Summary
PRCOM20172500
Building Permit - Commercial
Certificate of Occupancy
PARROT PROPERTIES INC
NEW COMMERCIAL
NEW CLUBHOUSE WITH DOG GROOMING AND GYM FOUNDATION PERMIT - PRCOM20180696
07/24/2017
01/02/2019
01/31/2018
08/30/2021
Locations
Contacts
CITYSCAPE CONSTRUCTION VIEW HIGH LLC, Address:10 W CARMEL DR STE 200, Phone:(317) 574-1600 Ext:100  
STANDARD HEATING & COOLING TOO LLC, Address:2006 E PRAIRIE CIRCLE , Phone:(913) 782-5409  
STANDARD ELECTRIC TOO LLC, Address:2006 E PRAIRIE CIRCLE, Phone:(913) 782-5409  
GARRISON PLUMBING, Address:15430 S MAHAFFIE ST STE 102, Phone:(913) 768-1311  
SGN+A ARCHITECTS, Address:315 W PONCE DE LEON AVE #755, Phone:(404) 373-7370  
PARROT PROPERTIES INC, Address:11303 VIEW HIGH DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 12/04/2018
Joe Dir
Miscellaneous Correction
Resolved
12/04/2018

Dry System Inspectors test valves ACTION REQUIRED: Plans need to indicate the location of the dry system inspectors test valves on all buildings.
Misc
Resolved
12/04/2018

Post Indicator Valves ACTION REQUIRED: Take the PIVs out of the plans, PIVs are not required for these buildings.
Installation acceptance testing
Corrective Action Required
12/04/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Field tests and acceptance testing for each building will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Sprinkler Plan Review Rejected 11/19/2018
Joe Dir
Miscellaneous Correction
Corrective Action Required
11/19/2018

Dry System Inspectors test valves ACTION REQUIRED: Plans need to indicate the location of the dry system inspectors test valves on all buildings.
Misc
Corrective Action Required
11/19/2018

Post Indicator Valves ACTION REQUIRED: Take the PIVs out of the plans, PIVs are not required for these buildings.
Licensed Contractors Approved 08/22/2017 11/08/2018
Dawn Bell
LC - General Contractor
Resolved
03/15/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 8/24/17 - acknowledged.
LC - MEP Subs
Resolved
11/08/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 8/24/17 - acknowledged.
Sprinkler Plan Review Rejected 09/19/2018
Joe Dir
Building Plan Review Approved with Conditions 08/29/2017 02/16/2018
Joe Frogge
Final Development Plan
Resolved
02/16/2018

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 8/24/17 - acknowledged.
Project cost
Resolved
02/16/2018

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes. We need a cost breakdown per structure. 8/24/17 - acknowledged.
Gen - Submittal documents 7-137
Resolved
08/24/2017

Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. **Missouri Board for Architects, Professional Engineers, Professional Land Surveyors and Professional Landscape Architects – Board Rules, Division 2030 – Chapter 3, 20 CSR 2030-3.060 Licensees SealDocuments must bear design professionals original seal with signature and date. (relevant portion paraphrased – reference original document for additional information) Action required: Provide at least one set with original seal/signature/date. All drawings must be sealed including H series.
Plan Submittal 2012 Codes
Resolved
08/24/2017

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Update cover sheet to reflect the use of the 2009 ICC/ANSI A117.1 for accessibility design/review.
Code analysis required
Resolved
08/24/2017

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Include occupant loads in code analysis.
Elevator Certificate of Inspection
Corrective Action Required
08/22/2017

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated prusuant to sections 701.350 to 701.380. Action required: Comment is for informational purposes. 8/24/17 - acknowledged.
Elevator Equipment Permit
Corrective Action Required
08/22/2017

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is for informational purposes. 8/24/17 - acknowledged.
Elevator Equipment Inspection
Corrective Action Required
08/22/2017

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration. Action required: Comment is for informational purposes. 8/24/17 - acknowledged.
Engineered truss package
Corrective Action Required
08/22/2017

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof and floor truss packages or request deferral. 8/24/17 - deferred to construction per request.
Screening - Ground mounted equipment
Resolved
08/24/2017

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Bldg - Common path of egress travel 1014.3
Resolved
08/24/2017

2012 IBC 1014.3 – Common path of egress travel. The common path of egress travel shall not exceed the common path of egress travel distances in Table 1014.3. Action required: Common path exceeded when exiting from theater room. Modify design to comply.
Bldg - Toilet room wall finish 1210.2.2
Resolved
08/24/2017

