Permit Application Status

PRCOM20170499


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20170499
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
TENANT FINISH FOR PERSONAL CARE SALON - FACIALS, WAXING, ETC ***NEW CONTACT PERSON- JUAN JUAREZ-816-738-4019. PRIMARY CONTACT POINT FOR JOB.
02/24/2017
04/05/2017
09/03/2017
10/26/2017
Locations
Contacts
MIDWEST CUSTOM CONTRACTORS INC, Address:2400 S NORWOOD AVE, Phone:(816) 510-5267  
MALIK HEATING & COOLING, Address:6403 W 158TH ST, Phone:(816) 813-1338  
M & E ELECTRIC, Address:2905 N 41ST, Phone:(816) 215-7496  
KMZC PLUMBING, Address:301 W WEA, Phone:(913) 238-2583  
DAVID KASTER, Address:KASTER ARCHITECTS, Phone:(913) 681-1200  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 06/23/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
06/23/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the system modifications will be required prior to the final occupancy inspection. to schedule a test contact the fire department at 816-969-1300.
Alarm Plan Review Rejected 06/19/2017
Joe Dir
Sprinkler Plan Review Released for Construction 05/24/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
06/08/2017

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: The systems flow and tamper switches shall be tested prior to final occupancy inspection.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
06/08/2017

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ACTION REQUIRED:(veriifed at inspection) The existing fire sprinkler riser shall be current with all required serving and maintenence. A current service tag shall be posted on the systems riser.
Licensed Contractors Approved 03/10/2017 04/05/2017
Development Center
LC - MEP Subs
Resolved
04/05/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 03/17/2017 03/16/2017
Joe Dir
03/16/2017

Misc
Corrective Action Required
03/10/2017

NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT. (VERIFIED AT INSPECTION)
Construction documents for fire alarm systems
Corrective Action Required
03/10/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE FIRE ALARM CONTRATOR PROVIDE SHOP DRAWEINGS OF ANY MODIFICATIONS TO BE DONE TO THE FIRE ALRM SYSTEM. (INFORMATION PURPOSES)
Address numbers required
Corrective Action Required
03/10/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC OR ALPHBETIC SUITE DESIGNATION ON THE EXTERIOR OF THE FRONT DOOR. THE ADDRESS SHALL BE OF A CONTRASTING COLOR TO THE BACKGROUND. ADDRESS SHALL BE READBLE FROM THE ROADWAY. (VERIFIED AT INSPECTION)
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
03/10/2017

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL OF THE REQUIRED SERVICE AND MAINTENANCE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE RISER. (VERIFIED AT INSPECTION)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
03/10/2017

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT FIRE EXTINGUISHER ACCORDING TO PLANS. (VERIFIED AT INSPECTION)
Construction documents - Fire protection systems
Corrective Action Required
03/10/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE FIRE SPRINKLER CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY MODIFICATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM. (INFORMATION PURPOSES)
Installation acceptance testing
Corrective Action Required
03/10/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF ANY MODIFICATIONS DONE TO THE FIRE ALARM SYSTEM SHALL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. (INFORMATION PURPOSES)
Building Plan Review Approved 03/17/2017 03/15/2017
Joe Frogge
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Resolved
03/15/2017

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Modify design to comply with minimum 54" clearance required at approach to door 102. (clearance is reduced to 48" if closer is removed)
Bldg - Toilet room wall finish 1210.2.2
Resolved
03/15/2017

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish materials in restroom. (if paint is used it must be epoxy based)
Misc
Resolved
03/15/2017

2012 IMC 501.3 Exhaust discharge. The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a nuisance and not less than the distances specified in Section 501.3.1. The air shall be discharged to a location from which it cannot again be readily drawn in by a ventilating system. Air shall not be exhausted into an attic or crawl space. (see code for exceptions) Action required: Specify backdraft dampers at exhaust fans.
Building Plan Review Rejected 03/08/2017 03/07/2017
Joe Frogge
Misc
Resolved
03/07/2017

2012 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that existing roof structure will support additional load imposed by new RTU or provide engineered fix to strengthen structure. 3/7/17 - rtu is existing per architect
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
03/07/2017

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Modify design to comply with minimum 54" clearance required at approach to door 102. (clearance is reduced to 48" if closer is removed)
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
03/07/2017

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish materials in restroom. (if paint is used it must be epoxy based)
Misc
Corrective Action Required
03/07/2017

