nd floor hallways Elevator lobbys and hoistways/pits Reference material: Elevator emergency operation, Area smoke Detection IFC 2012 sec. 907.2.13.1.1 907.3.3 Elevator lobbys - reference IFC 2012 sec. 907.2.13.1.1 NFPA 72 sec. 21.3.5 Elevator hoistways - reference IFC 2012 sec 907.2.13.1.1 NFPA 72 sec. 21.3.6, 21.3.7, 21.3.8
Miscellaneous Correction
Resolved
11/29/2018

Manufacturers specs. ACTION REQUIRED:Provide manufactures specs for the following: smoke dampers, carbon monoxide detectors to be installed in the garages. strobe only notification devices for the restrooms and other rooms specified
Installation acceptance testing
Corrective Action Required
11/29/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the Fire Alarm System in each building will required prior to the final occupancy inspection of each building. Contact the Fire Department to schedule testing. (816)969-1300
Miscellaneous Correction
Corrective Action Required
11/29/2018

Plan Sheet FA1.26 ACTION REQUIRED: Clubhouse Terrace Level - All addressable manual pull stations need to be removed from plan sheet FA1.26 Clubhouse terrace level. After a phone conversation with the (P.E.) Rich Beardmore a decision was made that the manual pull stations will be (X) marked off the plan sheets by the plan reviewer and a note added to plan sheets FA1.26 not to install the addressable manual pull stations on the terrace level of the clubhouse.
Alarm Plan Review Rejected 11/20/2018
Joe Dir
Miscellaneous Correction
Corrective Action Required
11/20/2018

Riser diagram / NFPA symbols ACTION REQUIRED: Alarm system riser diagram and the NFPA symbol legend need to include the WP horn/strobe and the W-horn strobe, and NAC symbols and definition.
Miscellaneous Correction
Corrective Action Required
11/20/2018

NAC panel ACTION REQUIRED: Plans show NAC circuits but no NAC panel . Plans need to show the NAC panel locations.
Misc
Corrective Action Required
11/20/2018

Manual pull stations ACTION REQUIRED: Eliminate all but one manual pull station from all buildings including the clubhouse. The one manual pull station is to be mounted by the FAC.
Miscellaneous Correction
Corrective Action Required
11/20/2018

Battery Caclulations ACTION REQUIRED: Battery Calculations need to include the size and number of batteries to be installed in each buildings FAC and NAC panels.
Miscellaneous Correction
Corrective Action Required
11/20/2018

FAA location ACTION REQUIRED: Relocate the FAA from the corridor to the Front entry vestibule.
Miscellaneous Correction
Corrective Action Required
11/20/2018

Strobe notification devices ACTION REQUIRED: Replace the horn and horn/strobe notification devices with STROBE only notification in the following areas. Clubhouse: restrooms, dogwash room, massage room and breakroom
Miscellaneous Correction
Corrective Action Required
11/20/2018

Smoke detection ACTION REQUIRED: Plans need to show smoke detection in the following areas. Sheet FA1-16 Type V bldg. 2nd floor hallways Sheet FA1-18 Type VI bldg. 2nd floor hallways Elevator lobbys and hoistways/pits Reference material: Elevator emergency operation, Area smoke Detection IFC 2012 sec. 907.2.13.1.1 907.3.3 Elevator lobbys - reference IFC 2012 sec. 907.2.13.1.1 NFPA 72 sec. 21.3.5 Elevator hoistways - reference IFC 2012 sec 907.2.13.1.1 NFPA 72 sec. 21.3.6, 21.3.7, 21.3.8
Miscellaneous Correction
Corrective Action Required
11/20/2018

