Permit Application Status

PRCOM20172360


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20172360
Building Permit - Commercial
Certificate of Occupancy
NSI INVESTMENTS LLC
CHANGE OF TENANT
TENANT FINISH FOR TOOL SALES **invite planner to final to verify screening
07/13/2017
01/16/2018
02/13/2018
02/28/2018
Locations
Contacts
SIMMONS CONSTRUCTION, Address:P O BOX 1770, Phone:(423) 626-4518  
ACMS MECHANICAL SERVICES INC, Address:7823 COMMERCE DR, Phone:(704) 483-8793  
RODINA COMPANY INC, Address:1204 N 59TH ST, Phone:(913) 334-5336  
C & C MECHANICAL LLC, Address:470 SW 850TH RD, Phone:(816) 255-8842  
ADA ARCHITECTS INC, Address:17710 DETROIT AVE, Phone:(216) 521-5134  
NSI INVESTMENTS LLC, Address:1851 MADISON AVE STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 02/09/2018
Joe Dir
Installation acceptance testing
Corrective Action Required
02/09/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the system will be required prior to the final occupancy inspection. contact the fire department to schedule testing. (816)969-1300.
Fire Plan Review Approved with Conditions 08/24/2017 02/01/2018
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
02/01/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of the fire alarm modifications to be done.
Address numbers required
Corrective Action Required
02/01/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified atinspection) Post the suite designation for the business on the exterior of all doors leading into the business. Address shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
02/01/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(Information purposes) Have the fire sprinkler system contractor provide shop drawings of the fire sprinkler system modifications to be done.
Installation acceptance testing
Corrective Action Required
02/01/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: (information purposes) Acceptance testing of the fire sprinkler and alarm systems shall be required prior to the final occupancy inspection. to schedule testing contact the fire department at 816-969-1300.
Portable fire extinguishers - general
Corrective Action Required
02/01/2018

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) mount 2A-10BC fire extinguishers according to plan sheet A1.2
Misc
Corrective Action Required
02/01/2018

Auxillery Generators ACTION REQUIRED: Fuel cells for the generators will need labeling with type fuel to be utilized wording should include (DIESEL) The generator or fencing around the generator will need a NFPA 704 placard posted with the MSDS hazard ratings numbers in the appropriate diamonds (flammability) (Health) (Reactivity) for the diesel fuel.
Zoning Review Approved 07/25/2017 01/16/2018
Development Center
Licensed Contractors Approved 08/31/2017 01/12/2018
Development Center
LC - General Contractor
Resolved
01/12/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
01/12/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Licensed Contractors Approved 08/17/2017 01/12/2018
Development Center
LC - General Contractor
Corrective Action Required
08/17/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
08/17/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Licensed Contractors Approved 07/31/2017 01/12/2018
Development Center
LC - General Contractor
Corrective Action Required
07/31/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
07/31/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Licensed Contractors Approved 07/13/2017 01/12/2018
Development Center
LC - General Contractor
Corrective Action Required
07/17/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
07/17/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved with Conditions 08/31/2017 08/30/2017
Joe Frogge
License Tax Application
Resolved
02/02/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Screening - Rooftop equipment
Corrective Action Required
08/24/2017

Unified Development Ordinance Article 7, Section 7.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section. 8/1/17 - color of screening to match adjacent existing screening. field verify
Misc
Corrective Action Required
01/12/2018

Per LS Water department: The new water meter must be installed in line with the other meters behind the building and be protected on each side with concrete pipe bollards. To be field verified.
Fire Plan Review Approved with Conditions 08/31/2017 08/29/2017
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
08/24/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of the fire alarm modifications to be done.
Address numbers required
Corrective Action Required
08/24/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified atinspection) Post the suite designation for the business on the exterior of all doors leading into the business. Address shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
08/24/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(Information purposes) Have the fire sprinkler system contractor provide shop drawings of the fire sprinkler system modifications to be done.
Installation acceptance testing
Corrective Action Required
08/24/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: (information purposes) Acceptance testing of the fire sprinkler and alarm systems shall be required prior to the final occupancy inspection. to schedule testing contact the fire department at 816-969-1300.
Portable fire extinguishers - general
Corrective Action Required
08/24/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) mount 2A-10BC fire extinguishers according to plan sheet A1.2
Misc
Resolved
08/29/2017

