Summary
PRCOM20162829
Building Permit - Commercial
Final Completion
BFRE LLC
ALTERATION COMMERCIAL
PARKING LOT LIGHTING
10/31/2016
11/01/2016
05/01/2017
Locations
Contacts
DESIGN BUILD ELECTRIC LLC, Address:7320 W 162ND ST STE 104, Phone:(913) 402-6002  
BFRE LLC, Address:3200 S OUTER RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 11/10/2016 10/31/2016
Joe Frogge
Licensed Contractors Approved 10/31/2016 10/31/2016
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $457.35 $457.35 Paid 11/01/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underground Electrical Inspection - Commercial Partial 11/16/2016 11/16/2016 11/16/2016
Misc
Partial Correction
11/16/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11;
Underground Electrical Inspection - Commercial Partial 11/17/2016 11/17/2016
Misc
Partial Correction
11/16/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11;
Misc
Partial Correction
11/17/2016
OK TO COVER WHEN READY TRENCHED CONDUIT AT FOLLOWING LIGHT POLE LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: Q-BOX TO #14; #13 TO #14 TO #15 TO #16; #15 TO #20; #20 TO #21; AT ENTRANCE DRIVE OK TO DIG, LAY CONDUIT AND COVER WHEN READY WITHOUT INSPECTION
Underground Electrical Inspection - Commercial Partial 11/17/2016 11/17/2016
Misc
Partial Correction
11/17/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11;
Misc
Partial Correction
11/17/2016
OK TO COVER WHEN READY TRENCHED CONDUIT AT FOLLOWING LIGHT POLE LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: Q-BOX TO #14; #13 TO #14 TO #15 TO #16; #15 TO #20; #20 TO #21; AT ENTRANCE DRIVE OK TO DIG, LAY CONDUIT AND COVER WHEN READY WITHOUT INSPECTION
Underground Electrical Inspection - Commercial Partial 11/17/2016 11/17/2016 11/17/2016
Misc
Partial Correction
11/17/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11; #13: #15; #16; #18; #20; #21 THRU #25;
Misc
Partial Correction
11/17/2016
OK TO COVER WHEN READY TRENCHED CONDUIT AT FOLLOWING LIGHT POLE LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: Q-BOX TO #14; #13 TO #14 TO #15 TO #16; #15 TO #20; #20 TO #21; AT ENTRANCE DRIVE OK TO DIG, LAY CONDUIT AND COVER WHEN READY WITHOUT INSPECTION
Underground Electrical Inspection - Commercial Partial 11/17/2016 11/17/2016
Misc
Partial Correction
11/17/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11; Q-BOX TO #14; #13 TO #14 TO #15 TO #16; #15 TO #20; #20 TO #21; AT ENTRANCE DRIVE OK TO DIG, LAY CONDUIT AND COVER WHEN READY WITHOUT INSPECTION
Underground Electrical Inspection - Commercial Partial 11/18/2016 11/18/2016 11/18/2016
Misc
Partial Correction
11/17/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11; #13: #15; #16; #18; #20; #21 THRU #25; #14; #26 THRU #31;
Misc
Partial Correction
11/17/2016
OK TO COVER WHEN READY TRENCHED CONDUIT AT FOLLOWING LIGHT POLE LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: Q-BOX TO #14; #13 TO #14 TO #15 TO #16; #15 TO #20; #20 TO #21; AT ENTRANCE DRIVE OK TO DIG, LAY CONDUIT AND COVER WHEN READY WITHOUT INSPECTION
Underground Electrical Inspection - Commercial Partial 11/18/2016 11/18/2016 11/18/2016
Misc
Partial Correction
11/18/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11; #13: #15; #16; #18; #20; #21 THRU #25; #14; #26 THRU #31; #12; #17; #19
Misc
Partial Correction
11/18/2016
OK TO COVER WHEN READY TRENCHED CONDUIT AT FOLLOWING LIGHT POLE LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: Q-BOX TO #14; #13 TO #14 TO #15 TO #16; #15 TO #20; #20 TO #21; J TO #14 & #19; #12 TO #13; #17 TO #18 TO #19 AT ENTRANCE DRIVE OK TO DIG, LAY CONDUIT AND COVER WHEN READY WITHOUT INSPECTION
Underground Electrical Inspection - Commercial Partial 11/23/2016 11/23/2016 11/23/2016
Misc
Partial Correction
11/18/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11; #13: #15; #16; #18; #20; #21 THRU #25; #14; #26 THRU #31; #12; #17; #19
Misc
Partial Correction
11/18/2016
OK TO COVER WHEN READY TRENCHED CONDUIT AT FOLLOWING LIGHT POLE LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: Q-BOX TO #14; #13 TO #14 TO #15 TO #16; #15 TO #20; #20 TO #21; J TO #14 & #19; #12 TO #13; #17 TO #18 TO #19 #6 TO #10 APPROVED AT ENTRANCE DRIVE OK TO DIG, LAY CONDUIT AND COVER WHEN READY WITHOUT INSPECTION
