Review Type |
Outcome |
Est. Completion Date |
Completed |
Alarm Plan Review
|
Released for Construction
|
|
12/31/2016
|
|
Joe Dir
|
|
|
Sprinkler Plan Review
|
Released for Construction
|
|
12/31/2016
|
|
Joe Dir
|
|
|
Building Plan Review
|
Approved with Conditions
|
10/07/2016
|
10/03/2016
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
Accessibility requirements.
Action required: Approval is contingent upon upgrading site as much as practical to current accessibility requirements without having to move existing walls. i.e. provide/perform the following:
- Door to restroom must swing inward into room.
- Provide fully supported side and rear grab bars at toilet.
- Protect piping under restroom sink from contact.
10/3/16 - these items to be field verified
|
|
Plumb - Drinking fountain substitution 410.3
2012 IPC 410.3 – Substitution. Where restaurants provide drinking water in a container free of charge, drinking fountains shall not be required in those restaurants. In other occupancies, where drinking fountains are required, water coolers, bottled water dispensers or break rooms with a kitchen sink shall be permitted to be substituted for the required drinking fountains. (As amended by the City of Lee’s Summit.)
Action required: Provide drinking fountain or provide letter agreeing to provide in one of the methods listed.
10/3/16 - business owner has agreed via email to provide water to patrons
|
|
|
Fire Plan Review
|
Approved with Conditions
|
10/07/2016
|
10/03/2016
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
ALL EXISTING EXIT AND EMERGENCY LIGHTS SHALL ILLUMINATE ON BOTH AC AND DC POWER.
(VERIFIED AT INSPECTION)
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF 3455 ON THE EXTERIOR OF THE FRONT AND REAR DOORS READABLE FROM THE ROADWAY, IN A CONTRASTING COLOR TO THE BACKGROUND.
(VERIFIED AT INSPECTION)
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL REQUIRED SERVICE/MAINTENANCE WITH A CURRENT SERVICE TAG POSTED ON THE RISER.
(VERIFIED AT INSPECTION)
|
|
Portable fire extinguishers - general
Corrective Action Required
2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
PPROVIDE ONE 2A-10BC FIRE EXTINGUISHER IF NOT ALREADY EXISTING. MOUNT CLOSE TO AN EXIT WITH A MAXIMUM TRAVEL DISTANCE OF 75'
(VERIFIED AT INSPECTION)
|
|
|
Licensed Contractors
|
Approved
|
09/30/2016
|
10/03/2016
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved with Conditions
|
09/30/2016
|
09/21/2016
|
|
Joe Dir
|
|
Misc
Corrective Action Required
ALL EXISTING EXIT AND EMERGENCY LIGHTS SHALL ILLUMINATE ON BOTH AC AND DC POWER.
(VERIFIED AT INSPECTION)
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF 3455 ON THE EXTERIOR OF THE FRONT AND REAR DOORS READABLE FROM THE ROADWAY, IN A CONTRASTING COLOR TO THE BACKGROUND.
(VERIFIED AT INSPECTION)
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL REQUIRED SERVICE/MAINTENANCE WITH A CURRENT SERVICE TAG POSTED ON THE RISER.
(VERIFIED AT INSPECTION)
|
|
Portable fire extinguishers - general
Corrective Action Required
2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
PPROVIDE ONE 2A-10BC FIRE EXTINGUISHER IF NOT ALREADY EXISTING. MOUNT CLOSE TO AN EXIT WITH A MAXIMUM TRAVEL DISTANCE OF 75'
(VERIFIED AT INSPECTION)
|
|
|
Building Plan Review
|
Rejected
|
09/30/2016
|
09/20/2016
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
Accessibility requirements.
Action required: Approval is contingent upon upgrading site as much as practical to current accessibility requirements without having to move existing walls. i.e. provide/perform the following:
- Door to restroom must swing inward into room.
- Provide fully supported side and rear grab bars at toilet.
- Protect piping under restroom sink from contact.
|
|
Plumb - Drinking fountain substitution 410.3
Corrective Action Required
2012 IPC 410.3 – Substitution. Where restaurants provide drinking water in a container free of charge, drinking fountains shall not be required in those restaurants. In other occupancies, where drinking fountains are required, water coolers, bottled water dispensers or break rooms with a kitchen sink shall be permitted to be substituted for the required drinking fountains. (As amended by the City of Lee’s Summit.)
Action required: Provide drinking fountain or provide letter agreeing to provide in one of the methods listed.
|
|
|
Licensed Contractors
|
Approved
|
09/30/2016
|
09/20/2016
|
|
Joe Frogge
|
|
|