shelf storage ACTION REQUIRED:(information purposes) 3207.2.1 Shelf storage. Shelf storage greater than 12 feet (3658 mm) but less than 15 feet (4572 mm) in height shall be in accordance with the fire protection requirements set forth in NFPA 13. Shelf storage 15 feet (4572 mm) or more in height shall be protected in an approved manner with special fire protection, such as in-rack sprinklers. 3207.3 Pile dimension and height limitations. Pile dimensions, the maximum permissible storage height and pile volume shall be in accordance with Table 3206.2.
Misc
Resolved
08/29/2017

Aisle width ACTION REQUIRED:(information purposes) 3206.9.1 Width. Aisle width shall be in accordance with Sections 3206.9.1.1 and 3206.9.1.2. Exceptions: 1. Aisles crossing rack structures or storage piles, which are used only for employee access, shall be a minimum of 24 inches (610 mm) wide. 2. Aisles separating shelves classified as shelf storage shall be a minimum of 30 inches (762 mm) wide. 3206.9.1.1 Sprinklered buildings. Aisles in sprinklered buildings shall be a minimum of 44 inches (1118 mm) wide. Aisles shall be a minimum of 96 inches (2438 mm) wide in high-piled storage areas exceeding 2,500 square feet (232 m2) in area, that are accessible to the public and designated to contain high-hazard commodities. Exception: Aisles in high-piled storage areas exceeding 2,500 square feet (232 m2) in area, that are accessible to the public and designated to contain high-hazard commodities, are protected by a sprinkler system designed for multiple-row racks of high-hazard commodities shall be a minimum of 44 inches (1118 mm) wide. Aisles shall be a minimum of 96 inches (2438 mm) wide in areas accessible to the public where mechanical stocking methods are used.
Building Plan Review Approved with Conditions 08/24/2017 08/18/2017
Joe Frogge
License Tax Application
Corrective Action Required
08/17/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Screening - Rooftop equipment
Corrective Action Required
08/17/2017

Unified Development Ordinance Article 7, Section 7.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section. 8/1/17 - color of screening to match adjacent existing screening. field verify
Fire Plan Review Approved with Conditions 08/24/2017 08/18/2017
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
08/17/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of the fire alarm modifications to be done.
Address numbers required
Corrective Action Required
08/17/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified atinspection) Post the suite designation for the business on the exterior of all doors leading into the business. Address shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
08/17/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(Information purposes) Have the fire sprinkler system contractor provide shop drawings of the fire sprinkler system modifications to be done.
Installation acceptance testing
Corrective Action Required
08/17/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: (information purposes) Acceptance testing of the fire sprinkler and alarm systems shall be required prior to the final occupancy inspection. to schedule testing contact the fire department at 816-969-1300.
Portable fire extinguishers - general
Corrective Action Required
08/17/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) mount 2A-10BC fire extinguishers according to plan sheet A1.2
Misc
Corrective Action Required
08/17/2017

shelf storage ACTION REQUIRED:(information purposes) 3207.2.1 Shelf storage. Shelf storage greater than 12 feet (3658 mm) but less than 15 feet (4572 mm) in height shall be in accordance with the fire protection requirements set forth in NFPA 13. Shelf storage 15 feet (4572 mm) or more in height shall be protected in an approved manner with special fire protection, such as in-rack sprinklers. 3207.3 Pile dimension and height limitations. Pile dimensions, the maximum permissible storage height and pile volume shall be in accordance with Table 3206.2.
Misc
Corrective Action Required
08/17/2017