Underground Electrical Inspection - Commercial Partial 11/29/2016 11/29/2016 11/29/2016
Misc
Partial Correction
11/23/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11; #13: #15; #16; #18; #20; #21 THRU #25; #14; #26 THRU #31; #12; #17; #19
Misc
Partial Correction
11/23/2016
OK TO COVER WHEN READY TRENCHED CONDUIT AT FOLLOWING LIGHT POLE LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: Q-BOX TO #14; #13 TO #14 TO #15 TO #16; #15 TO #20; #20 TO #21; J TO #14 & #19; #12 TO #13; #17 TO #18 TO #19; #6 TO #10; #9 TO #10 TO #11 TO #31;
Underground Electrical Inspection - Commercial Partial 12/1/2016 12/1/2016 12/01/2016
Misc
Partial Correction
11/29/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11; #13: #15; #16; #18; #20; #21 THRU #25; #14; #26 THRU #31; #12; #17; #19
Misc
Partial Correction
11/29/2016
OK TO COVER WHEN READY TRENCHED CONDUIT AT FOLLOWING LIGHT POLE LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: Q-BOX TO #14; #13 TO #14 TO #15 TO #16; #15 TO #20; #20 TO #21; J TO #14 & #19; #12 TO #13; #17 TO #18 TO #19; #6 TO #10; #9 TO #10 TO #11 TO #31;
Underground Electrical Inspection - Commercial Partial 12/2/2016 12/2/2016 12/02/2016
Misc
Partial Correction
12/01/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11; #13: #15; #16; #18; #20; #21 THRU #25; #14; #26 THRU #31; #12; #17; #19;
Misc
Partial Correction
12/01/2016
OK TO COVER WHEN READY TRENCHED CONDUIT AT FOLLOWING LIGHT POLE LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: Q-BOX TO #14; #13 TO #14 TO #15 TO #16; #15 TO #20; #20 TO #21; J TO #14 & #19; #12 TO #13; #17 TO #18 TO #19; #6 TO #10; #9 TO #10 TO #11 TO #31; #3 TO #4 TO #22 THRU #29;
Underground Electrical Inspection - Commercial Partial 12/5/2016 12/5/2016 12/05/2016
Misc
Partial Correction
12/02/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11; #13: #15; #16; #18; #20; #21 THRU #25; #14; #26 THRU #31; #12; #17; #19;
Misc
Partial Correction
12/02/2016
OK TO COVER WHEN READY TRENCHED CONDUIT AT FOLLOWING LIGHT POLE LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: Q-BOX TO #14; #13 TO #14 TO #15 TO #16; #15 TO #20; #20 TO #21; J TO #14 & #19; #12 TO #13; #17 TO #18 TO #19; #6 TO #10; #9 TO #10 TO #11 TO #31; #3 TO #4 TO #22 THRU #29; #5 TO #1 TO #2 TO #3;
Final Electrical Inspection - Commercial Partial 12/12/2016 12/12/2016
Misc
Corrective Action Required
12/12/2016
RESOLVE ANY PLANNING ISSUES
Misc
Corrective Action Required
12/12/2016
RESOLVE ANY PUBLIC WORKS ISSUES
Misc
Partial Correction
12/12/2016
PARKING LOT OK FOR USE PENDING APPROVAL FROM PLANNING & PUBLIC WORKS DEPARTMENTS
Underground Electrical Inspection - Commercial Passed 12/12/2016 12/5/2016 12/12/2016
Misc
Resolved
12/12/2016
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #11; #13: #15; #16; #18; #20; #21 THRU #25; #14; #26 THRU #31; #12; #17; #19;
Misc
Resolved
12/12/2016
OK TO COVER WHEN READY TRENCHED CONDUIT AT FOLLOWING LIGHT POLE LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: Q-BOX TO #14; #13 TO #14 TO #15 TO #16; #15 TO #20; #20 TO #21; J TO #14 & #19; #12 TO #13; #17 TO #18 TO #19; #6 TO #10; #9 TO #10 TO #11 TO #31; #3 TO #4 TO #22 THRU #29; #5 TO #1 TO #2 TO #3;
Investigation Inspection Complete 12/27/2016 05/01/2017
Final Electrical Inspection - Commercial Passed 5/1/2017 05/01/2017
Misc
Resolved
05/01/2017
RESOLVE ANY PLANNING ISSUES
Misc
Resolved
05/01/2017
RESOLVE ANY PUBLIC WORKS ISSUES
Misc
Resolved
05/01/2017
PARKING LOT OK FOR USE PENDING APPROVAL FROM PLANNING & PUBLIC WORKS DEPARTMENTS
Documents & Images
Date Uploaded File Type Document Name
11/01/2016 Receipt Receipt for transaction: 2016-006665
11/01/2016 Letter Codes Plan Review Conditions
11/01/2016 Letter Codes Building Permit
11/16/2016 Letter Inspection Summary
11/17/2016 Letter Inspection Summary
11/17/2016 Letter Inspection Summary
11/17/2016 Letter Inspection Summary
11/18/2016 Letter Inspection Summary
11/18/2016 Letter Inspection Summary
11/23/2016 Letter Inspection Summary
11/29/2016 Letter Inspection Summary
12/02/2016 Letter Inspection Summary
12/05/2016 Letter Inspection Summary
12/12/2016 Letter Inspection Summary
05/01/2017 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home