Permit Application Status

PRCOM20162811


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20162811
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
CHANGE OF TENANT
TENANT FINISH FOR FULL SERVICE RESTAURANT
10/27/2016
01/18/2017
04/29/2017
05/18/2017
Locations
Contacts
ARC GENERAL CONTRACTING, Address:7833 BARTON ST, Phone:(913) 492-8008  
PRO PLATINUM LLC, Address:6116 ALDEN RD, Phone:(913) 908-3512  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
PLUMBING PLUS INC, Address:13117 S 71 HWY, Phone:(816) 761-5757  
BATES ARCHITECTS, Address:106 N 37TH ST STE C, Phone:(479) 633-8155  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 03/27/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
03/27/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Field tests and acceptance testing of the system will be required prior to the final occupancy inspection. To schedule testing contact the fire department at 816-969-1300
Alarm Plan Review Released for Construction 03/17/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
03/17/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the system will be required prior to the final occupancy inspection. To schedule a test contact the fire department at 816-969-1300.
Misc
Corrective Action Required
03/17/2017

See the attached document to verify room useage
Health Department Review Approved 01/24/2017
Joe Frogge
Licensed Contractors Approved 11/30/2016 01/17/2017
Development Center
LC - General Contractor
Resolved
01/17/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
01/17/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved with Conditions 12/07/2016 12/02/2016
Joe Frogge
License Tax Application
Corrective Action Required
11/30/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 12/2/16 - acknowledged
Health Dept Inspection
Corrective Action Required
11/30/2016

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 12/2/16 - acknowledged
Health Dept Review
Resolved
01/24/2017

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 12/2/16 - acknowledged
Plumb - Minimum number of fixtures 403.1
Resolved
12/02/2016

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Provide additional water closets. Required number is 4 for each gender. (Fractional numbers to be rounded up per IPC 403.1.1)
Gen - Submittal documents 7-137
Resolved
12/02/2016

Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. Action required: Additional information required. Provide the following. - UL detail for wall "P6" that includes screw/nail patterns. - Domestic water riser diagram (waste riser duplicated) - Mechanical and Electrical roof plan(s). 12/2/16 - provided additional drawings
Misc
Resolved
12/02/2016

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Specify fire rating for doors 109 & 120B.
Bldg - Door swing 1008.1.2
Resolved
12/02/2016

2012 IBC 1008.1.2 – Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for possible exceptions.) Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. Action required: Door 101B must be altered to swing in direction of travel.
Bldg - Panic and fire exit hardware 1008.1.10
Resolved
12/02/2016

2012 IBC 1008.1.10 – Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Specify compliant hardware at patio gates.
Bldg - Toilet room wall finish 1210.2.2
Resolved
12/02/2016

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall covering material at service sink and side walls at water closets.
Misc
Resolved
12/02/2016

2012 IMC 506.3.13.1 Termination above the roof. Exhaust outlets that terminate above the roof shall have the discharge opening located not less than 40 inches above the roof surface. 2012 IMC 506.5.3 Exhaust fan mounting. An upblast fan shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning. The ductwork shall extend a minimum of 18 inches above the roof surface. Action required: At hood exhaust fan specify minimum height, hinge, and flexible conduit.
NEC - Receptacles - Other than dwelling units 210.8(B)
Resolved
12/02/2016

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles in kitchen will by GFCI protected.
Fire Plan Review Approved with Conditions 12/07/2016 12/01/2016
Joe Dir
12/01/2016

12/01/2016

12/01/2016

Posting of occupant load
Corrective Action Required
11/30/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. EACH AREA SHALL HAVE THE OCCUPANT LOADS POSTED SEPERATELY. (VERIFIED AT INSPECTION)
Construction documents for fire alarm systems
Corrective Action Required
11/30/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR MODIFICATIONS TO BE DONE TO THE FIRE ALARM SYSTEM. ALARM SYSTEM SHALL BE WIRED INTO EXISTING FIRE ALARM PANEL, NO SUB PANELS. (INFORMATION PURPOSES)
Address numbers required
Corrective Action Required
11/30/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE BUSINESS ADDRESS IN A CONTRASTING COLOR TO THE BACKGROUND ON THE EXTERIOR OF ALL DOORS LEADING INTO THE BUSINESS. (VERIFIED AT INSPECTION)
Construction documents - Fire protection systems
Corrective Action Required
11/30/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE MODIFICATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM. (INFORMATION PURPOSES)
Installation acceptance testing
Corrective Action Required
11/30/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE FIRE ALARM AND SPRINKLER SYSTEM PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE TESTING CONTACT THE FIRE DEPARTMENT AT 816-969-1300. (INFORMATION PURPOSES)
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
11/30/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL REQUIRED MAINTENANCE AND SERVICING. A CURRENT SERVICE TAG SHALL BE POSTED ON THE RISER. (VERIFIED AT INSPECTION)
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
11/30/2016