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant materials at Staff Toilet 117 and toilet 110.
Misc
Resolved
08/24/2017

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide exit sign and exterior emergency light at door L6 out of vestibule.
Bldg - Attic access 1209.2
Resolved
08/24/2017

2012 IBC 1209.2 – Attic spaces. An opening not less than 20 inches by 30 inches shall be provided to any attic area having a clear height of over 30 inches. Clear headroom of not less than 30 inches shall be provided in the attic space at or above the access opening. Action required: Provide attic access.
Misc
Resolved
08/24/2017

Flue design at pool equipment room incomplete. Action required: Clarify use of flue shown on mechanical drawings. a) is a heater to be installed? if so, a design is required. b) how is flue routed on upper floor? 8/24/17 - heater deleted.
Misc
Corrective Action Required
08/22/2017

2012 IPC 502.1 General. Water heaters shall be installed in accordance with the manufacturer’s installation instructions. Oil-fired water heaters shall conform to the requirements of this code and the International Mechanical Code. Electric water heaters shall conform to the requirements of this code and provisions of NFPA 70. Gas-fired water heaters shall conform to the requirements of the International Fuel Gas Code. Action required: Provide expansion tanks at water heaters or provide verification that water heaters installed will not require expansion tanks in the manufacturer's written instructions. 8/24/17 - Approved contingent upon approval by manufacturer. Field Verify.
Final Development Plan Review Approved 08/07/2018 02/16/2018
Joe Frogge
Fire Plan Review Approved with Conditions 08/29/2017 08/23/2017
Joe Dir
Address numbers required
Corrective Action Required
08/22/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Address shall be readable from the roadway.
Portable fire extinguishers - general
Corrective Action Required
08/22/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of one 2A-10BC fire extinguisher on each level of the building. Fire extinguishers shall be mounted on a normal path of travel close to an exit.
Misc
Corrective Action Required
08/22/2017

Door operations: ACTION REQUIRED:No keyed locks on the egress side of an exit B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ACTION REQUIRED: controlled access card readers [B] 1008.1.9.8  Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public.
Posting of occupant load
Resolved
08/23/2017

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED: figure and post the occpant loads for the theatre, lounge and fitness areas
Misc
Resolved
08/23/2017

Civil plans: ACTION REQUIRED: Provide civil plans showing the location of fire hydrants. 507.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet (122 m) from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.
Building Plan Review Rejected 08/07/2017 08/04/2017
Joe Frogge
Final Development Plan
Corrective Action Required
08/04/2017

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Project cost
Corrective Action Required
08/04/2017

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes. We need a cost breakdown per structure.
Gen - Submittal documents 7-137
Corrective Action Required
08/04/2017

Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. **Missouri Board for Architects, Professional Engineers, Professional Land Surveyors and Professional Landscape Architects – Board Rules, Division 2030 – Chapter 3, 20 CSR 2030-3.060 Licensees SealDocuments must bear design professionals original seal with signature and date. (relevant portion paraphrased – reference original document for additional information) Action required: Provide at least one set with original seal/signature/date. All drawings must be sealed including H series.
Plan Submittal 2012 Codes
Corrective Action Required
08/04/2017

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Update cover sheet to reflect the use of the 2009 ICC/ANSI A117.1 for accessibility design/review.
Code analysis required
Corrective Action Required
08/04/2017

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Include occupant loads in code analysis.
Elevator Certificate of Inspection
Corrective Action Required
08/04/2017

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated prusuant to sections 701.350 to 701.380. Action required: Comment is for informational purposes.
Elevator Equipment Permit
Corrective Action Required
08/04/2017

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is for informational purposes.
Elevator Equipment Inspection
Corrective Action Required
08/04/2017

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration. Action required: Comment is for informational purposes.
Engineered truss package
Corrective Action Required
08/04/2017

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof and floor truss packages or request deferral.
Screening - Ground mounted equipment
Corrective Action Required
08/04/2017

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Bldg - Common path of egress travel 1014.3
Corrective Action Required
08/04/2017

2012 IBC 1014.3 – Common path of egress travel. The common path of egress travel shall not exceed the common path of egress travel distances in Table 1014.3. Action required: Common path exceeded when exiting from theater room. Modify design to comply.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
08/04/2017

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant materials at Staff Toilet 117 and toilet 110.
Misc
Corrective Action Required
08/04/2017

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide exit sign and exterior emergency light at door L6 out of vestibule.
Bldg - Attic access 1209.2
Corrective Action Required
08/04/2017

