Summary
PRCOM20172757
Building Permit - Commercial
Final Completion
PINE TREE PLAZA LLC
ALTERATION COMMERCIAL
FACADE REMODEL INCLUDING SITE LIGHTING ALTERATIONS
08/14/2017
11/14/2017
02/14/2018
11/30/2018
Locations
Contacts
MILLER STAUCH CONSTRUCTION CO, Address:32 N 6TH ST, Phone:(913) 599-1040  
CLAYCO ELECTRIC COMPANY, Address:319 E 11TH AVE, Phone:(816) 221-0593  
KLOVER ARCHITECTS, Address:10955 LOWELL AVE, Phone:(913) 649-8181  
PINE TREE PLAZA LLC, Address:601 E SOUTH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 09/22/2017 01/31/2018
Joe Dir
Misc
Corrective Action Required
01/31/2018

ACTION REQUIRED: Maintain all area fire hydrants Maintain access to all area fire hydrants Maintain fire lanes around the Plaza Any addressing that may be affected by the rennovation shall be replaced, readable from the roadway.
Building Plan Review Approved 09/22/2017 11/13/2017
Development Center
Final Development Plan
Resolved
09/19/2017

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
License Tax Application
Resolved
11/13/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Project cost
Resolved
11/13/2017

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
Misc
Resolved
09/15/2017

Missouri Board for Architects, Professional Engineers, Professional Land Surveyors and Professional Landscape Architects – Board Rules, Division 2030 – Chapter 3, 20 CSR 2030-3.060 Licensees Seal Documents must bear design professionals original seal with signature and date. (relevant portion paraphrased – reference original document for additional information) Action required: Provide at least one copy of plan set with original seals/signatures or provide letters from design professionals attesting to the fact that these copies represent their digital seal.
Licensed Contractors Approved 09/15/2017 11/13/2017
Development Center
LC - General Contractor
Resolved
11/13/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
11/13/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 09/22/2017 09/19/2017
Joe Dir
Misc
Corrective Action Required
09/15/2017

ACTION REQUIRED: Maintain all area fire hydrants Maintain access to all area fire hydrants Maintain fire lanes around the Plaza Any addressing that may be affected by the rennovation shall be replaced, readable from the roadway.
Fire Plan Review Approved with Conditions 08/24/2017 08/18/2017
Joe Dir
Misc
Corrective Action Required
08/18/2017

ACTION REQUIRED: Maintain all area fire hydrants Maintain access to all area fire hydrants Maintain fire lanes around the Plaza Any addressing that may be affected by the rennovation shall be replaced, readable from the roadway.
Building Plan Review Rejected 08/24/2017 08/14/2017
Joe Frogge
Final Development Plan
Corrective Action Required
08/14/2017

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
License Tax Application
Corrective Action Required
08/14/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Project cost
Corrective Action Required
08/14/2017

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
08/14/2017

Missouri Board for Architects, Professional Engineers, Professional Land Surveyors and Professional Landscape Architects – Board Rules, Division 2030 – Chapter 3, 20 CSR 2030-3.060 Licensees Seal Documents must bear design professionals original seal with signature and date. (relevant portion paraphrased – reference original document for additional information) Action required: Provide at least one copy of plan set with original seals/signatures or provide letters from design professionals attesting to the fact that these copies represent their digital seal.
