Permit Application Status

PRCOM20171418


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20171418
Building Permit - Commercial
Certificate of Occupancy
EMERGENT CARE ASSET HOLDINGS LLC
ALTERATION COMMERCIAL
INTERIOR ALTERATIONS TO EXISTING MEDICAL OFFICE
05/04/2017
05/25/2017
11/07/2017
07/28/2017
Locations
Contacts
DAVID E ROSS CONSTRUCTION CO, Address:10201 E 75TH ST, Phone:(816) 737-2953  
RAND CONSTRUCTION COMPANY, Address:1428 W 9TH ST, Phone:(816) 421-4143  
R F FISHER ELECTRIC COMPANY LLC, Address:5299 DTC BLVD STE 600, Phone:(913) 384-1500  
RAND CONSTRUCTION COMPANY, Address:1428 W 9TH ST, Phone:(816) 421-4143  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
EMERGENT CARE ASSET HOLDINGS LLC, Address:2741 NE MCBAINE DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 06/15/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
06/15/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the fire alarm system modification will be required prior to the final occupancy inspection. To schedule a test contact the fire department at 816-969-1300.
Misc
Corrective Action Required
06/15/2017

Horn/Strobes ACTION REQUIRED: Existing toilet #207 and #206 on the plans show horn/strobe notification devices installed. The horn portion of the devices needs to be disabled or the horn/strobes need to be replaced with just strobe notification devices in the restrooms, No horns in restrooms.
Licensed Contractors Approved 05/22/2017 05/25/2017
Development Center
LC - General Contractor
Resolved
05/25/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
05/25/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
r
Building Plan Review Approved with Conditions 05/30/2017 05/25/2017
Joe Frogge
License Tax Application
Corrective Action Required
05/22/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Bldg - Toilet room wall finish 1210.2.2
Resolved
05/25/2017

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Modify finish material schedule on sheet A2 to reflect compliant materials at toilet rooms and janitor's closet.
Bldg - Means of egress horizontal projections 1003.3.3
Corrective Action Required
05/22/2017

2012 IBC 1003.3.3 - Horizontal projections. Structural elements, fixtures or furnishings shall not project horizontally from either side more than 4 inches over any walking surface between the heights of 27 inches and 80 inches above the walking surface. Action required: Barn doors and hardware to comply with horizontal projections requirements. To be field verified.
Bldg - Accessibility - Kitchens and kitchenettes 1109.4
Resolved
05/25/2017

2012 IBC 1109.4 – Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible. Action required: Provide compliant countertops at lounge. (max. 34" high) 5/25/17 - clarified - meets exception
Plumb - Indirect/Special Waste - Where required 802.1
Resolved
05/25/2017

2012 IPC 802.1 Where required. Food-handling equipment and clear-water waste shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. All health-care related fixtures, devices and equipment shall discharge to the drainage system through an indirect waste pipe by means of an air gap in accordance with this chapter and section 713.3. Fixtures not required by this section to be indirectly connected shall be directly connected to the plumbing system in accordance with Chapter 7. Action required: Provide indirect drain at ice machine.
Misc
Resolved
05/25/2017

Inadequate information to complete review. Provide the following: - Provide wire and wire insulation spec. 5/25/17 - provided - Rooftop condensing unit screening (existing?) 5/25/17 - existing - Convenience power to serve rooftop equipment. 5/25/17 - existing
Misc
Resolved
05/25/2017

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected. 5/25/17 -
Misc
Resolved
05/25/2017

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles. 2. Metal Boxes and enclosures containing receptacles. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system. 5/25/17 - clarified
Fire Plan Review Approved with Conditions 05/30/2017 05/25/2017
Joe Dir
Misc
Resolved
05/25/2017

Egress illumination ACTION REQUIRED: Provide information if lighting in stair 115 has emergency lighting capibility. If not provide emergency lighting in stair 115. [B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. [B] 1006.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 604. [B] 1006.3.1 Illumination level under emergency power. Emergency lighting facilities shall be arranged to provide initial illumination that is at least an average of 1 footcandle (11 lux) and a minimum at any point of 0.1 footcandle (1 lux) measured along the path of egress at floor level. Illumination levels shall be permitted to decline to 0.6 footcandle (6 lux) average and a minimum at any point of 0.06 footcandle (0.6 lux) at the end of the emergency lighting time duration. A maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceeded.
Construction documents for fire alarm systems
Corrective Action Required
05/22/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of any modfication to be done to the fire alarm system.
Installation acceptance testing
Corrective Action Required
05/22/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: (information purposes) Acceptance testing of fire alarm system modifications will be required prior to the final occupancy inspection. To schedule testing contact the fire department at 816-969-`1300.
Portable fire extinguishers - general
Corrective Action Required
05/22/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED: (information purposes) If not already existing provide two fire extingusihers for each floor level. Fire extinguishers to be mounted, one fire extinguisher by each stairway entrance.
Misc
Resolved
05/25/2017

Door hardware ACTION REQUIRED:No keyed locks on the egress side of an exit [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Misc
Corrective Action Required
05/22/2017

Panic hardware ACTION REQUIRED:Occupancies with an occupant load over 50 [B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware.
Building Plan Review Rejected 05/16/2017 05/11/2017
Joe Frogge
License Tax Application
Corrective Action Required
05/11/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
05/11/2017

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Modify finish material schedule on sheet A2 to reflect compliant materials at toilet rooms and janitor's closet.
Bldg - Means of egress horizontal projections 1003.3.3
Corrective Action Required
05/11/2017

