Permit Application Status

PRCOM20162583


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20162583
Building Permit - Commercial
Final Completion
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
CATH LAB EXPANSION
10/06/2016
10/28/2016
04/10/2017
04/05/2017
Locations
Contacts
JE DUNN CONSTRUCTION CO, Address:120 S CENTRAL AVE STE 350, Phone:(816) 474-8600  
RAND CONSTRUCTION COMPANY, Address:1428 W 9TH ST, Phone:(816) 421-4143  
MARK ONE ELECTRIC CO INC, Address:1414 GENESSEE ST, Phone:(816) 842-7023  
RAND CONSTRUCTION COMPANY, Address:1428 W 9TH ST, Phone:(816) 421-4143  
ACI BOLAND, Address:1421 EAST 104TH ST; SUITE 100, Phone:(816) 763-9600  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 01/27/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
01/27/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ALL NEW OR RELOCATED ALARM SYSTEM NOTIFICATION AND ACTIVATION DEVICES SHALL BE TESTED PRIOR TO THE FINAL OCCUPANCY INSPECTION. ALL CARD READERS, OR ELECTRONICALLY LOCKED ACCESS DOORS WILL DROP OFF ON THE ACTIVATION OF A FIRE ALARM OR POWER LOSS.TO SCHEDULE A TEST CONTACT THE FIRE DPEARTMENT AT 816-969-1300. (VERIFIED AT INSPECTION)
Sprinkler Plan Review Released for Construction 12/01/2016
Joe Dir
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
12/01/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. EXISTING SPSRINKLER SYSTEM RISERS SHALL BE CURRENT WITH ALL REQUIRED SERVICE/MAINTENANCE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE RISERS. (VERIFIED AT INSPECTION)
Building Plan Review Approved with Conditions 10/31/2016 10/26/2016
Joe Frogge
License Tax Application
Corrective Action Required
10/24/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
10/24/2016

Electrical design for cath equipment not submitted. Action required: Comment is for informational purposes. Electrical design will be deferred to construction per request. Field verify
Misc
Resolved
10/26/2016

2012 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Counter top at Break Room 1C121 must be accessible and conform with 2009 ICC/ANSI 606.3
Gen - Submittal documents 7-137
Resolved
10/26/2016

Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. Action required: Provide UL details complete with screw patterns. Also provide penetration details at rated walls.
Licensed Contractors Approved 10/24/2016 10/26/2016
Joe Frogge
LC - MEP Subs
Resolved
10/26/2016

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 10/31/2016 10/25/2016
Joe Dir
10/25/2016

10/25/2016

10/25/2016

Construction documents for fire alarm systems
Corrective Action Required
10/24/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
Construction documents - Fire protection systems
Corrective Action Required
10/24/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM.
Installation acceptance testing
Corrective Action Required
10/24/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACCEPTANCE VISUAL / AUDIBLE TESTING OF THE FIRE ALARM SYSTEM DEVICES WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
10/24/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH THE REQUIRED ANNUAL MAINTENANCE & SERVICE. CURRENT TAGS SHALL BE POSTED ON THE SYSTEMS RISERS. (VERIFIED AT INSPECTION)
Fire Plan Review Approved with Conditions 10/18/2016 10/11/2016
Joe Dir
Misc
Corrective Action Required
10/11/2016

ALL ELECTRONICALLY CONTROLLED CORRIDOR AND EGRESS DOORS WILL FOLLOW THE FOLLOWING SECTIONS IN IFC 2012: 1008.1.9.6, 1008.1.9.7, 1008.1.9.8, 1008.1.9.9
Construction documents for fire alarm systems
Corrective Action Required
10/11/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
Address numbers required
Corrective Action Required
10/11/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ALL ROOMS SHALL BE IDENTIFIED OFF THE CORRIDORS. (VERIFIED AT INSPECTION)
Construction documents - Fire protection systems
Corrective Action Required
10/11/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM.
Installation acceptance testing
Corrective Action Required
10/11/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACCEPTANCE VISUAL / AUDIBLE TESTING OF THE FIRE ALARM SYSTEM DEVICES WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
10/11/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH THE REQUIRED ANNUAL MAINTENANCE & SERVICE. CURRENT TAGS SHALL BE POSTED ON THE SYSTEMS RISERS. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
10/11/2016

CONTRACTOR SHALL PROVIDE MED GAS LINE TEST REPORTS PRIOR TO THE FINAL OCCPANCY INSPECTION. (INFORMATION PURPOSES)
Building Plan Review Rejected 10/18/2016 10/11/2016
Joe Frogge
License Tax Application
Corrective Action Required
10/11/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
10/11/2016

Electrical design for cath equipment not submitted. Action required: Comment is for informational purposes. Electrical design will be deferred to construction per request.
Misc
Corrective Action Required
10/11/2016

2012 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Counter top at Break Room 1C121 must be accessible and conform with 2009 ICC/ANSI 606.3
Gen - Submittal documents 7-137
Corrective Action Required
10/11/2016

Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. Action required: Provide UL details complete with screw patterns. Also provide penetration details at rated walls.
Licensed Contractors Rejected 10/18/2016 10/11/2016
Joe Frogge
LC - MEP Subs
Corrective Action Required
10/11/2016