Aisle width ACTION REQUIRED:(information purposes) 3206.9.1 Width. Aisle width shall be in accordance with Sections 3206.9.1.1 and 3206.9.1.2. Exceptions: 1. Aisles crossing rack structures or storage piles, which are used only for employee access, shall be a minimum of 24 inches (610 mm) wide. 2. Aisles separating shelves classified as shelf storage shall be a minimum of 30 inches (762 mm) wide. 3206.9.1.1 Sprinklered buildings. Aisles in sprinklered buildings shall be a minimum of 44 inches (1118 mm) wide. Aisles shall be a minimum of 96 inches (2438 mm) wide in high-piled storage areas exceeding 2,500 square feet (232 m2) in area, that are accessible to the public and designated to contain high-hazard commodities. Exception: Aisles in high-piled storage areas exceeding 2,500 square feet (232 m2) in area, that are accessible to the public and designated to contain high-hazard commodities, are protected by a sprinkler system designed for multiple-row racks of high-hazard commodities shall be a minimum of 44 inches (1118 mm) wide. Aisles shall be a minimum of 96 inches (2438 mm) wide in areas accessible to the public where mechanical stocking methods are used.
Building Plan Review Approved with Conditions 08/07/2017 08/01/2017
Joe Frogge
Misc
Resolved
08/01/2017

Drawings provided do not bear design professional's original seal. Action required: Submit at least one set of drawings with original seals. (the other 2 sets can be copies)
Misc
Resolved
08/01/2017

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Provide complete fire rated assembly construction details including nail/screw patterns and penetration details.
Misc
Resolved
08/01/2017

2012 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions) Action required: Wood blocking not allowed at RTU curbs. Revise plans.
License Tax Application
Corrective Action Required
07/31/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Screening - Rooftop equipment
Corrective Action Required
07/31/2017

Unified Development Ordinance Article 7, Section 7.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section. 8/1/17 - color of screening to match adjacent existing screening. field verify
Fire Plan Review Approved with Conditions 08/07/2017 08/01/2017
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
07/31/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of the fire alarm modifications to be done.
Address numbers required
Corrective Action Required
07/31/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified atinspection) Post the suite designation for the business on the exterior of all doors leading into the business. Address shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
07/31/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(Information purposes) Have the fire sprinkler system contractor provide shop drawings of the fire sprinkler system modifications to be done.
Installation acceptance testing
Corrective Action Required
07/31/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: (information purposes) Acceptance testing of the fire sprinkler and alarm systems shall be required prior to the final occupancy inspection. to schedule testing contact the fire department at 816-969-1300.
Portable fire extinguishers - general
Corrective Action Required
07/31/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) mount 2A-10BC fire extinguishers according to plan sheet A1.2
Misc
Resolved
08/01/2017

Seperation ACTION REQUIRED: Provide information that the seperation between the adjoining tenant on the east wall is aminimum of a 1-hour seperation. 3206.3 Separation of high-piled storage areas. High-piled storage areas shall be separated from other portions of the building where required by Sections 3206.3.1 through 3206.3.2.2.
Misc
Corrective Action Required
07/31/2017

shelf storage ACTION REQUIRED:(information purposes) 3207.2.1 Shelf storage. Shelf storage greater than 12 feet (3658 mm) but less than 15 feet (4572 mm) in height shall be in accordance with the fire protection requirements set forth in NFPA 13. Shelf storage 15 feet (4572 mm) or more in height shall be protected in an approved manner with special fire protection, such as in-rack sprinklers. 3207.3 Pile dimension and height limitations. Pile dimensions, the maximum permissible storage height and pile volume shall be in accordance with Table 3206.2.
Misc
Corrective Action Required
07/31/2017