Manufacturers specs. ACTION REQUIRED:Provide manufactures specs for the following: smoke dampers, carbon monoxide detectors to be installed in the garages. strobe only notification devices for the restrooms and other rooms specified
Licensed Contractors Approved 03/16/2018 03/16/2018
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Partial Commercial $501.48 $501.48 Paid 03/21/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 9/19/2018 9/19/2018 09/19/2018
Misc
Corrective Action Required
09/19/2018
PARTIAL- LOWER LEVEL MAIN TRUNK
Footing Inspection - Commercial Partial 10/19/2018 (8:00) 10/19/2018 at 7:00 AM 10/19/2018
Misc
Corrective Action Required
10/19/2018
lower west footing
Footing Inspection - Commercial Partial 10/23/2018 at 3:40 PM 10/23/2018
Misc
Corrective Action Required
10/23/2018
A6.2 DETAIL 1 FOOTING BASEMENT WALL OK TO POUR
Foundation Inspection - Commercial Partial 10/25/2018 10/25/2018
Misc
Corrective Action Required
10/25/2018
LOWER LEVEL WEST WALL
Footing Inspection - Commercial Partial 11/7/2018 (2:30) 11/8/2018 11/08/2018
Misc
Corrective Action Required
10/19/2018
lower west footing east lower footing
Footing Inspection - Commercial Partial 12/5/2018 (1:00) 12/5/2018 12/05/2018
Misc
Partial Correction
12/05/2018
A6.2 DETAIL 1 FOOTING BASEMENT WALL OK TO POUR; REST OF EAST APPROVED TO CORNER; INTERIOR FOOTING FOR GARAGE APPROVED
Footing Inspection - Commercial Partial 12/7/2018 (9:45) 12/7/2018 12/07/2018
Misc
Partial Correction
12/05/2018
A6.2 DETAIL 1 FOOTING BASEMENT WALL OK TO POUR; REST OF EAST APPROVED TO CORNER; INTERIOR FOOTING FOR GARAGE APPROVED remainder lover footing approved.
Footing Inspection - Commercial Partial 3/14/2019 (11:00) 3/14/2019 03/14/2019
Misc
Partial Correction
12/07/2018
A6.2 DETAIL 1 FOOTING BASEMENT WALL OK TO POUR; REST OF EAST APPROVED TO CORNER; INTERIOR FOOTING FOR GARAGE APPROVED remainder lover footing approved. Upper footing--north & west center portion ok to pour.
Foundation Inspection - Commercial Passed 03/15/2019
Misc
Corrective Action Required
10/25/2018
LOWER LEVEL WEST WALL
Footing Inspection - Commercial Passed 3/15/2019 (1:00) 3/15/2019 03/15/2019
Misc
Resolved
03/15/2019
A6.2 DETAIL 1 FOOTING BASEMENT WALL OK TO POUR; REST OF EAST APPROVED TO CORNER; INTERIOR FOOTING FOR GARAGE APPROVED remainder lover footing approved. Upper footing--north & west center portion ok to pour.
Underslab Plumbing Inspection - Commercial Passed 3/21/2019 3/21/2019 03/21/2019
Misc
Resolved
03/21/2019
PARTIAL- LOWER LEVEL MAIN TRUNK
Underslab Electrical Inspection - Commercial Passed 03/26/2019
Documents & Images
Date Uploaded File Type Document Name
03/21/2018 Receipt Receipt for transaction: 2018-001046
04/13/2018 Letter Codes Building Permit
09/19/2018 Letter Inspection Summary
10/19/2018 Letter Inspection Summary
10/23/2018 Letter Inspection Summary
10/25/2018 Letter Inspection Summary
11/08/2018 Letter Inspection Summary
11/20/2018 Letter Fire (Alarm) Plan Review Notice
11/20/2018 Letter Fire (Alarm) Plan Review Notice
11/29/2018 Letter Fire (Alarm) Plan Review Notice
12/05/2018 Letter INSPECTION SUMMARY
12/07/2018 Letter INSPECTION SUMMARY
03/14/2019 Letter INSPECTION SUMMARY
03/15/2019 Letter INSPECTION SUMMARY
03/21/2019 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home