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $3,281.75 $3,281.75 Paid 10/28/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Not Ready 11/10/2016 11/10/2016
Underslab Plumbing Inspection - Commercial Partial 11/11/2016 11/11/2016 11/11/2016
Misc
Partial Correction
11/11/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 1C122; 1D24; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Plumbing Inspection - Commercial Partial 11/14/2016 11/14/2016
Misc
Partial Correction
11/11/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 1C122; 1D24; 1C217; 1C218 EXCEPT ONE LOCATION TO BE BLOCKED-OUT FOR POSSIBLE REVISION; 1C218A; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
In-wall Inspection Partial 11/15/2016 11/15/2016 11/15/2016
Misc
Partial Correction
11/15/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL AFTER BOCA PLATES ARE IN PLACE TO PROTECT PVC PIPE AT BOTTOM TRACK;
In-wall Inspection Partial 11/18/2016 11/18/2016 11/18/2016
Misc
Partial Correction
11/15/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219;
Underslab Plumbing Inspection - Commercial Partial 11/18/2016 11/18/2016
Misc
Partial Correction
11/14/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 1C122; 1D24; 1C217; 1C218; 1C218A; RELOCATED SCRUB SINK @ 1C219; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
In-wall Inspection Partial 11/22/2016 11/22/2016 11/22/2016
Misc
Partial Correction
11/18/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F;
In-wall Inspection Partial 11/30/2016 11/30/2016 11/30/2016
Misc
Partial Correction
11/22/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; B/F = BOTH FACES O/SF = OUTSIDE FACE
Rated Assembly Inspection Partial 12/5/2016 12/5/2016 12/05/2016
Misc
Partial Correction
12/05/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: 1D25 & 1D26 WEST WALL; 1C133 S WALL B/F; B/F = BOTH FACES
In-wall Inspection Partial 12/5/2016 12/5/2016 12/05/2016
Misc
Partial Correction
11/30/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; B/F = BOTH FACES O/SF = OUTSIDE FACE
Final Inspection - Commercial Partial 12/7/2016 12/07/2016
Misc
Partial Correction
12/07/2016
1D22 EKG/VASCULAR OK FOR USE CONTINGENT ON LATER INSPECTION BY FIRE DEPT;
Rated Assembly Inspection Partial 12/7/2016 12/7/2016 12/07/2016
Misc
Partial Correction
12/05/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: 1D25 & 1D26 WEST WALL; 1C133 S WALL B/F; 1D25 & 1D26 BACK FACES, CONTINGENT ON APPROVABLE FIRE-STOPPING TO BE INSPECTED WHEN READY; B/F = BOTH FACES
In-wall Inspection Partial 12/7/2016 12/7/2016 12/07/2016
Misc
Partial Correction
12/05/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; B/F = BOTH FACES O/SF = OUTSIDE FACE
Underslab Plumbing Inspection - Commercial Partial 12/14/2016 12/14/2016 12/14/2016
Misc
Partial Correction
11/18/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 1C122; 1D24; 1C217; 1C218; 1C218A; RELOCATED SCRUB SINK @ 1C219; 1C117; 1C121; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Rated Assembly Inspection Partial 12/14/2016 12/14/2016
Misc
Partial Correction
12/07/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: 1D25 & 1D26 WEST WALL; 1C133 S WALL B/F; 1D25 & 1D26 BACK FACES, CONTINGENT ON APPROVABLE FIRE-STOPPING TO BE INSPECTED WHEN READY; N&W WALLS OF 1D24 UP TO 10' AFF B/F; B/F = BOTH FACES
In-wall Inspection Partial 12/14/2016 12/14/2016 12/14/2016
Misc
Partial Correction
12/07/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; B/F = BOTH FACES O/SF = OUTSIDE FACE
Underslab Plumbing Inspection - Commercial Partial 12/16/2016 12/16/2016
Misc
Partial Correction
12/14/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 1C122; 1D24; 1C217; 1C218; 1C218A; RELOCATED SCRUB SINK @ 1C219; 1C117; 1C121; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Misc
Partial Correction
12/16/2016
OK TO COVER WHEN READY TWO COPPER LINES SLEEVED IN PVC IN 1C218 FROM CENTER OF ROOM TO WEST WALL
Underslab Electrical Inspection - Commercial Partial 12/16/2016 12/16/2016 12/16/2016
Misc
Partial Correction
12/16/2016