2012 IMC 501.3 Exhaust discharge. The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a nuisance and not less than the distances specified in Section 501.3.1. The air shall be discharged to a location from which it cannot again be readily drawn in by a ventilating system. Air shall not be exhausted into an attic or crawl space. (see code for exceptions) Action required: Specify backdraft dampers at exhaust fans.
Licensed Contractors Rejected 03/08/2017 03/07/2017
Joe Frogge
LC - MEP Subs
Corrective Action Required
03/07/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 03/08/2017 02/27/2017
Joe Dir
Misc
Corrective Action Required
02/27/2017

NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT. (VERIFIED AT INSPECTION)
Construction documents for fire alarm systems
Corrective Action Required
02/27/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE FIRE ALARM CONTRATOR PROVIDE SHOP DRAWEINGS OF ANY MODIFICATIONS TO BE DONE TO THE FIRE ALRM SYSTEM. (INFORMATION PURPOSES)
Address numbers required
Corrective Action Required
02/27/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC OR ALPHBETIC SUITE DESIGNATION ON THE EXTERIOR OF THE FRONT DOOR. THE ADDRESS SHALL BE OF A CONTRASTING COLOR TO THE BACKGROUND. ADDRESS SHALL BE READBLE FROM THE ROADWAY. (VERIFIED AT INSPECTION)
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
02/27/2017

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ANY MODIFICATIONS DONE TO THE FIRE ALARM SYSTEM SHALL BE TESTED PRIOR TO THE FINAL OCCUPANCY INSPECTION. (INFORMATION PURPOSES)
Portable fire extinguishers - general
Corrective Action Required
02/27/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE A MINIMUM OF ONE 2A-10BC FIRE EXTINGUISHER FOR EVERY 3,000 SQ FEET OF BUSINESS SPACE. (INFORMATION PURPOSES)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
02/27/2017

