Permit Application Status

PRCOM20173153


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20173153
Building Permit - Commercial
Certificate of Occupancy
RAINTREE INVESTORS LLC
NEW COMMERCIAL
DRIVE-THRU COFFEE SHOP WITH NO IN STORE SERVICE
09/20/2017
11/30/2017
04/01/2018
03/12/2018
Locations
Contacts
BOUWENS CONTRACTING SERVICES, LLC, Address:11669 S CHESTNUT ST, Phone:(913) 369-5828  
AIR CARE HEATING & COOLING, Address:10332 W 79TH ST, Phone:(913) 362-5274  
EXPRESS ELECTRIC LLC, Address:24816 W 91ST PLACE, Phone:(913) 548-6541  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
[K] WARMAN ARCHITECTS, Address:1828 SWIFT, SUITE 101, Phone:(816) 474-2233  
RAINTREE INVESTORS LLC, Address:7387 W 162ND ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 10/04/2017 11/29/2017
Joe Frogge
Health Department Review Approved 11/29/2017
Joe Frogge
Building Plan Review Approved with Conditions 10/06/2017 11/27/2017
Joe Frogge
License Tax Application
Corrective Action Required
09/29/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 10/2/17 - acknowledged in letter
Final Development Plan
Resolved
11/29/2017

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 10/2/17 - acknowledged in letter
Plan Submittal 2012 Codes
Resolved
10/02/2017

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Revise code analysis to show correct year of ICC/ANSI. (2009)
Code analysis required
Resolved
10/02/2017

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Revise code analysis to show correct occupancy which is B.
Health Dept Review
Resolved
10/23/2017

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
09/29/2017

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Plumb - Cleanouts - Building sewer 708.3.2
Resolved
10/02/2017

2012 IPC 708.3.2 Building sewers. Building sewers shall be provided with cleanouts located not more than 100 feet apart measured from the upstream entrance of the cleanout. For building sewers 8 inches and larger, manholes shall be provided and located not more than 200 feet from the junction of the building drain and building sewer, at each change in direction and at intervals of not more than 400 feet apart. Manholes and manhole covers shall be of an approved type. Action required: Additional cleanout required as to not exceed the 100' limit.
Misc
Resolved
10/02/2017

Clarification required. Action required: Water meter is noted as 3/4". Is it your intention to use a full 3/4" meter? ($6,047.93) Or, the standard residential size of 5/8"x3/4" meter? ($3,774.83) 10/2/17 - resolved by calling MEP engineer (Mason with BC Engineers)
Licensed Contractors Approved 09/29/2017 11/27/2017
Joe Frogge
LC - General Contractor
Resolved
11/13/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 10/2/17 - acknowledged in letter
LC - MEP Subs
Resolved
11/27/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/2/17 - acknowledged in letter
Fire Plan Review Approved with Conditions 10/06/2017 10/02/2017
Joe Dir
Address numbers required
Corrective Action Required
09/29/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: Numeric address shall be readable from the addressed roadway
Portable fire extinguishers - general
Corrective Action Required
09/29/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide one 2A-10BC fire extinguisher. Fire extinguisher to be mounted close to the exit.
Building Plan Review Rejected 10/04/2017 09/25/2017
Joe Frogge
License Tax Application
Corrective Action Required
09/25/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Final Development Plan
Corrective Action Required
09/25/2017

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Plan Submittal 2012 Codes
Corrective Action Required
09/25/2017

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Revise code analysis to show correct year of ICC/ANSI. (2009)
Code analysis required
Corrective Action Required
09/25/2017

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Revise code analysis to show correct occupancy which is B.
Health Dept Review
Corrective Action Required
09/25/2017

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
09/25/2017

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Plumb - Cleanouts - Building sewer 708.3.2
Corrective Action Required
09/25/2017

2012 IPC 708.3.2 Building sewers. Building sewers shall be provided with cleanouts located not more than 100 feet apart measured from the upstream entrance of the cleanout. For building sewers 8 inches and larger, manholes shall be provided and located not more than 200 feet from the junction of the building drain and building sewer, at each change in direction and at intervals of not more than 400 feet apart. Manholes and manhole covers shall be of an approved type. Action required: Additional cleanout required as to not exceed the 100' limit.
Misc
Corrective Action Required
09/25/2017