OK TO COVER WHEN READY UNDER-SLAB ELECTRICAL CONDUIT & BOXES (MATERIAL & WORKMANSHIP) AT 1C218
In-wall Inspection Not Ready 12/22/2016 12/22/2016 12/22/2016
Misc
Partial Correction
12/14/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; B/F = BOTH FACES O/SF = OUTSIDE FACE
Rated Assembly Inspection Partial 12/27/2016 12/27/2016 12/27/2016
Misc
Partial Correction
12/14/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: 1D25 & 1D26 WEST WALL; 1C133 S WALL B/F; 1D25 & 1D26 BACK FACES, CONTINGENT ON APPROVABLE FIRE-STOPPING TO BE INSPECTED WHEN READY; N&W WALLS OF 1D24 UP TO 10' AFF B/F; LINER BOARD HIGH ON WALL @ 1D24 NE B/F; B/F = BOTH FACES
Above Ceiling Inspection Partial 12/27/2016 12/27/2016 12/27/2016
Misc
Partial Correction
12/27/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216;
In-wall Inspection Partial 12/27/2016 12/27/2016 12/27/2016
Misc
Partial Correction
12/22/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; B/F = BOTH FACES O/SF = OUTSIDE FACE
Above Ceiling Inspection Partial 12/28/2016 12/28/2016 12/28/2016
Misc
Partial Correction
12/27/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133 AFTER HANGING CONDUIT IS SECURED OR REMOVED, FLEX PENETRATION OF RATED WALL IS FIRE-STOPPED, AND COPPER PIPE IS ISOLATED FROM STEEL TOP TRACK; C137 AFTER HVAC DIFFUSER IS IN PLACE AND FLEX DUCT HAS PROPER LENGTH WITH NO KINKS;
In-wall Inspection Partial 12/28/2016 12/28/2016 12/28/2016
Misc
Partial Correction
12/27/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; B/F = BOTH FACES O/SF = OUTSIDE FACE
Final Inspection - Commercial Partial 12/30/2016 12/29/2016 12/29/2016
Misc
Partial Correction
12/07/2016
1D22 EKG/VASCULAR; 1C133; 1C216 OK FOR USE CONTINGENT ON LATER INSPECTION BY FIRE DEPT;
Occupancy Inspection - Fire Temporary C of O 12/30/2016 12/30/2016
In-wall Inspection Partial 1/9/2017 1/9/2017 01/09/2017
Misc
Partial Correction
12/28/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; [XXX] PER RFI; WALL AT/ADJACENT TO DOOR (1D23); B/F = BOTH FACES O/SF = OUTSIDE FACE
Above Ceiling Inspection Partial 1/9/2017 01/09/2017
Misc
Partial Correction
12/28/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133 AFTER HANGING CONDUIT IS SECURED OR REMOVED, FLEX PENETRATION OF RATED WALL IS FIRE-STOPPED, AND COPPER PIPE IS ISOLATED FROM STEEL TOP TRACK; C137; [1D25];
Underslab Electrical Inspection - Commercial Partial 1/9/2017 01/09/2017
Misc
Partial Correction
01/09/2017
OK TO COVER WHEN READY UNDER-SLAB ELECTRICAL CONDUIT & BOXES (MATERIAL & WORKMANSHIP) AT 1C218; RELOCATED ELECTRICAL CONDUIT & BOX AT [1C218];
Rated Assembly Inspection Partial 1/9/2017 01/09/2017
Misc
Partial Correction
12/27/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: 1D25 & 1D26 WEST WALL; 1C133 S WALL B/F; 1D25 & 1D26 BACK FACES, CONTINGENT ON APPROVABLE FIRE-STOPPING TO BE INSPECTED WHEN READY; N&W WALLS OF 1D24 UP TO 10' AFF B/F; LINER BOARD HIGH ON WALL @ 1D24 NE B/F; 1D24 NE; B/F = BOTH FACES
In-wall Inspection Partial 1/10/2017 01/10/2017
Misc
Partial Correction
01/09/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; [XXX] PER RFI; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; B/F = BOTH FACES O/SF = OUTSIDE FACE
In-wall Inspection Partial 1/11/2017 1/11/2017 01/11/2017
Misc
Partial Correction
01/10/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; [XXX] PER RFI; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; [1C118A] E WALL; [1C119] S WALL; B/F = BOTH FACES O/SF = OUTSIDE FACE
In-wall Inspection Partial 1/13/2017 1/13/2017 01/13/2017
Misc
Partial Correction
01/11/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; [XXX] PER RFI; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; [1C118A] E WALL; [1C119] S WALL; CHASE AT [218] SE CORNER; [219] E & W WALLS; B/F = BOTH FACES O/SF = OUTSIDE FACE
In-wall Inspection Partial 1/17/2017 1/17/2017 01/17/2017
Misc
Partial Correction
01/13/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; [XXX] PER RFI; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; [1C118A] E WALL; [1C119] S WALL; CHASE AT [218] SE CORNER; [219] E & W WALLS; [1D23] EXCEPT NOW-SEPARATED SPACE AT SOUTH MUST BE SBMITTED AND APPROVED AS REVISION OF RATED ASSEMBLY ENVELOPE; B/F = BOTH FACES O/SF = OUTSIDE FACE