Licensed Contractors Rejected 08/14/2017 08/14/2017
Joe Frogge
LC - General Contractor
Corrective Action Required
08/14/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
08/14/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $5,938.20 $5,938.20 Paid 11/14/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Not Ready 12/1/2017 (8:30) 12/1/2017 at 9:20 AM 12/01/2017
Rough Framing Inspection - Commercial Failed 12/1/2017 at 9:15 AM 12/01/2017
Misc
Corrective Action Required
12/01/2017
HORIZONTAL BRACING NOT CLIPPED
Rough Framing Inspection - Commercial Partial 12/5/2017 12/5/2017 at 10:35 AM 12/05/2017
Misc
Partial Correction
12/05/2017
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION;
Footing Inspection - Commercial Not Ready 12/6/2017 (10:45) 12/6/2017 at 11:30 AM 12/06/2017
Misc
Corrective Action Required
12/06/2017
RE-BAR MATS NOT IN PLACE
Footing Inspection - Commercial Partial 12/8/2017 at 8:25 AM 12/08/2017
Misc
Partial Correction
12/08/2017
OK TO POUR WHEN READY TWO FOOTINGS PER SECTION 01/S4.7 AND SECTION 02/S4.1;
Rough Framing Inspection - Commercial Partial 12/8/2017 12/8/2017 at 8:40 AM 12/08/2017
Misc
Partial Correction
12/05/2017
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. OK TO COVER WHEN READY LIGHT GAUGE STEEL FRAMING AT: [SOFFITS AND VERTICAL FRAMING ABOVE HARBOR FREIGHT ENTRANCE; COLUMN WRAP AND BUMP-OUTS AT GRADE;
Rough Framing Inspection - Commercial Partial 12/13/2017 12/13/2017 at 11:20 AM 12/13/2017
Misc
Partial Correction
12/08/2017
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. OK TO COVER WHEN READY LIGHT GAUGE STEEL FRAMING AT: SOFFITS AND VERTICAL FRAMING ABOVE HARBOR FREIGHT ENTRANCE; COLUMN WRAP AND BUMP-OUTS AT GRADE; ["BUMP-OUT" PER DETAIL 1/A310;
Rough Framing Inspection - Commercial Partial 12/18/2017 12/18/2017 at 11:35 AM 12/18/2017
Misc
Partial Correction
12/13/2017
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. OK TO COVER WHEN READY LIGHT GAUGE STEEL FRAMING AT: SOFFITS AND VERTICAL FRAMING ABOVE HARBOR FREIGHT ENTRANCE; COLUMN WRAP AND BUMP-OUTS AT GRADE; ["BUMP-OUT" PER DETAIL 1/A310; DECORATIVE COLUMN AT SE EXTERIOR CORNER OF BUILDING APPROVED
Rough Framing Inspection - Commercial Partial 12/22/2017 12/22/2017
Misc
Partial Correction
12/18/2017
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. OK TO COVER WHEN READY LIGHT GAUGE STEEL FRAMING AT: SOFFITS AND VERTICAL FRAMING ABOVE HARBOR FREIGHT ENTRANCE; COLUMN WRAP AND BUMP-OUTS AT GRADE; ["BUMP-OUT" PER DETAIL 1/A310; DECORATIVE COLUMN AT SE EXTERIOR CORNER OF BUILDING APPROVED
Above Ceiling Inspection Not Ready 1/9/2018 at 7:40 AM 01/09/2018
Above Ceiling Inspection Partial 1/12/2018 at 8:15 AM 01/12/2018
Misc
Partial Correction
01/12/2018
NEW FACADE SOFFIT AT EXISTING BUILDING OK TO COVER WHEN READY. EAST 50' OF SOFFIT/CEILING NOT READY WHERE PLUMBING STILL IN PROGRESS.
Above Ceiling Inspection Partial 1/17/2018 at 11:35 AM 01/17/2018
Misc
Partial Correction
01/17/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @: REMAINDER OF SOFFIT AT EAST EXTREMITY OF PHASE 1;
Underground Electrical Inspection - Commercial Passed 2/14/2018 2/14/2018 at 1:40 PM 02/14/2018
Electrical Service Inspection Partial 2/26/2018 2/26/2018 at 8:30 AM 02/26/2018
Electrical Service Inspection Partial 2/26/2018 at 9:40 AM 02/26/2018
Electrical Service Inspection Not Ready 2/26/2018 at 10:45 AM 02/26/2018
Electrical Service Inspection Passed 2/26/2018 at 11:35 AM 02/26/2018
Above Ceiling Inspection Partial 4/5/2018 at 9:30 AM 04/05/2018
Misc
Resolved
04/05/2018
NEW FACADE SOFFIT AT EXISTING BUILDING OK TO COVER WHEN READY. EAST 50' OF SOFFIT/CEILING NOT READY WHERE PLUMBING STILL IN PROGRESS.