Aisle width ACTION REQUIRED:(information purposes) 3206.9.1 Width. Aisle width shall be in accordance with Sections 3206.9.1.1 and 3206.9.1.2. Exceptions: 1. Aisles crossing rack structures or storage piles, which are used only for employee access, shall be a minimum of 24 inches (610 mm) wide. 2. Aisles separating shelves classified as shelf storage shall be a minimum of 30 inches (762 mm) wide. 3206.9.1.1 Sprinklered buildings. Aisles in sprinklered buildings shall be a minimum of 44 inches (1118 mm) wide. Aisles shall be a minimum of 96 inches (2438 mm) wide in high-piled storage areas exceeding 2,500 square feet (232 m2) in area, that are accessible to the public and designated to contain high-hazard commodities. Exception: Aisles in high-piled storage areas exceeding 2,500 square feet (232 m2) in area, that are accessible to the public and designated to contain high-hazard commodities, are protected by a sprinkler system designed for multiple-row racks of high-hazard commodities shall be a minimum of 44 inches (1118 mm) wide. Aisles shall be a minimum of 96 inches (2438 mm) wide in areas accessible to the public where mechanical stocking methods are used.
Fire Plan Review Rejected 07/25/2017 07/19/2017
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
07/19/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of the fire alarm modifications to be done.
Address numbers required
Corrective Action Required
07/19/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified atinspection) Post the suite designation for the business on the exterior of all doors leading into the business. Address shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
07/19/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(Information purposes) Have the fire sprinkler system contractor provide shop drawings of the fire sprinkler system modifications to be done.
Installation acceptance testing
Corrective Action Required
07/19/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: (information purposes) Acceptance testing of the fire sprinkler and alarm systems shall be required prior to the final occupancy inspection. to schedule testing contact the fire department at 816-969-1300.
Portable fire extinguishers - general
Corrective Action Required
07/19/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) mount 2A-10BC fire extinguishers according to plan sheet A1.2
Misc
Resolved
08/01/2017

Seperation ACTION REQUIRED: Provide information that the seperation between the adjoining tenant on the east wall is aminimum of a 1-hour seperation. 3206.3 Separation of high-piled storage areas. High-piled storage areas shall be separated from other portions of the building where required by Sections 3206.3.1 through 3206.3.2.2.
Misc
Corrective Action Required
07/19/2017

shelf storage ACTION REQUIRED:(information purposes) 3207.2.1 Shelf storage. Shelf storage greater than 12 feet (3658 mm) but less than 15 feet (4572 mm) in height shall be in accordance with the fire protection requirements set forth in NFPA 13. Shelf storage 15 feet (4572 mm) or more in height shall be protected in an approved manner with special fire protection, such as in-rack sprinklers. 3207.3 Pile dimension and height limitations. Pile dimensions, the maximum permissible storage height and pile volume shall be in accordance with Table 3206.2.
Misc
Corrective Action Required
07/19/2017

Aisle width ACTION REQUIRED:(information purposes) 3206.9.1 Width. Aisle width shall be in accordance with Sections 3206.9.1.1 and 3206.9.1.2. Exceptions: 1. Aisles crossing rack structures or storage piles, which are used only for employee access, shall be a minimum of 24 inches (610 mm) wide. 2. Aisles separating shelves classified as shelf storage shall be a minimum of 30 inches (762 mm) wide. 3206.9.1.1 Sprinklered buildings. Aisles in sprinklered buildings shall be a minimum of 44 inches (1118 mm) wide. Aisles shall be a minimum of 96 inches (2438 mm) wide in high-piled storage areas exceeding 2,500 square feet (232 m2) in area, that are accessible to the public and designated to contain high-hazard commodities. Exception: Aisles in high-piled storage areas exceeding 2,500 square feet (232 m2) in area, that are accessible to the public and designated to contain high-hazard commodities, are protected by a sprinkler system designed for multiple-row racks of high-hazard commodities shall be a minimum of 44 inches (1118 mm) wide. Aisles shall be a minimum of 96 inches (2438 mm) wide in areas accessible to the public where mechanical stocking methods are used.
Building Plan Review Rejected 07/25/2017 07/17/2017
Joe Frogge
Misc
Corrective Action Required
07/17/2017

Drawings provided do not bear design professional's original seal. Action required: Submit at least one set of drawings with original seals. (the other 2 sets can be copies)
Misc
Corrective Action Required
07/17/2017

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Provide complete fire rated assembly construction details including nail/screw patterns and penetration details.
Misc
Corrective Action Required
07/17/2017