2012 IBC 1209.2 – Attic spaces. An opening not less than 20 inches by 30 inches shall be provided to any attic area having a clear height of over 30 inches. Clear headroom of not less than 30 inches shall be provided in the attic space at or above the access opening. Action required: Provide attic access.
Misc
Corrective Action Required
08/04/2017

Flue design at pool equipment room incomplete. Action required: Clarify use of flue shown on mechanical drawings. a) is a heater to be installed? if so, a design is required. b) how is flue routed on upper floor?
Misc
Corrective Action Required
08/04/2017

2012 IPC 502.1 General. Water heaters shall be installed in accordance with the manufacturer’s installation instructions. Oil-fired water heaters shall conform to the requirements of this code and the International Mechanical Code. Electric water heaters shall conform to the requirements of this code and provisions of NFPA 70. Gas-fired water heaters shall conform to the requirements of the International Fuel Gas Code. Action required: Provide expansion tanks at water heaters or provide verification that water heaters installed will not require expansion tanks in the manufacturer's written instructions.
Licensed Contractors Rejected 08/07/2017 08/04/2017
Joe Frogge
LC - General Contractor
Corrective Action Required
08/04/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
08/04/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 08/07/2017 08/01/2017
Joe Dir
Address numbers required
Corrective Action Required
08/01/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Address shall be readable from the roadway.
Portable fire extinguishers - general
Corrective Action Required
08/01/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of one 2A-10BC fire extinguisher on each level of the building. Fire extinguishers shall be mounted on a normal path of travel close to an exit.
Misc
Corrective Action Required
08/01/2017

Door operations: ACTION REQUIRED:No keyed locks on the egress side of an exit B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ACTION REQUIRED: controlled access card readers [B] 1008.1.9.8  Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public.
Posting of occupant load
Corrective Action Required
08/01/2017

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED: figure and post the occpant loads for the theatre, lounge and fitness areas
Misc
Corrective Action Required
08/01/2017