20`12 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. PROVIDE A K-CLASS FIRE EXTINGUISHER FOR THE KITCHEN AREA. (VERIFIED AT INSPECTION)
Portable fire extinguishers - general
Corrective Action Required
11/30/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE FIRE EXTINGUISHERS AS ACCORDING TO PLANS.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
11/30/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT THE FIRE EXTINGUSIHERS ACCORDING TO PLANS.
Misc
Corrective Action Required
11/30/2016

MARKED EGRESS DOORS: [B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT. (VERIFIED AT INSPECTION)
Fire Plan Review Rejected 11/08/2016 10/31/2016
Joe Dir
Misc
Corrective Action Required
10/31/2016

VESTIBULE 101: [B] 1008.1.2 Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. CHANGE THE DIRECTION OF THE DOOR SWING IN VESTIBULE 101 TO BE IN THE DIRECTION OF EGRESS TRAVEL.
Posting of occupant load
Corrective Action Required
10/31/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. REFIGURE THE OCCUPANT LOADS OF THE DINING AREA AND THE BAR AREA. EACH AREA SHALL HAVE THE OCCUPANT LOADS POSTED SEPERATELY. (VERIFIED AT INSPECTION)
Construction documents for fire alarm systems
Corrective Action Required
10/31/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR MODIFICATIONS TO BE DONE TO THE FIRE ALARM SYSTEM. ALARM SYSTEM SHALL BE WIRED INTO EXISTING FIRE ALARM PANEL, NO SUB PANELS. (INFORMATION PURPOSES)
Address numbers required
Corrective Action Required
10/31/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE BUSINESS ADDRESS IN A CONTRASTING COLOR TO THE BACKGROUND ON THE EXTERIOR OF ALL DOORS LEADING INTO THE BUSINESS. (VERIFIED AT INSPECTION)
Construction documents - Fire protection systems
Corrective Action Required
10/31/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE MODIFICATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM. (INFORMATION PURPOSES)
Installation acceptance testing
Corrective Action Required
10/31/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE FIRE ALARM AND SPRINKLER SYSTEM PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE TESTING CONTACT THE FIRE DEPARTMENT AT 816-969-1300. (INFORMATION PURPOSES)
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
10/31/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL REQUIRED MAINTENANCE AND SERVICING. A CURRENT SERVICE TAG SHALL BE POSTED ON THE RISER. (VERIFIED AT INSPECTION)
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
10/31/2016

20`12 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. PROVIDE A K-CLASS FIRE EXTINGUISHER FOR THE KITCHEN AREA. (VERIFIED AT INSPECTION)
Portable fire extinguishers - general
Corrective Action Required
10/31/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE FIRE EXTINGUISHERS AS ACCORDING TO PLANS.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
10/31/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT THE FIRE EXTINGUSIHERS ACCORDING TO PLANS.
Misc
Corrective Action Required
10/31/2016

ADDITONAL EXIT SIGNAGE AND EMERGENCY LIGHTING NEEDED FOR EGRESS PATH C AT THE EXIT DISCHARGE DOOR. [B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
Misc
Corrective Action Required
10/31/2016

GATES OFF OF THE PATIO [B] 1008.2 Gates. Gates serving the means of egress system shall comply with the requirements of this section. Gates used as a component in a means of egress shall conform to the applicable requirements for doors.
Misc
Corrective Action Required
10/31/2016

MARKED EGRESS DOORS: [B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT. (VERIFIED AT INSPECTION)
Building Plan Review Rejected 11/08/2016 10/28/2016
Joe Frogge
License Tax Application
Corrective Action Required
10/28/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
10/28/2016

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Review
Corrective Action Required
10/28/2016