2012 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions) Action required: Wood blocking not allowed at RTU curbs. Revise plans.
License Tax Application
Corrective Action Required
07/19/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Screening - Rooftop equipment
Corrective Action Required
07/19/2017

Unified Development Ordinance Article 7, Section 7.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $898.70 $898.70 Paid 01/16/2018
8331507-Sewer Connection Fee $210.00 $210.00 Paid 01/16/2018
8331401-Water Tap Fee $8,915.00 $8,915.00 Paid 01/16/2018
8350015-Water Meter Fee $657.68 $657.68 Paid 01/16/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Partial 1/18/2018 at 8:50 AM 01/18/2018
Underslab Plumbing Inspection - Commercial Partial 1/22/2018 at 8:45 AM 01/22/2018
Misc
Partial Correction
01/22/2018
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING EXCEPT CONNECTION TO EXISTING BUILDING DRAIN. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
In-wall Inspection Partial 1/22/2018 at 9:20 AM 01/22/2018
Misc
Partial Correction
01/22/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: [WEST DEMISING WALL;
In-wall Inspection Partial 1/23/2018 1/23/2018 at 4:30 PM 01/23/2018
Misc
Partial Correction
01/22/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: WEST DEMISING WALL; [OK TO ONE-SIDE AT HANGING BULKHEAD AT [100]; TALL WALLS AT 102, 103, 110;
Rated Assembly Inspection Partial 1/25/2018 1/25/2018 at 1:20 PM 01/25/2018
Misc
Partial Correction
01/25/2018
RATED DEMISING WALL AT WEST: 5/8" TYPE X GWB AT E FACE OK TO TAPE, MUD AND FIRE-STOP;
In-wall Inspection Partial 1/25/2018 at 1:45 PM 01/25/2018
Misc
Partial Correction
01/23/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: WEST DEMISING WALL; [102, 103, 110 N & W WALLS; [INSULATION IN PLACE AT WEST DEMISING WALL WALL CAVITY EXCEPT AT N END OK TO ONE-SIDE AT: HANGING BULKHEAD AT 100; TALL WALLS AT ; [106; 107; 108
In-wall Inspection Not Ready 1/26/2018 at 8:05 AM 01/26/2018
Misc
Partial Correction
01/25/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: WEST DEMISING WALL; [102, 103, 110 N & W WALLS; [INSULATION IN PLACE AT WEST DEMISING WALL WALL CAVITY EXCEPT AT N END OK TO ONE-SIDE AT: HANGING BULKHEAD AT 100; TALL WALLS AT ; [106; 107; 108
Rated Assembly Inspection Failed 1/30/2018 1/30/2018 at 9:55 AM 01/30/2018
Misc
Partial Correction
01/25/2018
RATED DEMISING WALL AT WEST: 5/8" TYPE X GWB AT E FACE OK TO TAPE, MUD AND FIRE-STOP; WEST FACE NOT APPROVED; SCREW FIELD AT <= 12" O/C AND EDGES AT <= 8" O/C.
In-wall Inspection Partial 1/30/2018 1/30/2018 at 10:20 AM 01/30/2018
Misc
Partial Correction
01/26/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: WEST DEMISING WALL; 102, 103, [110 ALL WALLS; RESTROOMS NOT APPROVED: - NEED GROMMETS FOR WATER PIPE - NEED SHIELD/BOCA PLATES FOR PVC PIPE -- CHECK ALL - STRAP MC CABLE WITHIN 12" OF ENTRY TO BOXES
Rated Assembly Inspection Partial 1/31/2018 1/31/2018 at 8:20 AM 01/31/2018
