Permit Application Status

PRCOM20162494


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20162494
Building Permit - Commercial
Final Completion
JOHN KNOX VILLAGE
NEW OTHER (COMMERCIAL)
ELECTRICAL FOR NORTH PARKING LOT
09/30/2016
09/30/2016
11/08/2016
Locations
Contacts
TORGESON ELECTRIC CO INC, Address:3545 SW 6TH AVE, Phone:(785) 233-2213 Ext:101  
PARIC CORPORATION , Address:77 WESTORT PLAZA STE 250, Phone:(636) 561-9795  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
CAPITAL ELECTRIC CONSTRUCTION INC, Address:PO BOX 410079, Phone:(913) 335-1214  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 09/30/2016 09/30/2016
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Other $0.00 $0.00 Paid 09/30/2016
$45.08
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underground Electrical Inspection - Commercial Partial 10/3/2016 10/03/2016
Misc
Partial Correction
10/03/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #2; #3; #6;
Underground Electrical Inspection - Commercial Partial 10/4/2016 10/4/2016 10/04/2016
Misc
Partial Correction
10/03/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #2; #3; #5;
Misc
Partial Correction
10/04/2016
GROUND RODS FOUND DRIVEN IN PLACE AND G.E.C. CAD-WELDED AT L.P. LOCATIONS: #2; #3; #5;
Misc
Partial Correction
10/04/2016
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE LIGHTING INTERCONNECTING L.P. LOCATIONS #1 THRU #7
Underground Electrical Inspection - Commercial Partial 10/18/2016 10/18/2016
Misc
Partial Correction
10/04/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #2; #3; #5; #1; #4; #6; #7
Misc
Partial Correction
10/04/2016
GROUND RODS FOUND DRIVEN IN PLACE: G.E.C. CAD-WELDED AT L.P. LOCATIONS #2; #3; #5. LISTED CLAMPS AT #1; #4; #6; #7
Misc
Partial Correction
10/04/2016
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE LIGHTING INTERCONNECTING L.P. LOCATIONS #1 THRU #7
Underground Electrical Inspection - Commercial Partial 10/27/2016 10/27/2016 10/27/2016
Misc
Partial Correction
10/18/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #2; #3; #5; #1; #4; #6; #7; #9; #10; #11;
Misc
Partial Correction
10/18/2016
GROUND RODS FOUND DRIVEN IN PLACE: G.E.C. CAD-WELDED AT L.P. LOCATIONS #2; #3; #5. LISTED CLAMPS AT #1; #4; #6; #7
Misc
Partial Correction
10/18/2016
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE LIGHTING INTERCONNECTING L.P. LOCATIONS #1 THRU #7
Underground Electrical Inspection - Commercial Partial 10/28/2016 10/28/2016 10/28/2016
Misc
Partial Correction
10/27/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #2; #3; #5; #1; #4; #6; #7; #9; #10; #11; #8; #12; #13;
Misc
Partial Correction
10/27/2016
GROUND RODS FOUND DRIVEN IN PLACE: G.E.C. CAD-WELDED AT L.P. LOCATIONS #2; #3; #5. LISTED CLAMPS AT #1; #4; #6; #7;
Misc
Partial Correction
10/27/2016
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE LIGHTING INTERCONNECTING L.P. LOCATIONS #1 THRU #7
Underground Electrical Inspection - Commercial Partial 10/31/2016 10/31/2016 10/31/2016
Misc
Partial Correction
10/28/2016
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE LIGHTING INTERCONNECTING L.P. LOCATIONS #1 THRU #7; #9 TO #10; #11 TO #12 TO #13;
Misc
Partial Correction
10/28/2016
GROUND RODS FOUND DRIVEN IN PLACE: G.E.C. CAD-WELDED AT L.P. LOCATIONS #2; #3; #5. LISTED CLAMPS AT #1; #4; #6; #7;
Misc
Partial Correction
10/28/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #2; #3; #5; #1; #4; #6; #7; #9; #10; #11; #8; #12; #13;
Underground Electrical Inspection - Commercial Partial 10/31/2016 10/31/2016 10/31/2016
Misc
Partial Correction
10/31/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #2; #3; #5; #1; #4; #6; #7; #9; #10; #11; #8; #12; #13;
Misc
Partial Correction
10/31/2016
GROUND RODS FOUND DRIVEN IN PLACE: G.E.C. CAD-WELDED AT L.P. LOCATIONS #2; #3; #5. LISTED CLAMPS AT #1; #4; #6; #7;
Misc
Partial Correction
10/31/2016
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE LIGHTING INTERCONNECTING L.P. LOCATIONS #1 THRU #7; #9 TO #10; #11 TO #12 TO #13; #8 TO #9; #10 TO #11;
Final Electrical Inspection - Commercial Passed 11/8/2016 11/08/2016
Underground Electrical Inspection - Commercial Passed 11/8/2016 11/08/2016
Misc
Resolved
11/08/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #2; #3; #5; #1; #4; #6; #7; #9; #10; #11; #8; #12; #13;
Misc
Resolved
11/08/2016
GROUND RODS FOUND DRIVEN IN PLACE: G.E.C. CAD-WELDED AT L.P. LOCATIONS #2; #3; #5. LISTED CLAMPS AT #1; #4; #6; #7;
Misc
Resolved
11/08/2016
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE LIGHTING INTERCONNECTING L.P. LOCATIONS #1 THRU #7; #9 TO #10; #11 TO #12 TO #13; #8 TO #9; #10 TO #11;
Documents & Images
Date Uploaded File Type Document Name
09/30/2016 Letter Codes Plan Review Conditions
09/30/2016 Letter Codes Building Permit
10/04/2016 Letter Inspection Summary
10/18/2016 Letter Inspection Summary
10/27/2016 Letter Inspection Summary
10/28/2016 Letter Inspection Summary
10/31/2016 Letter Inspection Summary
10/31/2016 Letter Inspection Summary
11/08/2016 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home