In-wall Inspection Partial 1/19/2017 1/19/2017 01/19/2017
Misc
Partial Correction
01/17/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; [XXX] PER RFI; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; [1C118A] E WALL; [1C119] S WALL; CHASE AT [218] SE CORNER; [1C219] E & W WALLS; WING WALL @ [1C219] S; N WALL OF NEWLY-ENCLOSED CLOSET PER PR#5 AT [1D23] SOUTH; B/F = BOTH FACES O/SF = OUTSIDE FACE
Misc
Resolved
01/19/2017
Rated Assembly Inspection Partial 1/19/2017 01/19/2017
Misc
Partial Correction
01/09/2017
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: 1D25 & 1D26 WEST WALL; 1C133 S WALL B/F; 1D25 & 1D26 BACK FACES, CONTINGENT ON APPROVABLE FIRE-STOPPING TO BE INSPECTED WHEN READY; N&W WALLS OF 1D24 UP TO 10' AFF B/F; LINER BOARD HIGH ON WALL @ 1D24 NE B/F; 1D24 NE; [1D23] W WALL N + S WALL W; B/F = BOTH FACES
In-wall Inspection Partial 1/25/2017 1/25/2017 01/25/2017
Misc
Partial Correction
01/19/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; [1C118A] E WALL; [1C119] S WALL; CHASE AT [218] SE CORNER; [1C219] E & W WALLS; WING WALL @ [1C219] S; N WALL OF NEWLY-ENCLOSED CLOSET PER PR#5 AT [1D23] SOUTH; [1C211] N WALL B/F; FRAMING AT DOOR OPENINGS (1C101) & (1C197) B/F; B/F = BOTH FACES O/SF = OUTSIDE FACE
Above Ceiling Inspection Partial 1/26/2017 1/26/2017 01/26/2017
Misc
Partial Correction
01/09/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133 AFTER HANGING CONDUIT IS SECURED OR REMOVED, FLEX PENETRATION OF RATED WALL IS FIRE-STOPPED, AND COPPER PIPE IS ISOLATED FROM STEEL TOP TRACK; C137; [1D25];
Above Ceiling Inspection Not Ready 1/27/2017 01/27/2017
Misc
Partial Correction
01/26/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133 AFTER HANGING CONDUIT IS SECURED OR REMOVED, FLEX PENETRATION OF RATED WALL IS FIRE-STOPPED, AND COPPER PIPE IS ISOLATED FROM STEEL TOP TRACK; C137; [1D25];
Above Ceiling Inspection Partial 1/30/2017 1/30/2017 01/30/2017
Misc
Partial Correction
01/27/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133; C137; [1D25]; 1C217; 1C218A; 1C219; 1C218 WEST 1/2; REMOVE ABANDONED F.P. PIPING FROM EAST 1/2 >> REQUEST RE-INSPECTION 1C221 & 1C223 OK TO COVER AFTER LOW-VOLTAGE WIRING IS COMPLETED WITH BOXES CLOSED 1D24 NOT APPROVED TO COVER
In-wall Inspection Partial 2/1/2017 2/1/2017 02/01/2017
Misc
Partial Correction
01/25/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; [1C118A] E WALL; [1C119] S WALL; CHASE AT [218] SE CORNER; [1C219] E & W WALLS; WING WALL @ [1C219] S; N WALL OF NEWLY-ENCLOSED CLOSET PER PR#5 AT [1D23] SOUTH; [1C211] N WALL B/F; FRAMING AT DOOR OPENINGS (1C101) & (1C197) B/F; [1C101]; B/F = BOTH FACES O/SF = OUTSIDE FACE
Above Ceiling Inspection Partial 2/1/2017 02/01/2017
Misc
Partial Correction
01/30/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133; C137; [1D25]; 1C217; 1C218A; 1C219; 1C221; 1C223; 1C218 INCLUDING EAST 1/2; 1D24;
Above Ceiling Inspection Partial 2/6/2017 2/6/2017 02/06/2017
Misc
Partial Correction
02/01/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133; C137; [1D25]; 1C217; 1C218A; 1C219; 1C221; 1C223; 1C218 INCLUDING EAST 1/2; 1D24; 1D26 AFTER RATED WALL STICKERS ARE ADHERED TO WALL RATHER THAN TO M/E/P COMPONENTS; 1C117-1C120 SUBJECT TO RE-INSPECTION AFTER RENOVATION PROCEEDS;
Above Ceiling Inspection Not Ready 2/8/2017 2/8/2017 02/08/2017
Misc
Partial Correction
02/06/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133; C137; [1D25]; 1C217; 1C218A; 1C219; 1C221; 1C223; 1C218 INCLUDING EAST 1/2; 1D24; 1D26 AFTER RATED WALL STICKERS ARE ADHERED TO WALL RATHER THAN TO M/E/P COMPONENTS; 1C117-1C120 SUBJECT TO RE-INSPECTION AFTER RENOVATION PROCEEDS;
Alarm Test Passed 2/9/2017 02/09/2017
Occupancy Inspection - Fire Temporary C of O 2/9/2017 02/09/2017
Final Inspection - Commercial Partial 1/24/2017 1/24/2017 02/09/2017
Misc
Partial Correction
12/29/2016
SPACES OK FOR USE: 1D22 EKG/VASCULAR; 1C133; 1C216; 1C137; 1C101;