Miscellaneous Correction
Partial Correction
04/05/2018
OK TO COVER WHEN READY FRAMING AND ENCLOSED SYSTEMS AT: SOFFIT AT FRONT OF 300D PLANET FITNESS;
Rough Framing Inspection - Commercial Partial 4/13/2018 4/13/2018 at 11:45 AM 04/13/2018
Misc
Partial Correction
12/22/2017
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. OK TO COVER WHEN READY LIGHT GAUGE STEEL FRAMING AT: SOFFITS AND VERTICAL FRAMING ABOVE HARBOR FREIGHT ENTRANCE; COLUMN WRAP AND BUMP-OUTS AT GRADE; ["BUMP-OUT" PER DETAIL 1/A310; DECORATIVE COLUMN AT SE EXTERIOR CORNER OF BUILDING APPROVED
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
04/13/2018
A204 8-9 SEE PLANS
Rough Framing Inspection - Commercial Partial 4/26/2018 4/26/2018 at 10:10 AM 04/26/2018
Misc
Partial Correction
04/13/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. OK TO COVER WHEN READY LIGHT GAUGE STEEL FRAMING AT: SOFFITS AND VERTICAL FRAMING ABOVE HARBOR FREIGHT ENTRANCE; COLUMN WRAP AND BUMP-OUTS AT GRADE; ["BUMP-OUT" PER DETAIL 1/A310; DECORATIVE COLUMN AT SE EXTERIOR CORNER OF BUILDING APPROVED
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
04/26/2018
A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER.
Rough Framing Inspection - Commercial Failed 5/4/2018 5/4/2018 at 9:50 AM 05/04/2018
Misc
Partial Correction
04/26/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. OK TO COVER WHEN READY LIGHT GAUGE STEEL FRAMING AT: SOFFITS AND VERTICAL FRAMING ABOVE HARBOR FREIGHT ENTRANCE; COLUMN WRAP AND BUMP-OUTS AT GRADE; ["BUMP-OUT" PER DETAIL 1/A310; DECORATIVE COLUMN AT SE EXTERIOR CORNER OF BUILDING APPROVED
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
04/26/2018
A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER.
Misc
Corrective Action Required
05/04/2018
HANGING FACIA AT SW OF PLANTER FITNESS: SCREW ALL FLANGES OF TENSION STUDS AT TOP & BOTTOM TRACKS;
Rough Framing Inspection - Commercial Partial 5/7/2018 at 10:25 AM 05/07/2018
Misc
Partial Correction
05/04/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. OK TO COVER WHEN READY LIGHT GAUGE STEEL FRAMING AT: SOFFITS AND VERTICAL FRAMING ABOVE HARBOR FREIGHT ENTRANCE; COLUMN WRAP AND BUMP-OUTS AT GRADE; "BUMP-OUT" PER DETAIL 1/A310; DECORATIVE COLUMN AT SE EXTERIOR CORNER OF BUILDING APPROVED; A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; [AT FRONT OF SPACE 306;
THE FOLLOWING AREAS ARE APPROVED
Resolved
05/07/2018
Misc
Resolved
05/07/2018
HANGING FACIA AT SW OF PLANTER FITNESS: SCREW ALL FLANGES OF TENSION STUDS AT TOP & BOTTOM TRACKS;
Rough Framing Inspection - Commercial Partial 5/10/2018 5/10/2018 at 11:45 AM 05/10/2018
Misc
Partial Correction
05/07/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. OK TO COVER WHEN READY LIGHT GAUGE STEEL FRAMING AT: SOFFITS AND VERTICAL FRAMING ABOVE HARBOR FREIGHT ENTRANCE; COLUMN WRAP AND BUMP-OUTS AT GRADE; "BUMP-OUT" PER DETAIL 1/A310; DECORATIVE COLUMN AT SE EXTERIOR CORNER OF BUILDING APPROVED; A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; [NW TO COLUMN IN FRONT OF DOOR @ 310;
Footing Inspection - Commercial Partial 5/11/2018 5/11/2018 at 1:30 PM 05/11/2018
Misc
Partial Correction
12/08/2017
OK TO POUR WHEN READY TWO FOOTINGS PER SECTION 01/S4.7 AND SECTION 02/S4.1;
Misc
Partial Correction
05/11/2018
FOOTING AT 6A203: CONCRETE CONTRACTOR STATES WILL FLOAT IN #6 MATS; NO VERTICAL BARS PER DRAWING