Civil plans: ACTION REQUIRED: Provide civil plans showing the location of fire hydrants. 507.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet (122 m) from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Commercial $1,003.90 $1,003.90 Paid 11/21/2018
8331507-Sewer Connection Fee $480.00 $480.00 Paid 11/21/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Partial 3/6/2019 3/6/2019 03/06/2019
Misc
Partial Correction
03/06/2019
SUBMIT SPECIAL INSPECTION FOR SHEAR WALL FRAMING.
All Rough Inspection - Commercial Failed 4/9/2019 04/09/2019
Misc
Corrective Action Required
04/09/2019
- 1st floor -Protect NM cable within 1 1/4" from edge of studs. -Firestop all floor ceiling penetrations, between floor and attic. -Support Plumbing at Mid-story between floors and at 48"o.c -protect Nm within 6' of attic access - Move south attic access for headroom clearance. -Truss T04 missing hanger. - Firestop open chases between floor levels , sprinkler riser chase, chase right of elevator, heat chase, dbl wall chase left of stairs. Basement*- Plumbing protection in basement bath. support DWV in ceiling. -Turn clean outs in walls where accessible. - Tie ground in electrcial boxes. -Secrue electrcial in ceiling. -Plate bolts at exterior basement walls. ** -Provide structrual 3rd party report. -Verify structual ties at foyer entry and rear center walls. -Truss bearing on triple Girter truss at ends. -Nail 3 ply truss per plans
Misc
Corrective Action Required
04/09/2019
Stairs not installed at 1st rough inspection.
All Rough Inspection - Commercial Failed 4/11/2019 4/11/2019 04/11/2019
Misc
Corrective Action Required
04/09/2019
- 1st floor . -Firestop all floor ceiling penetrations, between floor and attic. -Support Plumbing at Mid-story between floor all locations. - - Firestop open chases between floor levels ,chase right of elevator, dbl wall chase left of stairs. Seal gaps. Basement*- -firestop south end at tan room and over tv room box out. -Turn clean outs in walls where accessible. Pool room wall ** -Provide structrual 3rd party report. -Verify structual ties at foyer entry and rear center walls. -Truss bearing on triple Girter truss at ends of foyer
Misc
Corrective Action Required
04/09/2019
Stairs not installed at 1st rough inspection.
All Rough Inspection - Commercial Partial 4/12/2019 04/12/2019
Misc
Resolved
04/12/2019
Misc
Corrective Action Required
04/11/2019
Stairs not installed at 1st rough inspection. Provide Special inspection report
Rated Assembly Inspection Passed 4/23/2019 4/23/2019 04/23/2019
Rated Assembly Inspection Partial 4/25/2019 4/25/2019 04/25/2019
Misc
Informational
04/25/2019
1st layer elevator
Rated Assembly Inspection Passed 5/2/2019 5/2/2019 05/02/2019
Misc
Informational
04/25/2019
1st layer elevator 2nd layer
All Rough Inspection - Commercial Failed 5/14/2019 05/14/2019
Misc
Corrective Action Required
04/12/2019
Stairs not installed at 1st rough inspection. Stairs - untreated lumber installed against concrete wall. install joist hangers. Provide Special inspection report
All Rough Inspection - Commercial Partial 5/16/2019 5/16/2019 05/16/2019
Misc
Corrective Action Required
05/14/2019
Provide Special inspection report
Above Ceiling Inspection Partial 6/4/2019 6/4/2019 06/04/2019
LOWER LEVEL
Corrective Action Required
06/04/2019
COMPLETE WALL INTO MEDIA ROOM AND SECURE ELECTRCIAL. TIE ALL GROUNDS IN CEILING BOXES. SECURE ALL NM WITHIN 12" OF BOX, AND 4.5FT O.C. TERMINATE ELECT TO CEILING BOX AT CEILING OF MEDIA ROOM. CLOSET AT REAR OF MEDIA ROOM INCOMPLETE.
FIRST FLOOR
Corrective Action Required
06/04/2019
SOFFIT IN MAIL ROOM OK. SOFFIT AT FRONT FOYER NEEDS GROUNDS TIED AND NM SECURED. TIE GROUNDS AT CEILING BOXES ON DECK.
Above Ceiling Inspection Partial 6/5/2019 6/5/2019 06/05/2019
LOWER LEVEL
Corrective Action Required
06/04/2019
tie all grounds in bathrooms in lower level recall when ready ok to rock.
FIRST FLOOR
Resolved
06/05/2019
SOFFIT IN MAIL ROOM OK. SOFFIT AT FRONT FOYER NEEDS GROUNDS TIED AND NM SECURED. TIE GROUNDS AT CEILING BOXES ON DECK.
Electrical Service Inspection Passed 7/16/2019 7/16/2019 07/16/2019
Underground Electrical Inspection - Commercial Partial 7/24/2019 7/24/2019 07/24/2019
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
07/24/2019
FRONT SIDEWALK LIGHTS
Alarm Test Passed 8/30/2019 08/30/2019
Sprinkler - Hydrostatic Test Passed 3/27/2019 08/30/2019
Sprinkler - Flow Test Passed 9/5/2019 09/05/2019
Occupancy Inspection - Fire Failed 9/5/2019 09/05/2019
Above Ceiling Inspection Passed 9/5/2019 09/05/2019
LOWER LEVEL
Resolved
09/05/2019
tie all grounds in bathrooms in lower level recall when ready ok to rock.
Miscellaneous Inspection Passed 9/5/2019 09/05/2019
Misc
Resolved
09/05/2019
SUBMIT SPECIAL INSPECTION FOR SHEAR WALL FRAMING.
Occupancy Inspection - Planning Failed 9/5/2019 09/05/2019
Corrective Action Required
09/05/2019
Parking areas not complete.
Corrective Action Required
09/05/2019
Parking lot not striped.
Corrective Action Required
09/05/2019
No accessible singage or markings.