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (VERIFIED AT INSPECTION)
Construction documents - Fire protection systems
Corrective Action Required
02/27/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE FIRE SPRINKLER CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY MODIFICATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM. (INFORMATION PURPOSES)
Installation acceptance testing
Corrective Action Required
02/27/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF ANY MODIFICATIONS DONE TO THE FIRE ALARM SYSTEM SHALL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. (INFORMATION PURPOSES)
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $224.42 $224.42 Paid 04/05/2017
8331507-Sewer Connection Fee $120.00 $120.00 Paid 04/05/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Not Ready 6/2/2017 6/2/2017 06/02/2017
Misc
Corrective Action Required
06/02/2017
UNDER-SLAB PLUMBING NOT COMPLETED FOR INSPECTION
Underslab Plumbing Inspection - Commercial Passed 6/6/2017 6/6/2017 06/06/2017
Misc
Corrective Action Required
06/02/2017
UNDER-SLAB PLUMBING NOT COMPLETED FOR INSPECTION
In-wall Inspection Failed 6/29/2017 6/29/2017 06/29/2017
Misc
Corrective Action Required
06/29/2017
MOUNTING OF IN-WALL ELECTRICAL BOXES: SECURE AGAINST DEFLECTION. STAND-OFFS MUST BE IN CONTACT WITH STRUCTURE TO BE EFFECTIVE.
Misc
Corrective Action Required
06/29/2017
NEC 300-11, 330.30 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES
In-wall Inspection Passed 6/30/2017 6/30/2017 06/30/2017
Misc
Resolved
06/30/2017
MOUNTING OF IN-WALL ELECTRICAL BOXES: SECURE AGAINST DEFLECTION. STAND-OFFS MUST BE IN CONTACT WITH STRUCTURE TO BE EFFECTIVE.
Misc
Resolved
06/30/2017
NEC 300-11, 330.30 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES
Electrical Service Inspection Passed 7/26/2017 7/26/2017 07/26/2017
Above Ceiling Inspection Not Ready 8/10/2017 8/10/2017 08/10/2017
Misc
Corrective Action Required
08/10/2017
IBC 109.1, 109.5; IRC R109.3 INSPECTION ACCESS: PROPERTY LOCKED; INTERIOR NOT ACCESSIBLE. CALL FOR INSPECTION ON DAY WHEN JOBSITE IS ACCESSIBLE.
Above Ceiling Inspection Partial 8/11/2017 08/11/2017
Misc
Partial Correction
08/11/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: RECEPTION AREA ONLY;
Above Ceiling Inspection Not Ready 9/1/2017 9/1/2017 at 1:45 PM 09/01/2017
Misc
Resolved
09/01/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: RECEPTION AREA ONLY;
Corrective Action Required
09/01/2017
CEILING TILE PLACED BEFORE ABOVE-CEILING INSPECTION. INSTALL NO CEILING TILE BEFORE ABOVE-CEILING INSPECTION -- EXCEPT THOSE FEW REQUIRED FOR MOUNTING OF DEVICES.
Above Ceiling Inspection Failed 9/11/2017 9/11/2017 at 10:35 AM 09/11/2017
Misc
Corrective Action Required
09/11/2017
EXPANSION TANK REQUIRED AT WATER HEATER
Misc
Corrective Action Required
09/11/2017
ENSURE EF-1s ARE NOT FOR NAIL STATIONS
Above Ceiling Inspection Passed 9/19/2017 9/19/2017 at 10:50 AM 09/19/2017
Misc
Resolved
09/19/2017
EXPANSION TANK REQUIRED AT WATER HEATER
Misc
Resolved
09/19/2017
ENSURE EF-1s ARE NOT FOR NAIL STATIONS
Alarm Test Passed 9/25/2017 09/25/2017
Gas Service Inspection - Commercial Passed 9/28/2017 9/28/2017 at 10:45 AM 09/28/2017
Occupancy Inspection - Codes Commercial Failed 10/18/2017 10/18/2017 at 1:50 PM 10/18/2017
Misc
Corrective Action Required
10/18/2017
RESOLVE FIRE DEPT ISSUES
Misc
Corrective Action Required
10/18/2017
ELECTRICAL SERVICE PANEL: - CLOSE UNUSED OPENINGS WITH LISTED PLUGS - NUMBER BREAKER POSITIONS - NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". LABEL UNOCCUPIED POSITIONS "SPACE".
Misc
Corrective Action Required
10/18/2017
ELECT RECEPTS AT SALON BASE CABINETS: - NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE; 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. - SCREW YOKES SOLID - FACE PLATES REQUIRED
Occupancy Inspection - Fire Failed 10/18/2017 10/18/2017
Occupancy Inspection - Codes Commercial Failed 10/20/2017 10/19/2017 at 9:20 AM 10/19/2017
Misc
Corrective Action Required
10/18/2017
RESOLVE FIRE DEPT ISSUES
Misc
Corrective Action Required
10/18/2017
ELECTRICAL SERVICE PANEL: - CLOSE UNUSED OPENINGS WITH LISTED PLUGS - NUMBER BREAKER POSITIONS - NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". LABEL UNOCCUPIED POSITIONS "SPACE".
Misc
Corrective Action Required
10/18/2017
ELECT RECEPTS AT SALON BASE CABINETS: - NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE; 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. - SCREW YOKES SOLID - FACE PLATES REQUIRED