Final Inspection - Commercial Failed 2/9/2017 02/09/2017
Misc
Partial Correction
02/09/2017
SPACES OK FOR USE: 1D22 EKG/VASCULAR; 1C133; 1C216; 1C137; 1C101;
Misc
Corrective Action Required
02/09/2017
1C218; 1D25; 1D26; 1C1`22; 1C123: - ELECTRICAL PANEL NOT IDENTIFIED - CIRCUITS AT PANEL NOT IDENTIFIED - DISCONNECT NOT LABELED - ENSURE ALL ELECTRICAL RECEPTACLES HAVE YOKE SPACERS IF NEEDED AND ARE MOUNTED SOLID - COPPER DRAIN PIPES NOT SECURED ABOVE FLOOR SINK - ONE EMERGENCY RECEPTACLE NOT HOT FOR TEST
Above Ceiling Inspection Partial 2/9/2017 02/09/2017
Misc
Partial Correction
02/08/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133; C137; [1D25]; 1C217; 1C218A; 1C219; 1C221; 1C223; 1C218 INCLUDING EAST 1/2; 1D24; 1D26 AFTER RATED WALL STICKERS ARE ADHERED TO WALL RATHER THAN TO M/E/P COMPONENTS; 1C117-1C120 SUBJECT TO RE-INSPECTION AFTER RENOVATION PROCEEDS; 1C101;
Final Inspection - Commercial Partial 2/10/2017 02/10/2017
Misc
Partial Correction
02/09/2017
SPACES OK FOR USE: 1D22 EKG/VASCULAR; 1C133; 1C216; 1C137; 1C101;
Misc
Corrective Action Required
02/09/2017
1C218; 1D25; 1D26; 1C1`22; 1C123: - ELECTRICAL PANEL NOT IDENTIFIED - CIRCUITS AT PANEL NOT IDENTIFIED - DISCONNECT NOT LABELED - ENSURE ALL ELECTRICAL RECEPTACLES HAVE YOKE SPACERS IF NEEDED AND ARE MOUNTED SOLID - COPPER DRAIN PIPES NOT SECURED ABOVE FLOOR SINK - ONE EMERGENCY RECEPTACLE NOT HOT FOR TEST
Above Ceiling Inspection Partial 2/11/2017 02/11/2017
Misc
Partial Correction
02/09/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133; C137; [1D25]; 1C217; 1C218A; 1C219; 1C221; 1C223; 1C218 INCLUDING EAST 1/2; 1D24; 1D26 AFTER RATED WALL STICKERS ARE ADHERED TO WALL RATHER THAN TO M/E/P COMPONENTS; 1C117-1C120 OK AFTER ONE F.A. BOX AND CONDUIT ARE REMOVED IF ABANDONED -- SECURED AND CLOSED IF TO REMAIN IN USE; 1C101;
Final Inspection - Commercial Partial 2/14/2017 2/14/2017 02/14/2017
Misc
Partial Correction
02/10/2017
SPACES OK FOR USE: 1D22 EKG/VASCULAR; 1C133; 1C216; 1C137; 1C101; 1C117-1C120 BLOOD DRAW AREA AFTER MICROWAVE OVEN RECEPT IS GFI PROTECTED;
Misc
Corrective Action Required
02/10/2017
1C218; 1D25; 1D26; 1C1`22; 1C123: - ELECTRICAL PANEL NOT IDENTIFIED - CIRCUITS AT PANEL NOT IDENTIFIED - DISCONNECT NOT LABELED - ENSURE ALL ELECTRICAL RECEPTACLES HAVE YOKE SPACERS IF NEEDED AND ARE MOUNTED SOLID - COPPER DRAIN PIPES NOT SECURED ABOVE FLOOR SINK - ONE EMERGENCY RECEPTACLE NOT HOT FOR TEST
Above Ceiling Inspection Partial 2/14/2017 02/14/2017
Misc
Partial Correction
02/11/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133; C137; [1D25]; 1C217; 1C218A; 1C219; 1C221; 1C223; 1C218 INCLUDING EAST 1/2; 1D24; 1D26 AFTER RATED WALL STICKERS ARE ADHERED TO WALL RATHER THAN TO M/E/P COMPONENTS; 1C117-1C120 OK AFTER ONE F.A. BOX AND CONDUIT ARE REMOVED IF ABANDONED -- SECURED AND CLOSED IF TO REMAIN IN USE; 1C101;
Misc
Partial Correction
02/14/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING FOR SOFFITS ABOVE DOORS AT TWO PREP ROOMS
Occupancy Inspection - Fire Temporary C of O 2/14/2017 02/14/2017
Underslab Plumbing Inspection - Commercial Partial 2/17/2017 2/17/2017 02/17/2017
Misc
Partial Correction
12/16/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 1C122; 1D24; 1C217; 1C218; 1C218A; RELOCATED SCRUB SINK @ 1C219; 1C117; 1C121; 1C123; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Misc
Resolved
02/17/2017
OK TO COVER WHEN READY TWO COPPER LINES SLEEVED IN PVC IN 1C218 FROM CENTER OF ROOM TO WEST WALL
Final Inspection - Commercial Not Ready 2/17/2017 2/17/2017 02/17/2017
Misc
Partial Correction
02/14/2017
SPACES OK FOR USE: 1D22 EKG/VASCULAR; 1C133; 1C216; 1C137; 1C101; 1C117-1C120 BLOOD DRAW AREA AFTER MICROWAVE OVEN RECEPT IS GFI PROTECTED;
Misc
Corrective Action Required
02/14/2017
1C218; 1D25; 1D26; 1C1`22; 1C123: - ELECTRICAL PANEL NOT IDENTIFIED - CIRCUITS AT PANEL NOT IDENTIFIED - DISCONNECT NOT LABELED - ENSURE ALL ELECTRICAL RECEPTACLES HAVE YOKE SPACERS IF NEEDED AND ARE MOUNTED SOLID - ONE EMERGENCY RECEPTACLE NOT HOT FOR TEST
In-wall Inspection Partial 2/17/2017 2/17/2017 02/17/2017
Misc