Misc
Partial Correction
01/30/2018
RATED DEMISING WALL AT WEST: 5/8" TYPE X GWB AT EAST AND WEST FACES OK TO TAPE, MUD AND FIRE-STOP;
In-wall Inspection Partial 1/31/2018 1/31/2018 at 8:30 AM 01/31/2018
Misc
Partial Correction
01/30/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: WEST DEMISING WALL; 102, 103, 110 ALL WALLS; [RESTROOMS COMPLETE;
Underslab Plumbing Inspection - Commercial Partial 1/31/2018 at 8:45 AM 01/31/2018
Misc
Partial Correction
01/22/2018
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING EXCEPT CONNECTION TO EXISTING BUILDING DRAIN. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Misc
Partial Correction
01/31/2018
OK TO COVER WHEN READY WATER LINE ENTRY UNDER FOOTING AT NE CORNER
Footing Inspection - Commercial Not Ready 2/1/2018 (8:00) 2/1/2018 at 8:40 AM 02/01/2018
Misc
Corrective Action Required
02/01/2018
TRENCH FOOTING AT TRUCK DOOR SLAB HAS BEEN EXCAVATED AND POURED WITHOUT INSPECTION. NOT APPROVED FOR USE.
Water Service Inspection Partial 2/2/2018 (9:45) 2/2/2018 at 10:30 AM 02/02/2018
Misc
Partial Correction
02/02/2018
OK TO COVER WHEN READY WATER SERVICE LINE FROM CONNECTION AT COMPLEX MAIN TO LOCASTION OF METERE WELL YET TO BE SET.
Water Service Inspection Passed 2/7/2018 2/7/2018 at 10:10 AM 02/07/2018
Misc
Resolved
02/07/2018
OK TO COVER WHEN READY WATER SERVICE LINE FROM CONNECTION AT COMPLEX MAIN TO LOCASTION OF METER WELL YET TO BE SET.
Rated Assembly Inspection Passed 2/9/2018 2/9/2018 at 2:05 PM 02/09/2018
Misc
Resolved
02/09/2018
RATED DEMISING WALL AT WEST: 5/8" TYPE X GWB AT EAST AND WEST FACES OK TO TAPE, MUD AND FIRE-STOP;
Above Ceiling Inspection Partial 2/13/2018 2/13/2018 at 1:40 PM 02/13/2018
Misc
Partial Correction
02/13/2018
NO ISSUES FOUND WITH HVAC SYSTEMS ABOVE CEILING.
Footing Inspection - Commercial Not Ready 2/14/2018 2/14/2018 at 10:50 AM 02/14/2018
Misc
Corrective Action Required
02/01/2018
TRENCH FOOTING AT TRUCK DOOR SLAB HAS BEEN EXCAVATED AND POURED WITHOUT INSPECTION. NOT APPROVED FOR USE.
Footing Inspection - Commercial Failed 2/14/2018 at 1:20 PM 02/14/2018
Misc
Corrective Action Required
02/14/2018
TRENCH FOOTING AT TRUCK DOOR SLAB HAS BEEN EXCAVATED AND POURED WITHOUT INSPECTION. NOT APPROVED FOR USE.
Footing Inspection - Commercial Passed 2/14/2018 at 4:05 PM 02/14/2018
Misc
Resolved
02/14/2018
TRENCH FOOTING AT TRUCK DOOR SLAB HAS BEEN EXCAVATED AND POURED WITHOUT INSPECTION. NOT APPROVED FOR USE.
Above Ceiling Inspection Passed 2/15/2018 2/15/2018 at 12:25 PM 02/15/2018
Misc
Resolved
02/15/2018
NO ISSUES FOUND WITH HVAC SYSTEMS ABOVE CEILING.
Gas Service Inspection - Commercial Not Ready 2/16/2018 2/16/2018 at 4:20 PM 02/16/2018
Misc
Corrective Action Required
02/16/2018
MAKE CORRECTIONS ON GAS PIPING. THEN REQUEST PRESSURE TEST.
Misc
Corrective Action Required
02/16/2018
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Gas Piping Inspection - Commercial Failed 2/16/2018 at 3:55 PM 02/16/2018
Misc