Rough Framing Inspection - Commercial Partial 5/22/2018 5/22/2018 at 10:45 AM 05/22/2018
Misc
Partial Correction
05/10/2018
OK TO INSTALL WHEN READY SHEATHING TO NEW/MODIFIED FRAMING AT FACADE VERTICAL FACE AND SOFFIT AT LOCATION: A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; [N/NW TO DOOR @ 314;
Rough Framing Inspection - Commercial Partial 5/22/2018 05/22/2018
Misc
Partial Correction
05/22/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; [N/NW TO DOOR @ 314;
Rough Framing Inspection - Commercial Partial 6/6/2018 6/6/2018 at 1:10 PM 06/06/2018
Misc
Partial Correction
05/22/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; [W TO 316 & 318;
Rough Framing Inspection - Commercial Partial 6/12/2018 6/12/2018 at 10:15 AM 06/12/2018
Misc
Partial Correction
06/06/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; [W THROUGH 322;
Rough Framing Inspection - Commercial Partial 6/20/2018 6/20/2018 at 11:50 AM 06/20/2018
Misc
Partial Correction
06/12/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; [W THROUGH 332;
Rough Framing Inspection - Commercial Partial 7/5/2018 at 11:25 AM 07/05/2018
Misc
Partial Correction
06/20/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; [W TO WEST SIDE OF MAIN ENTRANCE OF 332;
Footing Inspection - Commercial Partial 7/9/2018 (1:30) 7/9/2018 at 2:00 PM 07/09/2018
Misc
Partial Correction
05/11/2018
OK TO POUR WHEN READY TWO FOOTINGS PER SECTION 01/S4.7 AND SECTION 02/S4.1; FOOTING AT 6A203: CONCRETE CONTRACTOR STATES WILL FLOAT IN #6 MATS -- NO VERTICAL BARS PER DRAWING; FOOTING EXTENSION PER DETAIL 15/S3.0 PINNED TO EXISTING SUBSTRUCTURE AT EAST OUTER COLUMN AT ENTRANCE TO SPACE 332;
Misc
Resolved
07/09/2018
FOOTING AT 6A203: CONCRETE CONTRACTOR STATES WILL FLOAT IN #6 MATS; NO VERTICAL BARS PER DRAWING
Rough Framing Inspection - Commercial Partial 7/12/2018 at 9:00 AM 07/12/2018
Misc
Partial Correction
07/05/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; [W TO WEST SIDE OF MAIN ENTRANCE OF 332; NEW WALL & SOFFIT WEST THROUGH ALL THREE COLUMNS AT 332;
Rough Framing Inspection - Commercial Partial 7/17/2018 7/17/2018 at 8:40 AM 07/17/2018
Misc
Partial Correction
07/12/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; [W TO WEST SIDE OF MAIN ENTRANCE OF 332; NEW WALL & SOFFIT WEST THROUGH ALL THREE COLUMNS AT 332; WEST TO 2ND COLUMN WEST AT UNIT 340;
Rough Framing Inspection - Commercial Partial 7/23/2018 7/23/2018 at 3:00 PM 07/23/2018
Misc
Partial Correction
07/17/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; [W TO WEST SIDE OF MAIN ENTRANCE OF 332; NEW WALL & SOFFIT WEST THROUGH ALL THREE COLUMNS AT 332; WEST TO 2ND COLUMN WEST AT UNIT 340;340-346;
Rough Framing Inspection - Commercial Partial 8/9/2018 8/9/2018 at 3:25 PM 08/09/2018
Misc
Partial Correction
07/23/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; W TO WEST SIDE OF MAIN ENTRANCE OF 332; NEW WALL & SOFFIT WEST THROUGH ALL THREE COLUMNS AT 332; WEST TO 2ND COLUMN WEST AT UNIT 340;340-346; MAIN ENTRANCE AT 346;
Rough Framing Inspection - Commercial Partial 8/15/2018 8/15/2018 at 11:45 AM 08/15/2018
Misc
Partial Correction
08/09/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; W TO WEST SIDE OF MAIN ENTRANCE OF 332; NEW WALL & SOFFIT WEST THROUGH ALL THREE COLUMNS AT 332; WEST TO 2ND COLUMN WEST AT UNIT 340;340-346; MAIN ENTRANCE AT 346; WEST TO WITHIN 12' OF WEST END OF STRIP;