Partial Correction
02/01/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; [1C118A] E WALL; [1C119] S WALL; CHASE AT [218] SE CORNER; [1C219] E & W WALLS; WING WALL @ [1C219] S; N WALL OF NEWLY-ENCLOSED CLOSET PER PR#5 AT [1D23] SOUTH; [1C211] N WALL B/F; FRAMING AT DOOR OPENINGS (1C101) & (1C197) B/F; [1C101]; SINK MODIFICATION AT 1C123; B/F = BOTH FACES O/SF = OUTSIDE FACE
Final Inspection - Commercial Partial 2/21/2017 2/17/2017 02/17/2017
Misc
Partial Correction
02/17/2017
SPACES OK FOR USE: 1D22 EKG/VASCULAR; 1C133; 1C216; 1C137; 1C101; 1C117-1C120 BLOOD DRAW AREA; 1C124; 1C125;
Misc
Corrective Action Required
02/17/2017
1C218; 1D25; 1D26; 1C1`22; 1C123: - ELECTRICAL PANEL NOT IDENTIFIED - CIRCUITS AT PANEL NOT IDENTIFIED - DISCONNECT NOT LABELED
In-wall Inspection Partial 2/28/2017 2/28/2017 02/28/2017
Misc
Partial Correction
02/17/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; [1C118A] E WALL; [1C119] S WALL; CHASE AT [218] SE CORNER; [1C219] E & W WALLS; WING WALL @ [1C219] S; N WALL OF NEWLY-ENCLOSED CLOSET PER PR#5 AT [1D23] SOUTH; [1C211] N WALL B/F; FRAMING AT DOOR OPENINGS (1C101) & (1C197) B/F; [1C101]; SINK MODIFICATION AT 1C123; TWO CHASES/ COLUMMN WRAPS IN 1C116; B/F = BOTH FACES O/SF = OUTSIDE FACE
Final Inspection - Commercial Partial 2/28/2017 2/28/2017 02/28/2017
Misc
Partial Correction
02/17/2017
SPACES OK FOR USE: 1D22 EKG/VASCULAR; 1C133; 1C216; 1C137; 1C101; 1C117-1C120 BLOOD DRAW AREA; 1C124; 1C125; 1C218 ; 1C218A; 1C219; 1C221; 1C223;
Misc
Resolved
02/28/2017
1C218; 1D25; 1D26; 1C1`22; 1C123: - ELECTRICAL PANEL NOT IDENTIFIED - CIRCUITS AT PANEL NOT IDENTIFIED - DISCONNECT NOT LABELED
Above Ceiling Inspection Partial 2/28/2017 2/28/2017 02/28/2017
Misc
Partial Correction
02/14/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133; C137; [1D25]; 1C217; 1C218A; 1C219; 1C221; 1C223; 1C218 INCLUDING EAST 1/2; 1D24; 1D26 AFTER RATED WALL STICKERS ARE ADHERED TO WALL RATHER THAN TO M/E/P COMPONENTS; 1C117-1C120; 1C101; 1D25; 1D26; 1C1122; 1C123; FACIA ONLY AT SOFFIT IN 1C116; PARTIAL FOR MODIFICATIONS AT IR READ ROOM 116;
Misc
Partial Correction
02/14/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING FOR SOFFITS ABOVE DOORS AT TWO PREP ROOMS
Final Inspection - Commercial Partial 2/28/2017 02/28/2017
Misc
Partial Correction
02/28/2017
SPACES OK FOR USE: 1D22 EKG/VASCULAR; 1C133; 1C216; 1C137; 1C101; 1C117-1C120 BLOOD DRAW AREA; 1C124; 1C125; 1C218 ; 1C218A; 1C219; 1C221; 1C223;
Above Ceiling Inspection Partial 3/2/2017 3/2/2017 03/02/2017
Misc
Partial Correction
02/28/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133; C137; [1D25]; 1C217; 1C218A; 1C219; 1C221; 1C223; 1C218 INCLUDING EAST 1/2; 1D24; 1D26 AFTER RATED WALL STICKERS ARE ADHERED TO WALL RATHER THAN TO M/E/P COMPONENTS; 1C117-1C120; 1C101; 1D25; 1D26; 1C1122; 1C123; FACIA ONLY AT SOFFIT IN 1C116; PARTIAL FOR MODIFICATIONS AT IR READ ROOM 116; 1C197 AFTER ELECTRICAL BOXES ARE SECURED AND CLOSED;
Misc
Partial Correction
02/28/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING FOR SOFFITS ABOVE DOORS AT TWO PREP ROOMS; SOFFIT AT 1C115/116 BLOOD DRAW WAITING AFTER TWO ABANDONED STUDS ARE REMOVED;
In-wall Inspection Not Ready 3/6/2017 3/6/2017 03/06/2017
Misc
Partial Correction
02/28/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; [1C118A] E WALL; [1C119] S WALL; CHASE AT [218] SE CORNER; [1C219] E & W WALLS; WING WALL @ [1C219] S; N WALL OF NEWLY-ENCLOSED CLOSET PER PR#5 AT [1D23] SOUTH; [1C211] N WALL B/F; FRAMING AT DOOR OPENINGS (1C101) & (1C197) B/F; [1C101]; SINK MODIFICATION AT 1C123; TWO CHASES/ COLUMMN WRAPS IN 1C116; B/F = BOTH FACES O/SF = OUTSIDE FACE ****CALLED THREE TIMES, BUT ZACK NOT ANSWERING. CANCEL INSPECTION
In-wall Inspection Partial 3/7/2017 3/7/2017 03/07/2017
Misc
Partial Correction
03/06/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; [1C118A] E WALL; [1C119] S WALL; CHASE AT [218] SE CORNER; [1C219] E & W WALLS; WING WALL @ [1C219] S; N WALL OF NEWLY-ENCLOSED CLOSET PER PR#5 AT [1D23] SOUTH; [1C211] N WALL B/F; FRAMING AT DOOR OPENINGS (1C101) & (1C197) B/F; [1C101]; SINK MODIFICATION AT 1C123; TWO CHASES/ COLUMMN WRAPS IN 1C116; C102 WALL AND COLUMN. B/F = BOTH FACES O/SF = OUTSIDE FACE ****CALLED THREE TIMES, BUT ZACK NOT ANSWERING. CANCEL INSPECTION
