Permit Application Status

PRCOM20172903


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20172903
Building Permit - Commercial
Certificate of Occupancy
TI SUMMIT CREST PLAZA LLC
CHANGE OF TENANT
LUCKY WOK - TENANT FINISH FOR NEW CARRY-OUT RESTAURANT **invite planner to final to verify screening
08/29/2017
09/26/2017
03/19/2018
01/26/2018
Locations
Contacts
STEPHEN MASLAN & COMPANY, Address:8011 PASEO, Phone:(816) 444-6260  
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
CORNERSTONE ARCHITECT LLC, Address:8117 ROBERTS RD, Phone:(816) 838-3472  
TI SUMMIT CREST PLAZA LLC, Address:7611 STATE LINE RD STE 301  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 12/22/2017
Joe Dir
Licensed Contractors Approved 09/18/2017 09/26/2017
Joe Frogge
LC - General Contractor
Resolved
09/26/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
LC - MEP Subs
Resolved
09/26/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Building Plan Review Approved with Conditions 09/25/2017 09/22/2017
Joe Frogge
License Tax Application
Corrective Action Required
09/18/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Resolved
09/22/2017

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
09/18/2017

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Misc
Resolved
09/20/2017

2012 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: This building is a Type 5B. Revise code analysis.
Misc
Resolved
09/20/2017

2012 IMC 507.9 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. Exception: Clearance shall not be required from gypsum wallboard or ½ inch or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches in all directions from the hood. Action required: Provide verification that hood is attached to a wall built with non-combustible construction. i.e. metal studs. Also, specify non-combustible surface that extends at least 18" beyond hood. 9/20/17 - wall verified to be noncombustible per architect's letter
Misc
Resolved
09/20/2017

2012 IMC 507.2 Where Required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliance under a single hood requires a Type I hood, a Type I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed. Exception: Where cooking appliances are equipped with integral down-draft exhaust systems and such appliances and exhaust systems are listed and labeled for the application in accordance with NFPA 96, a hood shall not be required at or above them. Action required: Provide verification that "Chinese Stove" is not required to be under hood.
Screening - Rooftop equipment
Corrective Action Required
09/18/2017

Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped. Action required: Provide compliant screening at new rooftop equipment or provide verification that existing screening is adequate. 9/20/17 - acknowledged in letter - to be field verified.
Misc
Resolved
09/20/2017

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) within 25' of new rooftop equipment.
Health Department Review Approved 09/22/2017
Joe Frogge
Fire Plan Review Approved with Conditions 09/25/2017 09/19/2017
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
09/18/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED: (information purposes) Have the fire alarm system contractor provide shop drawings for approval of any modifications to be done to the fire alarm system.
Address numbers required
Corrective Action Required
09/18/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Address shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
09/18/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED: (information purposes) Have the Fire sprinkler system contractor provide shop drawings for approval of any modifications to be done to the fire sprinkler system. Have the Kitchen hood suppression system contractor provide the manufactures specs for the suppression system for the kitchen hood to be installed.
Installation acceptance testing
Corrective Action Required
09/18/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing for the fire alarm system and the kitchen hood system will be required prior to the final occupancy inspection. To schedule testing contact the fire department. 816-969-1300
Misc
Corrective Action Required
09/18/2017

kitchen hood monitoring ACTION REQUIRED: Wire the kitchen hood suppression system into the fire alarm panel for the shopping mall 904.3.4 Alarms and warning signs. Where alarms are required to indicate the operation of automatic fire-extinguishing systems, distinctive audible, visible alarms and warning signs shall be provided to warn of pending agent discharge. Where exposure to automatic-extinguishing agents poses a hazard to persons and a delay is required to ensure the evacuation of occupants before agent discharge, a separate warning signal shall be provided to alert occupants once agent discharge has begun. Audible signals shall be in accordance with Section 907.5.2. 904.3.5 Monitoring. Where a building fire alarm system is installed, automatic fire-extinguishing systems shall be monitored by the building fire alarm system in accordance with NFPA 72.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
09/18/2017

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ACTION REQUIRED: (verified at inspection) Provide a K-class fire extinguisher according to the plan comments
Portable fire extinguishers - general
Corrective Action Required
09/18/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED: (verified at inspection) Provide one 2A-10BC fire extinguisher. Extinguisher to be mounted by the rear exit.
Building Plan Review Rejected 09/11/2017 09/06/2017
Joe Frogge
License Tax Application
Corrective Action Required
09/06/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Corrective Action Required
09/06/2017

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
09/06/2017

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
09/06/2017

2012 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: This building is a Type 5B. Revise code analysis.
Misc
Corrective Action Required
09/06/2017

2012 IMC 507.9 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. Exception: Clearance shall not be required from gypsum wallboard or ½ inch or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches in all directions from the hood. Action required: Provide verification that hood is attached to a wall built with non-combustible construction. i.e. metal studs. Also, specify non-combustible surface that extends at least 18" beyond hood.
Misc
Corrective Action Required
09/06/2017

2012 IMC 507.2 Where Required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliance under a single hood requires a Type I hood, a Type I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed. Exception: Where cooking appliances are equipped with integral down-draft exhaust systems and such appliances and exhaust systems are listed and labeled for the application in accordance with NFPA 96, a hood shall not be required at or above them. Action required: Provide verification that "Chinese Stove" is not required to be under hood.
Screening - Rooftop equipment
Corrective Action Required
09/06/2017

Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped. Action required: Provide compliant screening at new rooftop equipment or provide verification that existing screening is adequate.
Misc
Corrective Action Required
09/06/2017

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) within 25' of new rooftop equipment.
Licensed Contractors Rejected 09/06/2017
Joe Frogge
LC - General Contractor
Corrective Action Required
09/06/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
LC - MEP Subs
Corrective Action Required
09/06/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Fire Plan Review Approved with Conditions 09/11/2017 08/30/2017
Joe Dir
08/30/2017

08/30/2017

Construction documents for fire alarm systems
Corrective Action Required
08/30/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED: (information purposes) Have the fire alarm system contractor provide shop drawings for approval of any modifications to be done to the fire alarm system.
Address numbers required
Corrective Action Required
08/30/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Address shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
08/30/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED: (information purposes) Have the Fire sprinkler system contractor provide shop drawings for approval of any modifications to be done to the fire sprinkler system. Have the Kitchen hood suppression system contractor provide the manufactures specs for the suppression system for the kitchen hood to be installed.
Installation acceptance testing
Corrective Action Required
08/30/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing for the fire alarm system and the kitchen hood system will be required prior to the final occupancy inspection. To schedule testing contact the fire department. 816-969-1300
Misc
Corrective Action Required
08/30/2017

kitchen hood monitoring ACTION REQUIRED: Wire the kitchen hood suppression system into the fire alarm panel for the shopping mall 904.3.4 Alarms and warning signs. Where alarms are required to indicate the operation of automatic fire-extinguishing systems, distinctive audible, visible alarms and warning signs shall be provided to warn of pending agent discharge. Where exposure to automatic-extinguishing agents poses a hazard to persons and a delay is required to ensure the evacuation of occupants before agent discharge, a separate warning signal shall be provided to alert occupants once agent discharge has begun. Audible signals shall be in accordance with Section 907.5.2. 904.3.5 Monitoring. Where a building fire alarm system is installed, automatic fire-extinguishing systems shall be monitored by the building fire alarm system in accordance with NFPA 72.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
08/30/2017

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ACTION REQUIRED: (verified at inspection) Provide a K-class fire extinguisher according to the plan comments
Portable fire extinguishers - general
Corrective Action Required
08/30/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED: (verified at inspection) Provide one 2A-10BC fire extinguisher. Extinguisher to be mounted by the rear exit.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $285.95 $285.95 Paid 09/26/2017
8331507-Sewer Connection Fee $270.00 $270.00 Paid 09/26/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 10/13/2017 10/13/2017 at 8:30 AM 10/13/2017
All Rough Inspection - Commercial Failed 10/18/2017 10/18/2017 at 12:00 PM 10/18/2017
Misc
Corrective Action Required
10/18/2017
INSTLL PLUMBING PROTECTION PLATES.
All Rough Inspection - Commercial Passed 10/19/2017 10/19/2017 at 9:20 AM 10/19/2017
Misc
Resolved
10/19/2017
INSTLL PLUMBING PROTECTION PLATES.
Hood/Duct Inspection Passed 12/12/2017 at 11:12 AM 12/12/2017
Gas Service Inspection - Commercial Passed 12/12/2017 12/12/2017 at 11:01 AM 12/12/2017
Gas Piping Inspection - Commercial Passed 12/12/2017
Alarm Test Failed 12/29/2017 12/29/2017
Alternate Protection Systems Inspection Failed 12/29/2017 12/29/2017
Alarm Test Passed 1/12/2018 01/12/2018
Alternate Protection Systems Inspection Passed 1/12/2018 01/12/2018
Occupancy Inspection - Fire Passed 01/16/2018
Occupancy Inspection - Codes Commercial Failed 1/16/2018 1/16/2018 at 3:00 PM 01/16/2018
Misc
Corrective Action Required
01/16/2018
-OBTAIN HEALTH DEPARTMENT APPROVAL -INSTALL VERTICLE GRAB BAR IN BATH -LABEL ACCESSABLE SIGNAGE BATH
Occupancy Inspection - Codes Commercial Full C of O 1/26/2018 1/26/2018 at 8:00 AM 01/26/2018
Misc
Resolved
01/26/2018
-OBTAIN HEALTH DEPARTMENT APPROVAL -INSTALL VERTICLE GRAB BAR IN BATH -LABEL ACCESSABLE SIGNAGE BATH
Documents & Images
Date Uploaded File Type Document Name
08/30/2017 Letter Fire Building Plan Review
09/06/2017 Letter Codes P/R Corrections Document
09/19/2017 Letter Fire Building Plan Review
09/20/2017 Letter Codes P/R Corrections Document
09/22/2017 New Food Establishment Plan Review - Approved FTG 0001369
09/26/2017 Letter Codes Plan Review Conditions
09/26/2017 Receipt Receipt for transaction: 2017-006529
09/26/2017 Letter Codes Building Permit
10/13/2017 Letter Inspection Summary
10/18/2017 Letter Inspection Summary
10/19/2017 Letter Inspection Summary
12/12/2017 Letter Inspection Summary
12/22/2017 Letter Fire (Sprinkler) Plan Review
01/16/2018 Letter Inspection Summary
01/26/2018 Letter Field Certificate of Occupancy
01/30/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home