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
10/28/2016

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Provide additional water closets. Required number is 4 for each gender. (Fractional numbers to be rounded up per IPC 403.1.1)
Gen - Submittal documents 7-137
Corrective Action Required
10/28/2016

Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. Action required: Additional information required. Provide the following. - UL detail for wall "P6" that includes screw/nail patterns. - Domestic water riser diagram (waste riser duplicated) - Mechanical and Electrical roof plan(s).
Misc
Corrective Action Required
10/28/2016

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Specify fire rating for doors 109 & 120B.
Bldg - Door swing 1008.1.2
Corrective Action Required
10/28/2016

2012 IBC 1008.1.2 – Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for possible exceptions.) Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. Action required: Door 101B must be altered to swing in direction of travel.
Bldg - Panic and fire exit hardware 1008.1.10
Corrective Action Required
10/28/2016

2012 IBC 1008.1.10 – Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Specify compliant hardware at patio gates.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
10/28/2016

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall covering material at service sink and side walls at water closets.
Misc
Corrective Action Required
10/28/2016

2012 IMC 506.3.13.1 Termination above the roof. Exhaust outlets that terminate above the roof shall have the discharge opening located not less than 40 inches above the roof surface. 2012 IMC 506.5.3 Exhaust fan mounting. An upblast fan shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning. The ductwork shall extend a minimum of 18 inches above the roof surface. Action required: At hood exhaust fan specify minimum height, hinge, and flexible conduit.
NEC - Receptacles - Other than dwelling units 210.8(B)
Corrective Action Required
10/28/2016

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles in kitchen will by GFCI protected.
Licensed Contractors Rejected 11/08/2016 10/28/2016
Joe Frogge
LC - General Contractor
Corrective Action Required
10/28/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
10/28/2016