Final Inspection - Commercial Partial 3/9/2017 3/9/2017 03/09/2017
Misc
Partial Correction
02/28/2017
SPACES OK FOR USE: 1D22 EKG/VASCULAR; 1C133; 1C216; 1C137; 1C101; 1C117-1C120 BLOOD DRAW AREA; 1C124; 1C125; 1C218 ; 1C218A; 1C219; 1C221; 1C223; 1C211:1C197
Above Ceiling Inspection Partial 3/9/2017 3/9/2017 03/09/2017
Misc
Partial Correction
03/02/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133; C137; [1D25]; 1C217; 1C218A; 1C219; 1C221; 1C223; 1C218 INCLUDING EAST 1/2; 1D24; 1D26 AFTER RATED WALL STICKERS ARE ADHERED TO WALL RATHER THAN TO M/E/P COMPONENTS; 1C117-1C120; 1C101; 1D25; 1D26; 1C1122; 1C123; FACIA ONLY AT SOFFIT IN 1C116; PARTIAL FOR MODIFICATIONS AT IR READ ROOM 116; 1C197 AFTER ELECTRICAL BOXES ARE SECURED AND CLOSED; 1C115;1C116
Misc
Partial Correction
03/02/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING FOR SOFFITS ABOVE DOORS AT TWO PREP ROOMS; SOFFIT AT 1C115/116 BLOOD DRAW WAITING AFTER TWO ABANDONED STUDS ARE REMOVED;
Final Inspection - Commercial Partial 3/14/2017 3/14/2017 03/14/2017
Misc
Partial Correction
03/09/2017
SPACES OK FOR USE & OCCUPANCY: 1D22 EKG/VASCULAR; 1C133; 1C216; 1C137; 1C101; 1C117-1C120 BLOOD DRAW AREA; 1C124; 1C125; 1C218 ; 1C218A; 1C219; 1C221; 1C223; 1C211:1C197; BLOOD DRAW RECEPTION 1C115/116;
In-wall Inspection Partial 3/14/2017 03/14/2017
Misc
Partial Correction
03/07/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; [1C118A] E WALL; [1C119] S WALL; CHASE AT [218] SE CORNER; [1C219] E & W WALLS; WING WALL @ [1C219] S; N WALL OF NEWLY-ENCLOSED CLOSET PER PR#5 AT [1D23] SOUTH; [1C211] N WALL B/F; FRAMING AT DOOR OPENINGS (1C101) & (1C197) B/F; [1C101]; SINK MODIFICATION AT 1C123; TWO CHASES/ COLUMMN WRAPS IN 1C116; C102WALL AND COLUMN; CORRIDOR WALL IN-FILL B/F AT CART PARK SPACE; B/F = BOTH FACES O/SF = OUTSIDE FACE
Above Ceiling Inspection Partial 3/17/2017 03/17/2017
Misc
Partial Correction
03/09/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING FOR SOFFITS ABOVE DOORS AT TWO PREP ROOMS; SOFFIT AT 1C115/116 BLOOD DRAW WAITING AFTER TWO ABANDONED STUDS ARE REMOVED;
Misc
Partial Correction
03/09/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133; C137; [1D25]; 1C217; 1C218A; 1C219; 1C221; 1C223; 1C218 INCLUDING EAST 1/2; 1D24; 1D26 AFTER RATED WALL STICKERS ARE ADHERED TO WALL RATHER THAN TO M/E/P COMPONENTS; 1C117-1C120; 1C101; 1D25; 1D26; 1C1122; 1C123; FACIA ONLY AT SOFFIT IN 1C116; PARTIAL FOR MODIFICATIONS AT IR READ ROOM 116; 1C197 AFTER ELECTRICAL BOXES ARE SECURED AND CLOSED; 1C115;1C116; ABOVE-CEILING MODIFICATIONS AT MAIN WAITING ROOMS EXPANSION SPACE TO BE COMPLETED DURING OFF-HOURS AND PUT INTO USE IMMEDIATELY OK TO COVER WHEN READY;
Above Ceiling Inspection Passed 3/23/2017 3/23/2017 03/23/2017
Misc
Resolved
03/23/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING FOR SOFFITS ABOVE DOORS AT TWO PREP ROOMS; SOFFIT AT 1C115/116 BLOOD DRAW WAITING AFTER TWO ABANDONED STUDS ARE REMOVED;
Misc
Resolved
03/23/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1C216; 1C133; C137; [1D25]; 1C217; 1C218A; 1C219; 1C221; 1C223; 1C218 INCLUDING EAST 1/2; 1D24; 1D26 AFTER RATED WALL STICKERS ARE ADHERED TO WALL RATHER THAN TO M/E/P COMPONENTS; 1C117-1C120; 1C101; 1D25; 1D26; 1C1122; 1C123; FACIA ONLY AT SOFFIT IN 1C116; PARTIAL FOR MODIFICATIONS AT IR READ ROOM 116; 1C197 AFTER ELECTRICAL BOXES ARE SECURED AND CLOSED; 1C115;1C116; ABOVE-CEILING MODIFICATIONS AT MAIN WAITING ROOMS EXPANSION SPACE TO BE COMPLETED DURING OFF-HOURS AND PUT INTO USE IMMEDIATELY OK TO COVER WHEN READY; STORAGE ROOM
In-wall Inspection Passed 3/17/2017 3/14/2017 03/24/2017
Misc
Resolved