2012 IBC 1003.3.3 - Horizontal projections. Structural elements, fixtures or furnishings shall not project horizontally from either side more than 4 inches over any walking surface between the heights of 27 inches and 80 inches above the walking surface. Action required: Barn doors and hardware to comply with horizontal projections requirements. To be field verified.
Bldg - Accessibility - Kitchens and kitchenettes 1109.4
Corrective Action Required
05/11/2017

2012 IBC 1109.4 – Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible. Action required: Provide compliant countertops at lounge. (max. 34" high)
Plumb - Indirect/Special Waste - Where required 802.1
Corrective Action Required
05/11/2017

2012 IPC 802.1 Where required. Food-handling equipment and clear-water waste shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. All health-care related fixtures, devices and equipment shall discharge to the drainage system through an indirect waste pipe by means of an air gap in accordance with this chapter and section 713.3. Fixtures not required by this section to be indirectly connected shall be directly connected to the plumbing system in accordance with Chapter 7. Action required: Provide indirect drain at ice machine.
Misc
Corrective Action Required
05/11/2017

Inadequate information to complete review. Provide the following: - Provide wire and wire insulation spec. - Rooftop condensing unit screening (existing?) - Convenience power to serve rooftop equipment.
Misc
Corrective Action Required
05/11/2017

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
Misc
Corrective Action Required
05/11/2017

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles. 2. Metal Boxes and enclosures containing receptacles. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
Licensed Contractors Rejected 05/04/2017 05/11/2017
Joe Frogge
LC - General Contractor
Corrective Action Required
05/11/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
05/11/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 05/16/2017 05/10/2017
Joe Dir
Misc
Corrective Action Required
05/10/2017

Egress illumination ACTION REQUIRED: Provide information if lighting in stair 115 has emergency lighting capibility. If not provide emergency lighting in stair 115. [B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. [B] 1006.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 604. [B] 1006.3.1 Illumination level under emergency power. Emergency lighting facilities shall be arranged to provide initial illumination that is at least an average of 1 footcandle (11 lux) and a minimum at any point of 0.1 footcandle (1 lux) measured along the path of egress at floor level. Illumination levels shall be permitted to decline to 0.6 footcandle (6 lux) average and a minimum at any point of 0.06 footcandle (0.6 lux) at the end of the emergency lighting time duration. A maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceeded.
Construction documents for fire alarm systems
Corrective Action Required
05/10/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of any modfication to be done to the fire alarm system.
Installation acceptance testing
Corrective Action Required
05/10/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: (information purposes) Acceptance testing of fire alarm system modifications will be required prior to the final occupancy inspection. To schedule testing contact the fire department at 816-969-`1300.
Portable fire extinguishers - general
Corrective Action Required
05/10/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED: (information purposes) If not already existing provide two fire extingusihers for each floor level. Fire extinguishers to be mounted, one fire extinguisher by each stairway entrance.
Misc
Corrective Action Required
05/10/2017

Door hardware ACTION REQUIRED:No keyed locks on the egress side of an exit [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Misc
Corrective Action Required
05/10/2017

Panic hardware ACTION REQUIRED: [B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet (1829 mm) wide that contain overcurrent devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $989.70 $989.70 Paid 05/25/2017
8331507-Sewer Connection Fee $330.00 $330.00 Paid 05/25/2017
8331506-EFHB Maybrook, Full $468.71 $468.71 Paid 05/25/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 5/30/2017 5/30/2017 05/30/2017
Above Ceiling Inspection Failed 7/6/2017 7/6/2017 07/06/2017
Misc
Corrective Action Required
07/06/2017
-RESTORE THE 1 HR STAIR ENCLOSURE WALL. FIRECAULK PENETRATIONS; PATCH OPEN GAP; MUD SCREW HEADS
Above Ceiling Inspection Passed 7/13/2017 07/13/2017
Misc
Resolved
07/13/2017
-RESTORE THE 1 HR STAIR ENCLOSURE WALL. FIRECAULK PENETRATIONS; PATCH OPEN GAP
Occupancy Inspection - Fire Passed 7/25/2017 07/25/2017
Alarm Test Passed 7/25/2017 07/25/2017
Occupancy Inspection - Codes Commercial Failed 7/25/2017 7/25/2017 07/25/2017
Misc
Corrective Action Required
07/25/2017
-THE RESTROOM DOORS LOCK LEVEL ARE NOT ACCESSIBILITY-COMPLIANT
Occupancy Inspection - Codes Commercial Full C of O 7/28/2017 7/28/2017 07/28/2017
Misc
Resolved
07/28/2017
-THE RESTROOM DOORS LOCK LEVEL ARE NOT ACCESSIBILITY-COMPLIANT
Documents & Images
Date Uploaded File Type Document Name
05/10/2017 Letter Fire Building Plan Review
05/11/2017 Letter Codes P/R Corrections Document
05/25/2017 Letter Fire Building Plan Review
05/25/2017 Letter Codes Plan Review Conditions
05/25/2017 Receipt Receipt for transaction: 2017-003067
05/25/2017 Letter Codes Building Permit
05/30/2017 Letter Inspection Summary
06/15/2017 Letter Fire (Alarm) Plan Review Notice
07/06/2017 Letter Inspection Summary
07/13/2017 Letter Inspection Summary
07/25/2017 Letter Inspection Summary
07/28/2017 Letter Field Certificate of Occupancy
07/31/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home