Permit Application Status

PRCOM20162031


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20162031
Building Permit - Commercial
Certificate of Occupancy
FORT WAYNE MATADOR INC
CHANGE OF TENANT
CHANGE OF TENANT FOR NEW SALES AND FRAMING OF ART *plans are in plan review file
08/12/2016
08/16/2016
09/21/2016
Locations
Contacts
CONSTRUCTION MASTERS INC, Address:14243 W 121ST STREET, Phone:(913) 782-1064  
G.J. ELECTRIC, Address:1511 DOC HENRY RD, Phone:(816) 537-3094  
LISBONA ARCHITECTS, Address:P O BOX 860905, Phone:(913) 390-1112  
FORT WAYNE MATADOR INC, Address:185 NW SPANISH RIVER BLVD STE 100  
Summit Development Co, Address:700 W 47th St Ste 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/31/2016
Joe Dir
Sprinkler Plan Review Released for Construction 08/24/2016 08/26/2016
Joe Dir
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
08/26/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL OF THE REQUIRED SERVICE/MAINTENANCE FOR THE SYSTEM. A CURRENT SERVICE TAG SHALL BE POSTED ON THE SYSTEM RISER. (VERIFIED AT INSPECTION)
Fire Plan Review Approved with Conditions 08/24/2016 08/16/2016
Joe Dir
Misc
Corrective Action Required
08/16/2016

CHECK AND ASSURE EXISTING EXIT AND EMERGENCY LIGHTING IS IN PROPER WORKING ORDER. (VERIFIED AT INSPECTION)
Construction documents for fire alarm systems
Corrective Action Required
08/16/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE ALARM DEVICES IN THE SUITE.
Address numbers required
Corrective Action Required
08/16/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 107 ON THE EXTERIOR OF THE FRONT AND REAR DOORS IN A CONTRASTING COLOR OF THE BACK GROUND. READABLE FROM THE ROADWAY. (VERIIFED AT INSPECTION)
Construction documents - Fire protection systems
Corrective Action Required
08/16/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
08/16/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ANY REQUIRED ANNUAL SERVICE/MAINTENANCE NEEDED FOR THE SYSTEM WITH A CURRENT SERVICE TAG ON THE SPRINKLER RISER. (VERIIFED AT INSPECTION)
Portable fire extinguishers - general
Corrective Action Required
08/16/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE A MINIMUM OF ONE 2A-10BC FIRE EXTINGUISHER.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/16/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT THE FIRE EXTINGUISHER(S) IN A NORMAL PATH OF TRAVEL CLOSE TO AN EXIT WITH A MAXIMUM TRAVEL DISTANCE OF 75' FROM ANY WHERE WITHIN THE SUITE. TOP OF EXTINGUISHER SHALL NOT BE ANY HIGHER THAN 60" OFF OF FINISH FLOOR. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
08/16/2016

NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT.
Building Plan Review Approved with Conditions 08/24/2016 08/15/2016
Joe Frogge
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Corrective Action Required
08/15/2016

2012 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Service counter to meet accessibility requirements. To be field verified.
Misc
Corrective Action Required
08/15/2016

2012 IPC 403.3.1 Access. The route to the public toilet facilities required by Section 403.3 shall not pass through kitchens, storage rooms or closets. Access to the required facilities shall be from within the building or from the exterior of the building. All routes shall comply with the accessibility requirements of the International Building Code. The public shall have access to the required toilet facilities at all times that the building is occupied. Action required: Comment is for informational purposes.
Licensed Contractors Approved 08/24/2016 08/12/2016
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $108.13 $108.13 Paid 08/16/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 8/23/2016 8/23/2016 08/23/2016
Occupancy Inspection - Fire Passed 9/16/2016 09/16/2016
Occupancy Inspection - Codes Commercial Temporary C of O 9/16/2016 9/16/2016 09/16/2016
Misc
Corrective Action Required
09/16/2016
-INSTALL GRAB BARS FOR RESTROOM -LABEL ELECTRIC PANEL ****FIRE DEPARTMENT APPROVED****
Occupancy Inspection - Codes Commercial Full C of O 9/21/2016 9/21/2016 09/21/2016
Misc
Resolved
09/21/2016
-INSTALL GRAB BARS FOR RESTROOM -LABEL ELECTRIC PANEL ****FIRE DEPARTMENT APPROVED****
Documents & Images
Date Uploaded File Type Document Name
08/16/2016 Letter Fire Building Plan Review
08/16/2016 Letter Codes Plan Review Conditions
08/16/2016 Receipt Receipt for transaction: 2016-005487
08/16/2016 Letter Codes Building Permit
08/23/2016 Letter Inspection Summary
08/26/2016 Letter Fire (Sprinkler) Plan Review
09/21/2016 Letter Field Certificate of Occupancy
09/22/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home