03/24/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 1C122 SOUTH WALL; 1C216; 1C217; CUT-IN DOOR 1C219; 1D23 NW WALL B/F; 1D25; 1D26; IN-FILL AT 1D22 N WALL B/F; 1D24 B/F; 1D25 O/SF; 1D26 W WALL B/F; 1D221 E WALL B/F; 1C223; 1C221 CONTINGENT ON SEGMENT OF CORRIDOR SMOKE WALL BEING SMOKE-SEALED; C137; E/NE WALL; 1C120 & 121 B/F; 1C218 E & S WALLS; [1C118] E & NW; [1C120] S WALL; [1C218] N WALL AFTER 2 BOCA PLATES IN PLACE; WALL AT/ADJACENT TO DOOR (1D23); [1C118] W WALL; [1C118A] E WALL; [1C119] S WALL; CHASE AT [218] SE CORNER; [1C219] E & W WALLS; WING WALL @ [1C219] S; N WALL OF NEWLY-ENCLOSED CLOSET PER PR#5 AT [1D23] SOUTH; [1C211] N WALL B/F; FRAMING AT DOOR OPENINGS (1C101) & (1C197) B/F; [1C101]; SINK MODIFICATION AT 1C123; TWO CHASES/ COLUMMN WRAPS IN 1C116; C102WALL AND COLUMN; CORRIDOR WALL IN-FILL B/F AT CART PARK SPACE; B/F = BOTH FACES O/SF = OUTSIDE FACE
Underslab Electrical Inspection - Commercial Passed 1/9/2017 03/24/2017
Misc
Resolved
03/24/2017
OK TO COVER WHEN READY UNDER-SLAB ELECTRICAL CONDUIT & BOXES (MATERIAL & WORKMANSHIP) AT 1C218; RELOCATED ELECTRICAL CONDUIT & BOX AT [1C218];
Underslab Plumbing Inspection - Commercial Passed 2/17/2017 03/24/2017
Misc
Resolved
03/24/2017
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 1C122; 1D24; 1C217; 1C218; 1C218A; RELOCATED SCRUB SINK @ 1C219; 1C117; 1C121; 1C123; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Rated Assembly Inspection Passed 1/19/2017 03/24/2017
Misc
Resolved
03/24/2017
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: 1D25 & 1D26 WEST WALL; 1C133 S WALL B/F; 1D25 & 1D26 BACK FACES, CONTINGENT ON APPROVABLE FIRE-STOPPING TO BE INSPECTED WHEN READY; N&W WALLS OF 1D24 UP TO 10' AFF B/F; LINER BOARD HIGH ON WALL @ 1D24 NE B/F; 1D24 NE; [1D23] W WALL N + S WALL W; B/F = BOTH FACES
Final Inspection - Commercial Passed 4/4/2017 4/4/2017 04/04/2017
Misc
Resolved
04/04/2017
SPACES OK FOR USE & OCCUPANCY: 1D22 EKG/VASCULAR; 1C133; 1C216; 1C137; 1C101; 1C117-1C120 BLOOD DRAW AREA; 1C124; 1C125; 1C218 ; 1C218A; 1C219; 1C221; 1C223; 1C211:1C197; BLOOD DRAW RECEPTION 1C115/116;
Occupancy Inspection - Fire Passed 4/4/2017 04/04/2017
Alarm Test Passed 4/4/2017 04/04/2017
Occupancy Inspection - Fire Passed 7/26/2017 07/26/2017
Documents & Images
Date Uploaded File Type Document Name
10/11/2016 Letter Fire Building Plan Review
10/12/2016 Letter Codes P/R Corrections Document
10/25/2016 Letter Fire Building Plan Review
10/26/2016 Letter Codes Plan Review Conditions
10/28/2016 Receipt Receipt for transaction: 2016-006630
10/28/2016 Letter Codes Building Permit
11/11/2016 Letter Inspection Summary
11/14/2016 Letter Inspection Summary
11/15/2016 Letter Inspection Summary
11/18/2016 Letter Inspection Summary
11/22/2016 Letter Inspection Summary
11/30/2016 Letter Inspection Summary
12/01/2016 Letter Fire (Sprinkler) Plan Review
12/05/2016 Letter Inspection Summary
12/07/2016 Letter Inspection Summary
12/14/2016 Letter Inspection Summary
12/16/2016 Letter Inspection Summary
12/22/2016 Letter Inspection Summary
12/27/2016 Letter Inspection Summary
12/28/2016 Letter Inspection Summary
12/29/2016 Letter Inspection Summary
01/09/2017 Letter Inspection Summary
01/10/2017 Letter Inspection Summary
01/11/2017 Letter Inspection Summary
01/13/2017 Letter Inspection Summary
01/17/2017 Letter Inspection Summary
01/19/2017 Letter Inspection Summary
01/25/2017 Letter Inspection Summary
01/27/2017 Letter Fire (Alarm) Plan Review Notice
01/30/2017 Letter Inspection Summary
01/30/2017 Letter Inspection Summary
02/01/2017 Letter Inspection Summary
02/06/2017 Letter Inspection Summary
02/09/2017 Letter Inspection Summary
02/10/2017 Letter Inspection Summary
02/11/2017 Letter Inspection Summary
02/14/2017 Letter Inspection Summary
02/17/2017 Letter Inspection Summary
02/17/2017 Letter Inspection Summary
02/28/2017 Letter Inspection Summary
03/02/2017 Letter Inspection Summary
03/06/2017 Letter Inspection Summary
03/07/2017 Letter Inspection Summary
03/09/2017 Letter Inspection Summary
03/14/2017 Letter Inspection Summary
03/17/2017 Letter Inspection Summary
03/23/2017 Letter Inspection Summary
03/27/2017 Code Mod Request Approved Code Modification Request
04/04/2017 Letter Inspection Summary
11/06/2018 Letter DOC110618-11062018110102
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home