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $1,940.38 $1,940.38 Paid 01/18/2017
8331507-Sewer Connection Fee $240.00 $240.00 Paid 01/18/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 2/10/2017 02/10/2017
Misc
Partial Correction
02/10/2017
OK TO COVER WHEN READY UNDER-SLAB PVC & C.I. SANITARY DRAIN, WASTE, & VENT PIPING EXCEPT VENT PIPING YET TO BE INSTALLED. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Plumbing Inspection - Commercial Passed 2/13/2017 2/13/2017 02/13/2017
Misc
Resolved
02/13/2017
OK TO COVER WHEN READY UNDER-SLAB PVC & C.I. SANITARY DRAIN, WASTE, & VENT PIPING EXCEPT VENT PIPING YET TO BE INSTALLED. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Electrical Inspection - Commercial Passed 2/13/2017 02/13/2017
Rough Framing Inspection - Commercial Passed 2/22/2017 2/22/2017 02/22/2017
In-wall Inspection Not Ready 2/27/2017 2/27/2017 02/27/2017
In-wall Inspection Partial 2/28/2017 2/28/2017 02/28/2017
Misc
Partial Correction
02/28/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS EXCEPT SHORT WALL ADJACENT TO RAISED PLATFORM AT NE CORNER
Above Ceiling Inspection Partial 3/1/2017 03/01/2017
Misc
Partial Correction
03/01/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: CEILING AT BAR AREA; BULKHEADS AT DINING AREA EAST AND ENTRANCE SOUTH
In-wall Inspection Partial 3/1/2017 03/01/2017
Misc
Partial Correction
02/28/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS EXCEPT SHORT WALL ADJACENT TO RAISED PLATFORM AT NE CORNER NEW DOOR 120B: WALL FRAMING AND SOUTH FACE 1ST LAYER 5/8" TYPE X GWB OK TO COVER WHEN READY
Rated Assembly Inspection Partial 3/3/2017 03/03/2017
Misc
Partial Correction
03/03/2017
NEW DOOR 120B -- OK TO COVER WHEN READY: WALL FRAMING AND SOUTH FACE 1ST LAYER 5/8" TYPE X GWB; NORTH FACE 1ST LAYER 5/8" TYPE X GWB; THEN OK TO TAPES, MUD AND FIRE-STOP BOTH FACES AS NECESSARY
Rated Assembly Inspection Partial 3/7/2017 3/7/2017 03/07/2017
Misc
Partial Correction
03/07/2017
1st LAYER OF SPRAY FIRE RESITIVE PAINT APPLIED TO DECK JOISTS. APPLY TO NON TREATED WOOD IN PARTITION NON BEARING WALLS.
Rated Assembly Inspection Partial 3/13/2017 3/13/2017 03/13/2017
Misc
Partial Correction
03/03/2017
NEW DOOR 120B -- OK TO COVER WHEN READY: WALL FRAMING AND SOUTH FACE 1ST LAYER 5/8" TYPE X GWB; NORTH FACE 1ST LAYER 5/8" TYPE X GWB; THEN OK TO TAPES, MUD AND FIRE-STOP BOTH FACES AS NECESSARY
Misc
Partial Correction
03/13/2017
OK TO COVER WHEN READY FRAMING FOR WOOD PLATFORM AND PONY WALLS AT NE CORNER WHERE TWO COATS OF FLAME STOP INTUMESCENT PAINT (IM) HAVE BEEN APPLIED PER MFGR INSTRUCTIONS.
Above Ceiling Inspection Partial 3/22/2017 3/22/2017 03/22/2017
Misc
Partial Correction
03/01/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: CEILING AT BAR AREA; BULKHEADS AT DINING AREA EAST AND ENTRANCE SOUTH; HARD LID CEILING ABOVE THE BAR AREA
Above Ceiling Inspection Partial 3/29/2017 3/29/2017 03/29/2017
Misc
Partial Correction
03/22/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: CEILING AT BAR AREA; BULKHEADS AT DINING AREA EAST AND ENTRANCE SOUTH; HARD LID CEILING ABOVE THE BAR AREA; VESTIBULE 101; PLATFORM DINING AREA 103; DINING AREA 107; DINING AREA 108; CORRIDOR 118; OFFICE 116; MEN'S RR 117; WOMEN'S RR 118;
Hood/Duct Inspection Partial 3/31/2017 3/31/2017 03/31/2017
Misc
Partial Correction
03/31/2017
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SEAM SHOP WELDS APPROVED;
Hood/Duct Inspection Partial 4/7/2017 4/7/2017 04/07/2017
Misc
Partial Correction
03/31/2017
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SEAM SHOP WELDS APPROVED; LIGHT TEST OF JOINT FIELD WELD APPROVED
Gas Piping Inspection - Commercial Passed 4/7/2017 04/07/2017
Gas Service Inspection - Commercial Passed 4/7/2017 4/7/2017 04/07/2017
