Permit Application Status

PRCOM20180204


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20180204
Building Permit - Commercial
Certificate of Occupancy
TI SUMMIT CREST PLAZA LLC
CHANGE OF TENANT
BUILD A PRIVATE OFFICE AND REPLACE FLOORING, ACOUSTICAL CEILING TILE AND PAINT WALLS **drawings are in plan review file
01/26/2018
02/01/2018
03/02/2018
Locations
Contacts
TI SUMMIT CREST PLAZA LLC, Address:7611 STATE LINE RD STE 301  
KELLY CONSTRUCTION GROUP INC, Address:4021 E 143RD ST, Phone:(816) 621-7600  
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 02/07/2018 01/30/2018
Joe Frogge
Building Plan Review Approved 02/07/2018 01/30/2018
Joe Frogge
Fire Plan Review Approved with Conditions 02/07/2018 01/30/2018
Joe Frogge
Address numbers required
Corrective Action Required
01/30/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Post the numeric address of 3516 on the exterior of the front and rear doors. Address shall be readfable from the roadway
Construction documents - Fire protection systems
Corrective Action Required
01/30/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings for approval of any modifications to be done to the fire sprinkler system.
Portable fire extinguishers - general
Corrective Action Required
01/30/2018

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide one 2A-10BC fire extinguisher. The extinguisher to be mounted on a normal path of travel close to an exit.
Misc
Corrective Action Required
01/30/2018

Door operations: ACTION REQUIRED: No keyed locks on the egress side of an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Fire Plan Review Approved with Conditions 02/07/2018 01/30/2018
Joe Dir
Address numbers required
Corrective Action Required
01/30/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Post the numeric address of 3516 on the exterior of the front and rear doors. Address shall be readfable from the roadway
Construction documents - Fire protection systems
Corrective Action Required
01/30/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings for approval of any modifications to be done to the fire sprinkler system.
Portable fire extinguishers - general
Corrective Action Required
01/30/2018

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide one 2A-10BC fire extinguisher. The extinguisher to be mounted on a normal path of travel close to an exit.
Misc
Corrective Action Required
01/30/2018

Door operations: ACTION REQUIRED: No keyed locks on the egress side of an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $69.45 $69.45 Paid 02/01/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Not Ready 2/14/2018 2/14/2018 02/14/2018
Misc
Corrective Action Required
02/14/2018
locked, no access
In-wall Inspection Passed 2/15/2018 at 10:35 AM 02/15/2018
Misc
Resolved
02/15/2018
locked, no access
Above Ceiling Inspection Passed 2/20/2018 at 2:30 PM 02/20/2018
Occupancy Inspection - Fire Passed 3/2/2018 03/02/2018
Occupancy Inspection - Codes Commercial Full C of O 3/2/2018 3/2/2018 03/02/2018
Documents & Images
Date Uploaded File Type Document Name
01/30/2018 Letter Fire Building Plan Review
01/30/2018 Letter Codes Plan Review Conditions
02/01/2018 Receipt Receipt for transaction: 2018-000392
02/01/2018 Letter Codes Building Permit
02/01/2018 Drawing DOC020118-002
02/14/2018 Letter Inspection Summary
02/15/2018 Letter Inspection Summary
02/20/2018 Letter Inspection Summary
03/02/2018 Letter Field Certificate of Occupancy
03/05/2018 Letter Codes Final Certificate of Occupancy
08/31/2018 FW 3516 SW Market Street Lee's Summit MO
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home