Corrective Action Required
02/16/2018
ROOFTOP PIPING NOT CONFIGURED FOR CLEARANCE ON DIRT LEG CAPS
Misc
Corrective Action Required
02/16/2018
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING FROM METER TO AND INCLUDING ROOFTOP.
Gas Service Inspection - Commercial Passed 2/20/2018 2/20/2018 at 8:20 AM 02/20/2018
Misc
Resolved
02/20/2018
MAKE CORRECTIONS ON GAS PIPING. THEN REQUEST PRESSURE TEST.
Misc
Resolved
02/20/2018
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Miscellaneous Inspection Partial 2/20/2018 at 8:40 AM 02/20/2018
Miscellaneous Inspection Partial 2/21/2018 at 1:30 PM 02/21/2018
In-wall Inspection Passed 1/31/2018 02/21/2018
Misc
Resolved
02/21/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: WEST DEMISING WALL; 102, 103, 110 ALL WALLS; [RESTROOMS COMPLETE;
Underslab Plumbing Inspection - Commercial Passed 1/31/2018 02/21/2018
Misc
Resolved
02/21/2018
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING EXCEPT CONNECTION TO EXISTING BUILDING DRAIN. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Alarm Test Passed 2/21/2018 02/21/2018
Miscellaneous Inspection Passed 2/22/2018 at 1:50 PM 02/22/2018
Gas Piping Inspection - Commercial Passed 2/22/2018 02/22/2018
Misc
Resolved
02/22/2018
ROOFTOP PIPING NOT CONFIGURED FOR CLEARANCE ON DIRT LEG CAPS
Misc
Resolved
02/22/2018
ROOFTOP GAS PIPE NOT PAINTED
Misc
Resolved
02/22/2018
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Occupancy Inspection - Fire Partial 2/23/2018 02/23/2018
Occupancy Inspection - Codes Commercial Partial 2/23/2018 2/23/2018 at 2:10 PM 02/23/2018
Misc
Corrective Action Required
02/22/2018
- ROOFTOP GAS PIPING PIPING BLOCKS NOT COMPLETED AT UNITS. STACKED BLOCKS MUST BE FASTENED TOGETHER. WOOD BLOCKS IN CONTACT WITH ROOF MEMBRANE MUST HAVE SLIP SHEETS SCREWED TO SIDES OF BLOCKS. - ROOFTOP GAS PIPE NOT PAINTED 100% - CLEAN ALL DEBRIS OFF ROOF
Misc
Corrective Action Required
02/23/2018
ELECTRICAL SERVICE PERMANENT CONFIGURATION TO BE COMPLETED AND APPROVED.
Misc
Corrective Action Required
02/23/2018
OBTAIN FINAL APPROVAL FROM: - LS WATER DEPARTMENT - LS FIRE DEPARTMENT
Misc
Corrective Action Required
02/23/2018
OK TO SET UP FOR BUSINESS. NO PUBLIC ENTRY OR BUSINESS OPERATIONS PRIOR TO APPROVAL.
Occupancy Inspection - Planning Passed 02/23/2018
Occupancy Inspection - Codes Commercial Partial 2/27/2018 at 1:25 PM 02/27/2018
Misc
Corrective Action Required
02/23/2018
- ROOFTOP GAS PIPING PIPING BLOCKS NOT COMPLETED AT UNITS. STACKED BLOCKS MUST BE FASTENED TOGETHER. WOOD BLOCKS IN CONTACT WITH ROOF MEMBRANE MUST HAVE SLIP SHEETS SCREWED TO SIDES OF BLOCKS. - ROOFTOP GAS PIPE NOT PAINTED 100% - CLEAN ALL DEBRIS OFF ROOF
Misc
Corrective Action Required
02/23/2018
ELECTRICAL SERVICE PERMANENT CONFIGURATION TO BE COMPLETED AND APPROVED.
Misc
Corrective Action Required
02/23/2018
OBTAIN FINAL APPROVAL FROM: - LS WATER DEPARTMENT - LS FIRE DEPARTMENT
Misc
Corrective Action Required
02/23/2018