Clarification required. Action required: Water meter is noted as 3/4". Is it your intention to use a full 3/4" meter? ($6,047.93) Or, the standard residential size of 5/8"x3/4" meter? ($3,774.83)
Licensed Contractors Rejected 09/20/2017 09/25/2017
Joe Frogge
LC - General Contractor
Corrective Action Required
09/25/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
09/25/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 10/04/2017 09/25/2017
Joe Dir
Address numbers required
Corrective Action Required
09/25/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: Numeric address shall be readable from the addressed roadway
Portable fire extinguishers - general
Corrective Action Required
09/25/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide one 2A-10BC fire extinguisher. Fire extinguisher to be mounted close to the exit.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $234.65 $234.65 Paid 11/27/2017
8331504-EFHB Middle Big Creek, Full $200.88 $200.88 Paid 11/27/2017
8331507-Sewer Connection Fee $180.00 $180.00 Paid 11/27/2017
8331401-Water Tap Fee $3,343.00 $3,343.00 Paid 11/27/2017
8350015-Water Meter Fee $431.83 $431.83 Paid 11/27/2017
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 11/27/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Passed 11/30/2017 at 2:25 AM 11/30/2017
Underslab Plumbing Inspection - Commercial Passed 12/6/2017 12/6/2017 at 8:25 AM 12/06/2017
Rough Framing Inspection - Commercial Passed 12/22/2017 at 11:10 AM 12/22/2017
All Rough Inspection - Commercial Passed 1/8/2018 1/8/2018 at 10:00 AM 01/08/2018
Electrical Service Inspection Passed 2/9/2018 2/9/2018 02/09/2018
Underground Electrical Inspection - Commercial Not Ready 2/9/2018 at 12:15 PM 02/09/2018
Underground Electrical Inspection - Commercial Failed 2/9/2018 at 1:35 PM 02/09/2018
Misc
Corrective Action Required
02/09/2018
L.P. BASE CAGES ARE #5. DRAWING SAYS SIX #6 REQUIRED.
Underground Electrical Inspection - Commercial Failed 2/12/2018 2/12/2018 02/12/2018
Misc
Corrective Action Required
02/09/2018
LIGHT POLES APPROVED, CONDUIT DEPTH FAILED
Underground Electrical Inspection - Commercial Passed 2/15/2018 2/15/2018 at 3:00 PM 02/15/2018
Misc
Resolved
02/15/2018
LIGHT POLES APPROVED, CONDUIT DEPTH FAILED
Above Ceiling Inspection Passed 2/16/2018 2/16/2018 at 10:30 AM 02/16/2018
Occupancy Inspection - Fire Passed 3/7/2018 03/07/2018
Occupancy Inspection - Codes Commercial Temporary C of O 3/7/2018 3/9/2018 03/09/2018
Corrective Action Required
03/09/2018
REPAIR SOUTH ENTRANCE ACCESSIBLE ROUTE
Occupancy Inspection - Planning Passed 03/09/2018
Occupancy Inspection - Codes Commercial Full C of O 3/12/2018 at 8:10 AM 03/12/2018
Driveway Inspection Passed 3/12/2018 at 8:05 AM 03/19/2018
Informational
03/19/2018
Matt Munger 03/12/2018 8:30 AM Driveway met ADA standards.
Sidewalk Inspection Passed 3/12/2018 at 8:05 AM 03/19/2018
PW-Misc
Informational
03/19/2018
Matt Munger 03/12/2018 8:31 AM Corrections were made to the sidewalk to comply with ADA standards.
Occupancy Inspection - Water Utilities Passed 04/02/2018
Documents & Images
Date Uploaded File Type Document Name
09/25/2017 Letter Fire Building Plan Review
09/25/2017 Letter Codes P/R Corrections Document
10/02/2017 Scooter's Water Meter
10/02/2017 Letter Fire Building Plan Review
10/03/2017 Letter Codes P/R Corrections Document
10/23/2017 New Food Establishment Plan Review - Approved FTG 0001784
11/27/2017 Receipt Receipt for transaction: 2017-007422
11/29/2017 Letter Codes Plan Review Conditions
11/30/2017 Letter Codes Building Permit
11/30/2017 Letter Inspection Summary
12/06/2017 Letter Inspection Summary
12/22/2017 Letter Inspection Summary
01/08/2018 Letter Inspection Summary
02/09/2018 Letter Inspection Summary
02/09/2018 Letter Inspection Summary
02/09/2018 Letter Inspection Summary
02/12/2018 Letter Inspection Summary
02/15/2018 Letter Inspection Summary
02/16/2018 Letter Inspection Summary
03/09/2018 Letter Codes Temporary Certificate of Occupancy
03/12/2018 Letter Field Certificate of Occupancy
03/14/2018 Letter Codes Final Certificate of Occupancy
03/19/2018 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents