Permit Application Status

PRCOM20161245


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20161245
Building Permit - Commercial
Certificate of Occupancy
HY VEE FOOD STORES INC
ALTERATION COMMERCIAL
HYVEE WEST - INTERIOR ALTERATIONS TO EXISTING GROCERY STORE - MODIFY CAFETERIA INTO RESTAURANT AND BUILD MEDICAL CLINIC
05/31/2016
07/05/2016
04/16/2017
08/17/2017
Locations
Contacts
CHIEF HEATING & COOLING INC, Address:920 NW TECHNOLOGY DR, Phone:(816) 246-4646  
R F FISHER ELECTRIC COMPANY LLC, Address:5299 DTC BLVD STE 600, Phone:(913) 384-1500  
RODRIGUEZ MECHANICAL CONTRACTORS INC, Address:541 S 11TH ST, Phone:(913) 281-1814  
BURNS & MCDONNELL ENGINEERING COMPANY INC, Address:9400 WARD PARKWAY, Phone:(816) 333-9400  
HY VEE FOOD STORES INC, Address:5820 WESTOWN PKWY  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/31/2016
Joe Dir
Sprinkler Plan Review Released for Construction 10/10/2016
Joe Dir
Fire Plan Review Approved with Conditions 06/23/2016 09/26/2016
Joe Dir
Misc
Corrective Action Required
09/26/2016

LOCKS:[B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT.
Posting of occupant load
Corrective Action Required
09/26/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. POST THE OCCUPANT LOAD FOR THE MARKET GRILL AND THE CASUAL DINING AREAS AS PER PLANS.
Type I hood - Where required
Corrective Action Required
09/26/2016

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. PROVIDE INFORMATION ABOUT A NEW OR EXSITING TYPE-1 KITCHEN HOOD AND FIRE SUPRESSION SYSTEM THAT WILL NEWLY INSTALLED OT RELOCATED.
Construction documents - Fire protection systems
Corrective Action Required
09/26/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE MANUFACTURES SPECS ON THE NEW FIRE SUPRESSION SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
09/26/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF THE KITCHEN HOODS FIRE SUPRESSION SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. COORDINATE THE TESTING WITH THE FIRE SPRINKLER AND FIRE ALARMS SYSTEMS. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT @ 816-969-1300.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
09/26/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ALL EXSITING HOOD SYSTEMS WILL NEED TO BE CURRENT WITH THE REQUIRED 6 MONTH SERVICE/MAINTENANCE.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
09/26/2016

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. PROVIDE A K-CLASS FIRE EXTINGUISHER FOR THE KITCHEN AREA.
Misc
Corrective Action Required
09/26/2016

PROVIDE A METAL CAN WITH A LID TO DEPOSIT ANY ASH / DEBRIS FROM THE SMOKER.
Misc
Corrective Action Required
09/26/2016

THE TYPE 1 EXHAUST DUCT NEEDS TO BE ENCLOSED IN 1 HOUR FIRE RATED WRAP MATERIAL.
Sprinkler Plan Review Released for Construction 07/25/2016
Joe Dir
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
07/25/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXSISTING FIRE SPRINKLER SYSTEM RISER SHALL BE CURRENT WITH THE REQUIRED ANNUAL MAINTENANACE/SERVICE WITH A CURRENT SERVICE TAG ON THE RISER. (verified at inspection)
Building Plan Review Approved with Conditions 06/23/2016 06/29/2016
Joe Frogge
License Tax Application
Corrective Action Required
06/16/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 6/16/16 - acknowledged in letter
Health Dept Review
Resolved
09/27/2016

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 6/16/16 - acknowledged in letter - not yet received 9/26/16 - new approval required due to addition to food prep area
Health Dept Inspection
Corrective Action Required
06/16/2016

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 6/16/16 - acknowledged in letter
Misc
Resolved
06/16/2016

2012 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update references. This building is a Type IIIB.
Bldg - Occupant load posting 1004.3
Corrective Action Required
06/16/2016

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. To be field verified. 6/16/16 - acknowledged in letter
Bldg - Emergency power for illumination 1006.3
Corrective Action Required
06/16/2016

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide emergency lighting at exterior side of dining room exit. 6/16/16 - acknowledged in letter - to be field verified
Misc
Corrective Action Required
06/16/2016

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles. 2. Metal Boxes and enclosures containing receptacles. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system. 6/16/16 - acknowledged in letter - approved contingent upon MC cable being routed uninterrupted back to panel. Field verify.
Misc
Resolved
06/16/2016

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle within 25' of new roof mounted HP-1. 6/16/16 - acknowledged in letter
Misc
Corrective Action Required
09/26/2016

Adjusted fee requirement. Action required: General Contractor must pay addition $120.00 due to addition of 4 plumbing traps
Misc
Resolved
09/30/2016

Additional information required. Action required: Provide the following: - Where does new a/c unit condensate piping terminate? - Provide verification that UL listing for new a/c unit includes approval for commercial use.
Health Department Review Approved 06/29/2016
Joe Frogge
Licensed Contractors Approved 06/16/2016 06/29/2016
Joe Frogge
LC - General Contractor
Resolved
06/16/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
06/29/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 06/23/2016 06/17/2016
Joe Dir
Misc
Corrective Action Required
06/16/2016

LOCKS:[B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT.
Posting of occupant load
Corrective Action Required
06/16/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. POST THE OCCUPANT LOAD FOR THE MARKET GRILL AND THE CASUAL DINING AREAS AS PER PLANS.
Type I hood - Where required
Corrective Action Required
06/16/2016

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. PROVIDE INFORMATION ABOUT A NEW OR EXSITING TYPE-1 KITCHEN HOOD AND FIRE SUPRESSION SYSTEM THAT WILL NEWLY INSTALLED OR RELOCATED.
Construction documents - Fire protection systems
Corrective Action Required
06/16/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE MANUFACTURES SPECS ON THE NEW FIRE SUPRESSION SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
06/16/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF THE KITCHEN HOODS FIRE SUPRESSION SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. COORDINATE THE TESTING WITH THE FIRE SPRINKLER AND FIRE ALARMS SYSTEMS. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT @ 816-969-1300.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
06/16/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ALL EXSITING HOOD SYSTEMS WILL NEED TO BE CURRENT WITH THE REQUIRED 6 MONTH SERVICE/MAINTENANCE.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
06/16/2016

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. PROVIDE A K-CLASS FIRE EXTINGUISHER FOR THE KITCHEN AREA.
Misc
Corrective Action Required
06/16/2016

PROVIDE A METAL CAN WITH A LID TO DEPOSIT ANY ASH / DEBRIS FROM THE SMOKER.
Misc
Corrective Action Required
06/16/2016

THE TYPE 1 EXHAUST DUCT NEEDS TO BE ENCLOSED IN 1 HOUR FIRE RATED WRAP MATERIAL OR 1 HOUR RATED ENCLOSURE.
Building Plan Review Rejected 06/10/2016 06/09/2016
Joe Frogge
License Tax Application
Corrective Action Required
06/09/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Corrective Action Required
06/09/2016

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
06/09/2016

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
06/09/2016

2012 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update references. This building is a Type IIIB.
Bldg - Occupant load posting 1004.3
Corrective Action Required
06/09/2016

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. To be field verified.
Bldg - Emergency power for illumination 1006.3
Corrective Action Required
06/09/2016

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide emergency lighting at exterior side of dining room exit.
Misc
Corrective Action Required
06/09/2016

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles. 2. Metal Boxes and enclosures containing receptacles. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
Misc
Corrective Action Required
06/09/2016

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle within 25' of new roof mounted HP-1.
Licensed Contractors Rejected 06/10/2016 06/09/2016
Joe Frogge
LC - General Contractor
Corrective Action Required
06/09/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
06/09/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 06/10/2016 06/03/2016
Joe Dir
Misc
Corrective Action Required
06/03/2016

LOCKS:[B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT.
Posting of occupant load
Corrective Action Required
06/03/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. POST THE OCCUPANT LOAD FOR THE MARKET GRILL AND THE CASUAL DINING AREAS AS PER PLANS.
Type I hood - Where required
Corrective Action Required
06/03/2016