Rough Framing Inspection - Commercial Partial 8/21/2018 8/21/2018 at 2:10 PM 08/21/2018
Misc
Partial Correction
08/15/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; W TO WEST SIDE OF MAIN ENTRANCE OF 332; NEW WALL & SOFFIT WEST THROUGH ALL THREE COLUMNS AT 332; WEST TO 2ND COLUMN WEST AT UNIT 340;340-346; MAIN ENTRANCE AT 346; WEST TO WITHIN 12' OF WEST END OF STRIP; COMPLETE TO WEST END OF STRIP;
Rough Framing Inspection - Commercial Partial 9/10/2018 9/10/2018 at 9:00 AM 09/10/2018
Misc
Partial Correction
08/21/2018
OK WHEN READY TO INSTALL SHEATHING TO FACADE VERTICAL FACE ABOVE SOFFIT ELEVATION. A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; W TO WEST SIDE OF MAIN ENTRANCE OF 332; NEW WALL & SOFFIT WEST THROUGH ALL THREE COLUMNS AT 332; WEST TO 2ND COLUMN WEST AT UNIT 340;340-346; MAIN ENTRANCE AT 346; WEST TO WITHIN 12' OF WEST END OF STRIP; COMPLETE TO WEST END OF STRIP; OK TO COVER FACADE SOFFIT AND FACIA FRAMING AND ELECTRICAL WIRING/FIXTURES AT EAST END OF STRIP: EAST ELEVATION COMPLETE;
Rough Framing Inspection - Commercial Partial 9/17/2018 9/17/2018 at 9:35 AM 09/17/2018
Misc
Partial Correction
09/10/2018
OK TO COVER FACADE SOFFIT AND FACIA FRAMING AND ELECTRICAL WIRING/FIXTURES AT EAST END OF STRIP: EAST ELEVATION COMPLETE; SOUTH ELEVATION AT 276, 278, 280; A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; W TO WEST SIDE OF MAIN ENTRANCE OF 332; NEW WALL & SOFFIT WEST THROUGH ALL THREE COLUMNS AT 332; WEST TO 2ND COLUMN WEST AT UNIT 340;340-346; MAIN ENTRANCE AT 346; WEST TO WITHIN 12' OF WEST END OF STRIP; COMPLETE TO WEST END OF STRIP;
Rough Framing Inspection - Commercial Partial 9/28/2018 at 10:00 AM 09/28/2018
Misc
Partial Correction
09/17/2018
OK TO COVER FACADE SOFFIT AND FACIA FRAMING AND ELECTRICAL WIRING/FIXTURES AT EAST END OF STRIP: EAST ELEVATION COMPLETE; SOUTH ELEVATION AT 276, 278, 280; 282;284;286;290 A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; W TO WEST SIDE OF MAIN ENTRANCE OF 332; NEW WALL & SOFFIT WEST THROUGH ALL THREE COLUMNS AT 332; WEST TO 2ND COLUMN WEST AT UNIT 340;340-346; MAIN ENTRANCE AT 346; WEST TO WITHIN 12' OF WEST END OF STRIP; COMPLETE TO WEST END OF STRIP;
Rough Framing Inspection - Commercial Partial 10/11/2018 at 9:40 AM 10/11/2018
Misc
Partial Correction
09/28/2018
OK TO COVER FACADE SOFFIT AND FACIA FRAMING AND ELECTRICAL WIRING/FIXTURES AT EAST END OF STRIP: EAST ELEVATION COMPLETE; SOUTH ELEVATION AT 276, 278, 280; 282;284;286;290 A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; W TO WEST SIDE OF MAIN ENTRANCE OF 332; NEW WALL & SOFFIT WEST THROUGH ALL THREE COLUMNS AT 332; WEST TO 2ND COLUMN WEST AT UNIT 340;340-346; MAIN ENTRANCE AT 346; WEST TO WITHIN 12' OF WEST END OF STRIP; COMPLETE TO WEST END OF STRIP; EAST END OF STRIP WEST THROUGH SUITE 290;
Rough Framing Inspection - Commercial Partial 10/12/2018 at 10:35 AM 10/12/2018
Misc
Partial Correction
10/11/2018
OK TO COVER FACADE SOFFIT AND FACIA FRAMING AND ELECTRICAL WIRING/FIXTURES AT EAST END OF STRIP: EAST ELEVATION COMPLETE; SOUTH ELEVATION AT 276, 278, 280; 282;284;286;290 A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; W TO WEST SIDE OF MAIN ENTRANCE OF 332; NEW WALL & SOFFIT WEST THROUGH ALL THREE COLUMNS AT 332; WEST TO 2ND COLUMN WEST AT UNIT 340;340-346; MAIN ENTRANCE AT 346; WEST TO WITHIN 12' OF WEST END OF STRIP; COMPLETE TO WEST END OF STRIP; EAST END OF STRIP WEST THROUGH SUITE 290; WEST ACROSS FRONT OF 296;