Hood/Duct Inspection Partial 4/10/2017 4/10/2017 04/10/2017
Misc
Partial Correction
04/07/2017
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SEAM SHOP WELDS APPROVED; LIGHT TEST OF JOINT FIELD WELD APPROVED; FIRE WRAP 1ST LAYER APPROVED TO COVER;
Above Ceiling Inspection Partial 4/13/2017 4/13/2017 04/13/2017
Misc
Partial Correction
03/29/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: CEILING AT BAR AREA; BULKHEADS AT DINING AREA EAST AND ENTRANCE SOUTH; HARD LID CEILING ABOVE THE BAR AREA; VESTIBULE 101; PLATFORM DINING AREA 103; DINING AREA 107; DINING AREA 108; CORRIDOR 118; OFFICE 116; MEN'S RR 117; WOMEN'S RR 118; KITCHEN AREA: RE-ESTABLISH 1 HOUR RATING WALL AT WEST WALL WHERE 1 HOUR WALL WAS DEMO. OKAY TO DROP THE REST OF THE KITCHEN.
Hood/Duct Inspection Passed 04/13/2017
Misc
Resolved
04/13/2017
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SEAM SHOP WELDS APPROVED; LIGHT TEST OF JOINT FIELD WELD APPROVED; FIRE WRAP 1ST LAYER APPROVED TO COVER;
Alternate Protection Systems Inspection Passed 4/20/2017 04/20/2017
Alarm Test Passed 4/20/2017 04/20/2017
Rated Assembly Inspection Passed 3/7/2017 04/25/2017
Misc
Resolved
04/25/2017
1st LAYER OF SPRAY FIRE RESITIVE PAINT APPLIED TO DECK JOISTS. APPLY TO NON TREATED WOOD IN PARTITION NON BEARING WALLS.
Above Ceiling Inspection Passed 4/13/2017 04/25/2017
Misc
Partial Correction
04/13/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: CEILING AT BAR AREA; BULKHEADS AT DINING AREA EAST AND ENTRANCE SOUTH; HARD LID CEILING ABOVE THE BAR AREA; VESTIBULE 101; PLATFORM DINING AREA 103; DINING AREA 107; DINING AREA 108; CORRIDOR 118; OFFICE 116; MEN'S RR 117; WOMEN'S RR 118; KITCHEN AREA: RE-ESTABLISH 1 HOUR RATING WALL AT WEST WALL WHERE 1 HOUR WALL WAS DEMO. OKAY TO DROP THE REST OF THE KITCHEN.
Occupancy Inspection - Fire Temporary C of O 4/27/2017 04/27/2017
Occupancy Inspection - Codes Commercial Failed 4/27/2017 4/27/2017 04/27/2017
Misc
Corrective Action Required
04/27/2017
HANDRAILS REQUIRED AT STAIRS AT DINING PLATFORM
Misc
Corrective Action Required
04/27/2017
IPC 608: BACKFLOW PREVENTION DEVICE REQUIRED AT POTABLE WATER-FED EQUIPMENT EXCEPT WHERE APPROVED AIR GAP IS EXPOSED. AT CARBONATED BEVERAGE DISPENSING EQUIPMENT USE ASSE 1022 LISTED DEVICE.
Misc
Corrective Action Required
04/27/2017
LABEL DUAL GAS AND ELECTRICAL SERVICES
Misc
Corrective Action Required
04/27/2017
LABEL RTU'S AND REFLECT DESIGNATIONS AT ELECTRICAL PANELS
Misc
Corrective Action Required
04/27/2017
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Occupancy Inspection - Codes Commercial Failed 4/28/2017 04/28/2017
Misc
Corrective Action Required
04/27/2017
HANDRAILS REQUIRED AT STAIRS AT DINING PLATFORM
Misc
Corrective Action Required
04/27/2017
IPC 608: BACKFLOW PREVENTION DEVICE REQUIRED AT POTABLE WATER-FED EQUIPMENT EXCEPT WHERE APPROVED AIR GAP IS EXPOSED. AT CARBONATED BEVERAGE DISPENSING EQUIPMENT USE ASSE 1022 LISTED DEVICE.
Misc
Corrective Action Required
04/27/2017
LABEL DUAL GAS AND ELECTRICAL SERVICES PER UTILITY DESIGNATIONS USING MEDALLIONS AND STICKERS, RESPECTIVELY, PRECRIBED BY CODES
Misc
Corrective Action Required
04/27/2017
LABEL RTU'S AND EF'S; REFLECT DESIGNATIONS AT ELECTRICAL PANELS
Misc
Corrective Action Required
04/27/2017
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Misc
Corrective Action Required
04/28/2017
AT MECHANICAL ROOM: - CONSTRUCT "DOWNSPOUT" TO RECEPTOR FOR DRIP TROUGH UNDER WET PIPING ABOVE ELECTRICAL EQUIPMENT
Misc
Corrective Action Required
04/28/2017
ROOFTOP: - PAINT ALL NEW BLACK IRON GAS PIPE (INCLUDING UNDER STRAPS) AND FITTINGS - LIQUID-TIGHT ELECTRICAL WHIP AT ONE EF IS EXCESSIVELY LONG -- SHORTEN TO CORRECT LENGTH - GREASE PAN AT ONE EF IS NOT ATTACHED - CLEAR/CLEAN ALL DEBRIS AND UNUSED MATERIAL FROM ENTIRE FOOTPRINT OF NEW UNIT "W". SEE UNUSED SCREWS AT BASE OF MUA UNIT