Corrective Action Required
09/05/2019
Sod was not installed.
Corrective Action Required
09/05/2019
Pool area was not complete.
All Rough Inspection - Commercial Passed 9/5/2019 09/05/2019
Misc
Resolved
09/05/2019
Provide Special inspection report
Occupancy Inspection - Codes Commercial Failed 9/5/2019 9/5/2019 09/05/2019
Misc
Corrective Action Required
09/05/2019
--Provide State inspection on Elevator. --Correct grab bars issue. --Label all electrical panels, pool room. --Provide Final special inspections report on building. Approved to stock, install permanent furniture and fixtures, tables chairs etc. NOT APPROVED FOR OCCUPANCY. NOT TO BE OPEN TO THE PUBLIC. See other departments on separate covers. Pool on separate permit. Lower level patio, access to pool room, pool deck incomplete at this inspection.
Occupancy Inspection - Fire Passed 9/16/2019 09/16/2019
Occupancy Inspection - Water Utilities Passed 9/5/2019 09/17/2019
Occupancy Inspection - Codes Commercial Failed 10/4/2019 10/4/2019 10/04/2019
Misc
Corrective Action Required
09/05/2019
Pending approval from other departments for TCO Codes, Fire , water ok for tco. Approved to stock, install permanent furniture and fixtures, tables chairs etc. NOT APPROVED FOR OCCUPANCY. NOT TO BE OPEN TO THE PUBLIC. See other departments on separate covers. Pool on separate permit. Lower level patio, access to pool room, pool deck incomplete at this inspection.
Occupancy Inspection - Engineering Temporary C of O 11/6/2019 11/05/2019
Sewer Service Inspection Passed 11/7/2019 11/07/2019
Occupancy Inspection - Codes Commercial Temporary C of O 11/7/2019 11/07/2019
Misc
Corrective Action Required
10/04/2019
Club house approved for TCO Club house Permit will be held open until project is complete and all items on 17 buildings including pool, trash enclosure, maintenance building are complete. Each building will be closed as needed.
Underground Electrical Inspection - Commercial Failed 11/15/2019 11/15/2019 11/15/2019
Misc
Corrective Action Required
11/15/2019
Site Light pole Base and conduit inspections for 28 poles: Provide engineered plans with details- plans submitted has no detail and size, grounding, pier depth etc. 1st pole light next to clubhouse already poured and was 12" in diameter. 2 was full of water and mud, 3rd north of garage #1 incomplete. electrical to pole lights incomplete. grounding incomplete.
Underground Electrical Inspection - Commercial Passed 4/13/2021 06/04/2021
Misc
Resolved
06/04/2021
Site Light pole Base and conduit inspections for 28 poles: Provide engineered plans with details- plans submitted has no detail and size, grounding, pier depth etc. 1st pole light next to clubhouse already poured and was 12" in diameter. 2 was full of water and mud, 3rd north of garage #1 incomplete. electrical to pole lights incomplete. grounding incomplete.
Occupancy Inspection - Planning Passed 6/4/2021 06/04/2021
Occupancy Inspection - Codes Commercial Temporary C of O 8/10/2021 08/10/2021
Misc
Corrective Action Required
11/07/2019
Club house approved for TCO Club house Permit will be held open until project is complete and all items on 17 buildings including pool, trash enclosure, maintenance building are complete. Each building will be closed as needed.
Occupancy Inspection - Codes Commercial Full C of O 08/30/2021
Misc
Resolved
08/30/2021
Club house approved for TCO Club house Permit will be held open until project is complete and all items on 17 buildings including pool, trash enclosure, maintenance building are complete. Each building will be closed as needed.
Documents & Images
Date Uploaded File Type Document Name
08/01/2017 Letter Fire Building Plan Review
08/04/2017 Letter Codes P/R Corrections Document
08/23/2017 Letter Fire Building Plan Review
10/16/2017 Activity Document Meridian Site Map
09/19/2018 Letter Fire (Sprinkler) Plan Review
11/19/2018 Letter Fire (Sprinkler) Plan Review
11/21/2018 Receipt Receipt for transaction: 2018-007329
12/04/2018 Letter Fire (Sprinkler) Plan Review
01/02/2019 Letter Codes Building Permit
01/02/2019 Letter Codes Plan Review Conditions
03/06/2019 Letter INSPECTION SUMMARY
04/09/2019 Letter INSPECTION SUMMARY
04/25/2019 Letter INSPECTION SUMMARY
05/02/2019 Letter INSPECTION SUMMARY
05/14/2019 Letter INSPECTION SUMMARY
05/16/2019 Letter INSPECTION SUMMARY
06/04/2019 Letter INSPECTION SUMMARY
06/05/2019 Letter INSPECTION SUMMARY
07/16/2019 Letter INSPECTION SUMMARY
07/24/2019 Letter INSPECTION SUMMARY
09/05/2019 Letter INSPECTION SUMMARY
10/04/2019 Letter INSPECTION SUMMARY
10/04/2019 Letter INSPECTION SUMMARY
11/07/2019 Letter INSPECTION SUMMARY
11/07/2019 Letter Codes Temporary Certificate of Occupancy
11/15/2019 Letter INSPECTION SUMMARY
06/04/2021 Letter INSPECTION SUMMARY
06/04/2021 Letter INSPECTION SUMMARY
08/10/2021 Letter Codes Temporary Certificate of Occupancy
08/30/2021 Letter Codes Final Certificate of Occupancy
08/30/2021 Letter Codes Final Certificate of Occupancy
08/30/2021 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home