Misc
Corrective Action Required
10/19/2017
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Misc
Corrective Action Required
10/19/2017
NEC 210.63 ELECTRICAL RECEPTACLE OUTLET FOR SERVICING OF HACR EQUIPMENT: REQUIRED WITHIN 25' OF EQUIPMENT AT SAME LEVEL AS EQUIPMENT
Misc
Corrective Action Required
10/19/2017
IFGC 407; 415: PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS FOR ROOFTOP EQUIPMENT AND GAS PIPING: COMPLY WITH MAXIMUM SUPPORT SPACING PER IFGC. USE WEATHER-RESISTANT BLOCKING MATERIAL PROVIDING SOLID SUPPORT UNDER PIPE. LOOSE-CLAMP BLOCKS TO PIPE. APPLY SPECIFIED / APPROVED, ROOF-COMPATIBLE SLIP SHEET TO UNDERSIDE OF BLOCKS WITH METAL FASTENERS AT SIDES OF BLOCKS.
Misc
Corrective Action Required
10/19/2017
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED AND RE-INSTALLED FOR CLEANING
Misc
Corrective Action Required
10/19/2017
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT METER AND ROOFTOP. PAINTING OF ROOFTOP GAS PIPE NOT APPROVED; RE-PAINT
Corrective Action Required
10/19/2017
SOME ROOFTOP GAS PIPE NOT SECURED TO BLOCKS
Occupancy Inspection - Fire Passed 10/20/2017 10/20/2017
Investigation Inspection Complete 10/24/2017 10/24/2017
Occupancy Inspection - Codes Commercial Failed 10/24/2017 10/24/2017 at 9:10 AM 10/24/2017
Misc
Resolved
10/24/2017
RESOLVE FIRE DEPT ISSUES
Misc
Resolved
10/24/2017
ELECTRICAL SERVICE PANEL: - CLOSE UNUSED OPENINGS WITH LISTED PLUGS - NUMBER BREAKER POSITIONS - NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". LABEL UNOCCUPIED POSITIONS "SPACE".
Misc
Corrective Action Required
10/19/2017
ELECT RECEPTS SHOWN ON APPROVED DRAWINGS AT SALON BASE CABINETS HAVE BEEN CAPPED OFF. INSTALL PER DRAWING AND CODE OR HAVE ENGINEER SUBMIT REVISED DRAWING FOR APPROVAL.
Misc
Resolved
10/24/2017
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Misc
Resolved
10/24/2017
NEC 210.63 ELECTRICAL RECEPTACLE OUTLET FOR SERVICING OF HACR EQUIPMENT: REQUIRED WITHIN 25' OF EQUIPMENT AT SAME LEVEL AS EQUIPMENT
Misc
Corrective Action Required
10/19/2017
IFGC 407; 415: PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS FOR ROOFTOP EQUIPMENT AND GAS PIPING: COMPLY WITH MAXIMUM SUPPORT SPACING PER IFGC. USE WEATHER-RESISTANT BLOCKING MATERIAL PROVIDING SOLID SUPPORT UNDER PIPE. LOOSE-CLAMP BLOCKS TO PIPE. APPLY SPECIFIED / APPROVED, ROOF-COMPATIBLE SLIP SHEET TO UNDERSIDE OF BLOCKS WITH METAL FASTENERS AT SIDES OF BLOCKS.
Misc
Resolved
10/24/2017
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED AND RE-INSTALLED FOR CLEANING
Occupancy Inspection - Codes Commercial Full C of O 10/26/2017 10/26/2017 at 11:05 AM 10/26/2017
Misc
Resolved
10/26/2017
ELECT RECEPTS SHOWN ON APPROVED DRAWINGS AT SALON BASE CABINETS HAVE BEEN CAPPED OFF. INSTALL PER DRAWING AND CODE OR HAVE ENGINEER SUBMIT REVISED DRAWING FOR APPROVAL.
Misc
Resolved
10/26/2017
IFGC 407; 415: PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS FOR ROOFTOP EQUIPMENT AND GAS PIPING: COMPLY WITH MAXIMUM SUPPORT SPACING PER IFGC. USE WEATHER-RESISTANT BLOCKING MATERIAL PROVIDING SOLID SUPPORT UNDER PIPE. LOOSE-CLAMP BLOCKS TO PIPE. APPLY SPECIFIED / APPROVED, ROOF-COMPATIBLE SLIP SHEET TO UNDERSIDE OF BLOCKS WITH METAL FASTENERS AT SIDES OF BLOCKS.
Documents & Images
Date Uploaded File Type Document Name
02/27/2017 Letter Fire Building Plan Review
03/07/2017 Letter Codes P/R Corrections Document
03/16/2017 Letter Fire Building Plan Review
04/05/2017 Letter Codes Plan Review Conditions
04/05/2017 Letter Codes Building Permit
04/05/2017 Receipt Receipt for transaction: 2017-001253
05/04/2017 RE Brow Threading - plan review PRCOM20170499
06/02/2017 Letter Inspection Summary
06/06/2017 Letter Inspection Summary
06/06/2017 Letter Inspection Summary
06/08/2017 Letter Fire (Sprinkler) Plan Review
06/23/2017 Letter Fire (Alarm) Plan Review Notice
06/29/2017 Letter Inspection Summary
06/30/2017 Letter Inspection Summary
07/26/2017 Letter Inspection Summary
08/10/2017 Letter Inspection Summary
08/11/2017 Letter Inspection Summary
09/11/2017 Letter Inspection Summary
09/19/2017 Letter Inspection Summary
09/19/2017 Letter DOC091917-003
09/28/2017 Letter Inspection Summary
10/18/2017 Letter Inspection Summary
10/19/2017 Letter Inspection Summary
10/24/2017 Letter Inspection Summary
10/26/2017 Letter Field Certificate of Occupancy
10/27/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home