Misc
Corrective Action Required
04/28/2017
OK TO SET UP FOR BUSINESS. NO PUBLIC ENTRY OR BUSINESS OPERATIONS PRIOR TO APPROVAL.
Occupancy Inspection - Fire Passed 5/9/2017 05/09/2017
Occupancy Inspection - Codes Commercial Temporary C of O 5/10/2017 5/9/2017 05/09/2017
Misc
Corrective Action Required
04/28/2017
RAISED PLATFORM DINING AREA NOT APPROVED FOR USE UNTIL REQUIRED HANDRAILS ARE INSTALLED AND APPROVED.
Misc
Resolved
05/09/2017
IPC 608: BACKFLOW PREVENTION DEVICE REQUIRED AT POTABLE WATER-FED EQUIPMENT EXCEPT WHERE APPROVED AIR GAP IS EXPOSED. AT CARBONATED BEVERAGE DISPENSING EQUIPMENT USE ASSE 1022 LISTED DEVICE.
Misc
Resolved
05/09/2017
LABEL DUAL GAS AND ELECTRICAL SERVICES PER UTILITY DESIGNATIONS USING MEDALLIONS AND STICKERS, RESPECTIVELY, PRECRIBED BY CODES
Misc
Resolved
05/09/2017
LABEL RTU'S AND EF'S; REFLECT DESIGNATIONS AT ELECTRICAL PANELS
Misc
Corrective Action Required
04/28/2017
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Misc
Resolved
05/09/2017
AT MECHANICAL ROOM: - CONSTRUCT "DOWNSPOUT" TO RECEPTOR FOR DRIP TROUGH UNDER WET PIPING ABOVE ELECTRICAL EQUIPMENT
Misc
Resolved
05/09/2017
ROOFTOP: - PAINT ALL NEW BLACK IRON GAS PIPE (INCLUDING UNDER STRAPS) AND FITTINGS - LIQUID-TIGHT ELECTRICAL WHIP AT ONE EF IS EXCESSIVELY LONG -- SHORTEN TO CORRECT LENGTH - GREASE PAN AT ONE EF IS NOT ATTACHED - CLEAR/CLEAN ALL DEBRIS AND UNUSED MATERIAL FROM ENTIRE FOOTPRINT OF NEW UNIT "W". SEE UNUSED SCREWS AT BASE OF MUA UNIT
Misc
Resolved
05/09/2017
OK TO SET UP FOR BUSINESS. NO PUBLIC ENTRY OR BUSINESS OPERATIONS PRIOR TO APPROVAL.
Occupancy Inspection - Codes Commercial Partial 5/16/2017 5/16/2017 05/16/2017
Misc
Corrective Action Required
05/09/2017
RAISED PLATFORM DINING AREA NOT APPROVED FOR USE UNTIL REQUIRED HANDRAILS ARE INSTALLED AND APPROVED. NORTH END OK.
Misc
Corrective Action Required
05/09/2017
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Occupancy Inspection - Codes Commercial Full C of O 5/18/2017 05/18/2017
Misc
Resolved
05/18/2017
RAISED PLATFORM DINING AREA NOT APPROVED FOR USE UNTIL REQUIRED HANDRAILS ARE INSTALLED AND APPROVED. NORTH END OK.
Misc
Resolved
05/18/2017
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Documents & Images
Date Uploaded File Type Document Name
10/31/2016 Letter Fire Building Plan Review
10/31/2016 Letter Codes P/R Corrections Document
12/01/2016 Letter Fire Building Plan Review
01/17/2017 Letter Codes Plan Review Conditions
01/17/2017 Letter Codes Building Permit
01/18/2017 Receipt Receipt for transaction: 2017-000156
01/24/2017 BigWhiskey
02/10/2017 Letter Inspection Summary
02/13/2017 Letter Inspection Summary
02/22/2017 Letter Inspection Summary
02/28/2017 Letter Inspection Summary
02/28/2017 16104 Big Whiskey's Lee's Summit, MO Narrative ADD 3
02/28/2017 Flame-Stop-IM
03/01/2017 Letter Inspection Summary
03/03/2017 Letter Inspection Summary
03/07/2017 Letter Inspection Summary
03/13/2017 Letter Inspection Summary
03/17/2017 Letter Fire (Alarm) Plan Review Notice
03/17/2017 Letter Fire (Alarm) Plan Review Notice
03/22/2017 Letter Inspection Summary
03/27/2017 Letter Fire (Sprinkler) Plan Review
03/29/2017 Letter Inspection Summary
03/31/2017 Letter Inspection Summary
04/07/2017 Letter Inspection Summary
04/10/2017 Letter Inspection Summary
04/13/2017 Letter Inspection Summary
04/27/2017 Letter Inspection Summary
04/28/2017 Letter Inspection Summary
05/09/2017 Letter Codes Temporary Certificate of Occupancy
05/15/2017 AFC - Big Whiskey's Kitchen Hoods
05/18/2017 Letter Field Certificate of Occupancy
05/19/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home