Rough Framing Inspection - Commercial Passed 10/24/2018 10/24/2018 at 1:40 PM 10/24/2018
Misc
Resolved
10/24/2018
OK TO COVER FACADE SOFFIT AND FACIA FRAMING AND ELECTRICAL WIRING/FIXTURES AT EAST END OF STRIP: EAST ELEVATION COMPLETE; SOUTH ELEVATION AT 276, 278, 280; 282;284;286;290 A204 8-9 SEE PLANS; AREA DUE WEST OF PLANET FITNESS TO CORNER; AT FRONT OF SPACE 306; NW TO COLUMN IN FRONT OF DOOR @ 310; N/NW TO DOOR @ 314; W TO 316 & 318; W THROUGH 322; W TO WEST SIDE OF MAIN ENTRANCE OF 332; NEW WALL & SOFFIT WEST THROUGH ALL THREE COLUMNS AT 332; WEST TO 2ND COLUMN WEST AT UNIT 340;340-346; MAIN ENTRANCE AT 346; WEST TO WITHIN 12' OF WEST END OF STRIP; COMPLETE TO WEST END OF STRIP; EAST END OF STRIP WEST THROUGH SUITE 290; WEST ACROSS FRONT OF 296;
Footing Inspection - Commercial Passed 7/9/2018 10/24/2018
Misc
Resolved
10/24/2018
OK TO POUR WHEN READY TWO FOOTINGS PER SECTION 01/S4.7 AND SECTION 02/S4.1; FOOTING AT 6A203: CONCRETE CONTRACTOR STATES WILL FLOAT IN #6 MATS -- NO VERTICAL BARS PER DRAWING; FOOTING EXTENSION PER DETAIL 15/S3.0 PINNED TO EXISTING SUBSTRUCTURE AT EAST OUTER COLUMN AT ENTRANCE TO SPACE 332;
Above Ceiling Inspection Passed 4/5/2018 10/24/2018
Miscellaneous Correction
Resolved
10/24/2018
OK TO COVER WHEN READY FRAMING AND ENCLOSED SYSTEMS AT: SOFFIT AT FRONT OF 300D PLANET FITNESS;
Final Inspection - Commercial Passed 7/12/2018 11/30/2018 at 7:55 AM 11/30/2018
Corrective Action Required
01/12/2018
Documents & Images
Date Uploaded File Type Document Name
08/18/2017 Letter Fire Building Plan Review
08/18/2017 Letter Codes P/R Corrections Document
09/19/2017 Letter Fire Building Plan Review
09/20/2017 Letter Codes P/R Corrections Document
11/14/2017 Receipt Receipt for transaction: 2017-007275
11/14/2017 Letter Codes Building Permit
11/14/2017 Letter Codes Plan Review Conditions
12/05/2017 Letter Inspection Summary
12/08/2017 Letter Inspection Summary
12/13/2017 Letter Inspection Summary
12/18/2017 Letter Inspection Summary
12/22/2017 Letter Inspection Summary
01/12/2018 Letter Inspection Summary
01/17/2018 revised drawings
01/17/2018 Letter Inspection Summary
01/30/2018 RE Pine Tree Plaza Facade
01/31/2018 Letter Fire Building Plan Review
02/14/2018 Letter Inspection Summary
02/26/2018 Letter Inspection Summary
04/05/2018 Letter Inspection Summary
04/13/2018 Letter Inspection Summary
04/13/2018 Letter Inspection Summary
04/26/2018 Letter Inspection Summary
05/04/2018 Letter Inspection Summary
05/07/2018 Letter Inspection Summary
05/10/2018 Letter Inspection Summary
05/11/2018 Letter Inspection Summary
05/22/2018 Letter Inspection Summary
05/22/2018 Letter Inspection Summary
06/06/2018 Letter Inspection Summary
06/12/2018 Letter Inspection Summary
06/20/2018 Letter Inspection Summary
07/05/2018 Letter Inspection Summary
07/09/2018 Letter Inspection Summary
07/12/2018 Letter Inspection Summary
07/17/2018 Letter Inspection Summary
07/23/2018 Letter Inspection Summary
08/09/2018 Letter Inspection Summary
08/15/2018 Letter Inspection Summary
08/21/2018 Letter Inspection Summary
09/10/2018 Letter Inspection Summary
09/17/2018 Letter Inspection Summary
09/28/2018 Letter Inspection Summary
10/11/2018 Letter Inspection Summary
10/12/2018 Letter Inspection Summary
10/24/2018 Letter Inspection Summary
11/30/2018 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home