Permit Application Status

PRCOM20163024


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20163024
Building Permit - Commercial
Certificate of Occupancy
JVM NEW LONGVIEW LLC
ADDITION COMMERCIAL
ADDITION TO EXISTING LEASING OFFICE TO ACCOMODATE INCREASING SIZE OF WORKOUT ROOM - PROJECT INCLUDES ELECTRICAL TO TEMPORARY LEASING TRAILER
11/18/2016
12/15/2016
05/27/2017
04/28/2017
Locations
Contacts
SIGNAL RESTORATION, Address:2321 NE INDEPENDENCE AVE, Phone:(816) 287-3030  
THREE TRAILS HEATING COOLING, Address:13223 S 71 HWY, Phone:(816) 701-6377  
SUBURBAN ELECTRIC , Address:PO BOX 275, Phone:(816) 517-6739  
ODIMO, Address:601 E 63RD ST STE 205, Phone:(816) 572-2018  
JVM NEW LONGVIEW LLC, Address:PO BOX 06494  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 12/16/2016 12/13/2016
Joe Frogge
License Tax Application
Corrective Action Required
12/09/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 12/12/16 - acknowledged in letter
Project cost
Resolved
12/13/2016

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes. 12/12/16 - acknowledged in letter
Misc
Resolved
12/12/2016

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how new condensing unit will be screened per referenced UDO section. 12/12/16 - noted on drawing to screen with landscaping
Gen - Submittal documents 7-137
Resolved
12/12/2016

Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. Action required: Clarify installation of new air conditioning unit. How is it supported? Is it above the GWB ceiling? If so, clarify method of access and service clearances. Is this a gas fired appliance? If yes, we need gas piping and combustion air method to be shown and/or specified on plan. 12/12/16 - to be supported from structure above
Fire Plan Review Approved with Conditions 12/16/2016 12/13/2016
Joe Dir
12/13/2016

12/13/2016

Construction documents for fire alarm systems
Corrective Action Required
12/09/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY MODIFICATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
Address numbers required
Corrective Action Required
12/09/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 460 ON THE EXTERIOR OF THE BUILDING IN A CONTRASTING COLOR READABLE FROM THE ROADWAY. (VERIFIED AT INSPECTION)
Installation acceptance testing
Corrective Action Required
12/09/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACCEPTANCE TESTING OF THE MODIFICATIONS DONE TO THE FIRE ALARM SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE TESTING CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
Portable fire extinguishers - general
Corrective Action Required
12/09/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE TWO 2A-10BC FIRE EXTINGUISHERS AND MOUNT THEM ON A NORMAL PATH OF TRAVEL WITH A MAXIMUM TRAVEL DISTANCE OF 75 FEET FROM ANYWHERE WITHIN THE CLUBHOUSE. (VERIFIED AT INSPECTION)
Licensed Contractors Approved 12/09/2016 12/09/2016
Development Center
LC - General Contractor
Resolved
12/09/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
12/09/2016

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 12/06/2016 11/23/2016
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
11/23/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY MODIFICATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
Address numbers required
Corrective Action Required
11/23/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 460 ON THE EXTERIOR OF THE BUILDING IN A CONTRASTING COLOR READABLE FROM THE ROADWAY. (VERIFIED AT INSPECTION)
Construction documents - Fire protection systems
Corrective Action Required
11/23/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY MODIFICATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM.
Installation acceptance testing
Corrective Action Required
11/23/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACCEPTANCE TESTING OF THE MODIFICATIONS DONE TO THE FIRE ALARM SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE TESTING CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
11/23/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL REQUIRED SERVICE/MAINTENANCE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE SPRINKLER SYSTEM RISER. (VERIFIED AT INSPECTION)
Portable fire extinguishers - general
Corrective Action Required
11/23/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE TWO 2A-10BC FIRE EXTINGUISHERS AND MOUNT THEM ON A NORMAL PATH OF TRAVEL WITH A MAXIMUM TRAVEL DISTANCE OF 75 FEET FROM ANYWHERE WITHIN THE CLUBHOUSE. (VERIFIED AT INSPECTION)
Building Plan Review Rejected 12/06/2016 11/21/2016
Joe Frogge
License Tax Application
Corrective Action Required
11/21/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Project cost
Corrective Action Required
11/21/2016

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
11/21/2016

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how new condensing unit will be screened per referenced UDO section.
Gen - Submittal documents 7-137
Corrective Action Required
11/21/2016

Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. Action required: Clarify installation of new air conditioning unit. How is it supported? Is it above the GWB ceiling? If so, clarify method of access and service clearances. Is this a gas fired appliance? If yes, we need gas piping and combustion air method to be shown and/or specified on plan.
Licensed Contractors Rejected 12/06/2016 11/21/2016
Joe Frogge
LC - General Contractor
Corrective Action Required
11/21/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
11/21/2016

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Addition to Commercial $699.60 $699.60 Paid 12/15/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Partial 1/6/2017 1/6/2017 01/06/2017
Misc
Corrective Action Required
01/06/2017
TEMP METER AND DISCONNECT ONLY TRAILER NORTH OF BUILDING( SALES OFFICE TRAILER) NOT A CONSTRUCTION TRAILER no inspection of trailer electrical only temp meter and disconnect. ok to release.
Footing Inspection - Commercial Not Ready 2/21/2017 (10:30) 2/21/2017 02/21/2017
Misc
Corrective Action Required
02/21/2017
NO PLANS OR CONTRACTOR ON SITE. DO NOT POUR.
Footing Inspection - Commercial Passed 3/17/2017 03/17/2017
Misc
Resolved
03/17/2017
pending revised plan on north wall. east footing ok to pour.
Footing Inspection - Commercial Partial 2/22/2017 (2:00) 2/23/2017 03/17/2017
Misc
Resolved
03/17/2017
pending revised plan on north wall. east footing ok to pour.
All Rough Inspection - Commercial Passed 3/17/2017 03/17/2017
Occupancy Inspection - Fire Passed 04/28/2017
Occupancy Inspection - Codes Commercial Full C of O 4/28/2017 4/28/2017 04/28/2017
Documents & Images
Date Uploaded File Type Document Name
11/23/2016 Letter Fire Building Plan Review
11/28/2016 Letter Codes P/R Corrections Document
12/13/2016 Letter Fire Building Plan Review
12/13/2016 Letter Codes Plan Review Conditions
12/15/2016 Receipt Receipt for transaction: 2016-007163
12/15/2016 Letter Codes Building Permit
01/06/2017 Letter Inspection Summary
02/17/2017 footing mod
02/21/2017 Letter Inspection Summary
02/23/2017 Letter Inspection Summary
03/17/2017 Letter Inspection Summary
04/28/2017 Letter Codes Final Certificate of Occupancy
05/01/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home