OK TO SET UP FOR BUSINESS. NO PUBLIC ENTRY OR BUSINESS OPERATIONS PRIOR TO APPROVAL.
Gas Piping Inspection - Commercial Passed 2/27/2018 02/27/2018
Misc
Resolved
02/27/2018
ROOFTOP PIPING NOT CONFIGURED FOR CLEARANCE ON DIRT LEG CAPS
Misc
Resolved
02/27/2018
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING FROM METER TO AND INCLUDING ROOFTOP.
Occupancy Inspection - Codes Commercial Partial 2/27/2018 at 2:40 PM 02/27/2018
Misc
Corrective Action Required
02/27/2018
- ROOFTOP GAS PIPING PIPING BLOCKS NOT COMPLETED AT UNITS. STACKED BLOCKS MUST BE FASTENED TOGETHER. WOOD BLOCKS IN CONTACT WITH ROOF MEMBRANE MUST HAVE SLIP SHEETS SCREWED TO SIDES OF BLOCKS. - ROOFTOP GAS PIPE NOT PAINTED 100% - CLEAN ALL DEBRIS OFF ROOF
Misc
Resolved
02/27/2018
ELECTRICAL SERVICE PERMANENT CONFIGURATION TO BE COMPLETED AND APPROVED.
Misc
Corrective Action Required
02/27/2018
OBTAIN FINAL APPROVAL FROM: - LS WATER DEPARTMENT - LS FIRE DEPARTMENT
Misc
Resolved
02/27/2018
OK TO SET UP FOR BUSINESS. NO PUBLIC ENTRY OR BUSINESS OPERATIONS PRIOR TO APPROVAL.
Occupancy Inspection - Fire Passed 2/28/2018 02/28/2018
Occupancy Inspection - Codes Commercial Full C of O 2/28/2018 at 1:15 PM 02/28/2018
Misc
Resolved
02/28/2018
- ROOFTOP GAS PIPING PIPING BLOCKS NOT COMPLETED AT UNITS. STACKED BLOCKS MUST BE FASTENED TOGETHER. WOOD BLOCKS IN CONTACT WITH ROOF MEMBRANE MUST HAVE SLIP SHEETS SCREWED TO SIDES OF BLOCKS. - ROOFTOP GAS PIPE NOT PAINTED 100% - CLEAN ALL DEBRIS OFF ROOF
Misc
Resolved
02/28/2018
OBTAIN FINAL APPROVAL FROM: - LS WATER DEPARTMENT - LS FIRE DEPARTMENT
Documents & Images
Date Uploaded File Type Document Name
07/19/2017 Letter Fire Building Plan Review
07/19/2017 Letter Codes P/R Corrections Document
08/01/2017 Letter Fire Building Plan Review
08/01/2017 Letter Codes P/R Corrections Document
08/18/2017 Letter Fire Building Plan Review
08/29/2017 Letter Fire Building Plan Review
01/12/2018 RE Harbor Freight lees summit MO
01/12/2018 Letter Codes Plan Review Conditions
01/16/2018 Receipt Receipt for transaction: 2018-000153
01/16/2018 Letter Codes Building Permit
01/22/2018 Letter Inspection Summary
01/23/2018 Letter Inspection Summary
01/25/2018 Letter Inspection Summary
01/30/2018 Letter Inspection Summary
01/31/2018 Letter Inspection Summary
02/01/2018 Letter Inspection Summary
02/01/2018 Letter Fire Building Plan Review
02/01/2018 Letter Fire Building Plan Review
02/02/2018 Letter Codes P/R Corrections Document
02/02/2018 Letter Inspection Summary
02/07/2018 Letter Inspection Summary
02/09/2018 Letter Fire (Alarm) Plan Review Notice
02/09/2018 Letter Fire (Alarm) Plan Review Notice
02/09/2018 Letter Inspection Summary
02/14/2018 Letter Inspection Summary
02/14/2018 Letter Inspection Summary
02/15/2018 Letter Inspection Summary
02/16/2018 Letter Inspection Summary
02/20/2018 Letter Inspection Summary
02/23/2018 Letter Inspection Summary
02/28/2018 Letter Field Certificate of Occupancy
03/01/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home