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. PROVIDE INFORMATION ABOUT A NEW OR EXSITING TYPE-1 KITCHEN HOOD AND FIRE SUPRESSION SYSTEM THAT WILL NEWLY INSTALLED OT RELOCATED.
Construction documents - Fire protection systems
Corrective Action Required
06/03/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE MANUFACTURES SPECS ON THE NEW FIRE SUPRESSION SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
06/03/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF THE KITCHEN HOODS FIRE SUPRESSION SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. COORDINATE THE TESTING WITH THE FIRE SPRINKLER AND FIRE ALARMS SYSTEMS. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT @ 816-969-1300.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
06/03/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ALL EXSITING HOOD SYSTEMS WILL NEED TO BE CURRENT WITH THE REQUIRED 6 MONTH SERVICE/MAINTENANCE.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
06/03/2016

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. PROVIDE A K-CLASS FIRE EXTINGUISHER FOR THE KITCHEN AREA.
Misc
Corrective Action Required
06/03/2016

PROVIDE A METAL CAN WITH A LID TO DEPOSIT ANY ASH / DEBRIS FORM THE SMOKER.
Misc
Corrective Action Required
06/03/2016

THE TYPE 1 EXHAUST DUCT NEEDS TO BE ENCLOSED IN 1 HOUR FIRE RATED WRAP MATERIAL.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $2,310.63 $2,310.63 Paid 07/05/2016
8331507-Sewer Connection Fee $450.00 $450.00 Paid 07/05/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 7/15/2016 7/15/2016 07/15/2016
Misc
Corrective Action Required
07/15/2016
PARTAIL- FLOOR DRAIN TO FLORAL.
Underslab Plumbing Inspection - Commercial Partial 7/19/2016 7/19/2016 07/19/2016
Misc
Corrective Action Required
07/15/2016
PARTAIL- FLOOR DRAIN TO FLORAL. -BATH GROUP FOR THE GRILLE
Underslab Plumbing Inspection - Commercial Partial 7/21/2016 7/21/2016 07/21/2016
Misc
Corrective Action Required
07/19/2016
PARTAIL- FLOOR DRAIN TO FLORAL. -BATH GROUP FOR THE GRILLE -SALAD BAR DRAIN
In-wall Inspection Partial 7/28/2016 7/28/2016 07/28/2016
Misc
Partial Correction
07/28/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: NEW ENTRANCE VESTIBULE; FLORAL SHOP;
Underslab Plumbing Inspection - Commercial Partial 7/28/2016 7/28/2016 07/28/2016
Misc
Partial Correction
07/28/2016
PARTAIL- FLOOR DRAIN TO FLORAL. -BATH GROUP FOR THE GRILLE -SALAD BAR DRAIN - CLINIC PER 1/A3.7A
Underslab Plumbing Inspection - Commercial Partial 8/4/2016 8/4/2016 08/04/2016
Misc
Partial Correction
07/28/2016
PARTAIL- FLOOR DRAIN TO FLORAL. -BATH GROUP FOR THE GRILLE -SALAD BAR DRAIN - CLINIC PER 1/A3.7A -GRILLE SINKS AND MAIN 4"/
In-wall Inspection Partial 8/4/2016 8/4/2016 08/04/2016
Misc
Partial Correction
07/28/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: NEW ENTRANCE VESTIBULE; FLORAL SHOP; TALL WALL SOUTH OF ENTRY;
Underslab Plumbing Inspection - Commercial Passed 8/5/2016 8/5/2016 08/05/2016
Misc
Resolved
08/05/2016
PARTAIL- FLOOR DRAIN TO FLORAL. -BATH GROUP FOR THE GRILLE -SALAD BAR DRAIN - CLINIC PER 1/A3.7A -GRILLE SINKS AND MAIN 4"/
Above Ceiling Inspection Partial 8/5/2016 8/5/2016 08/05/2016
Misc
Corrective Action Required
08/05/2016
AREA OVER FRONT ENTRY-PARTAIL NEED TO INSTALL 3 SUPPLY VENTS. -INSIDE ENTRY,INCOMPLETE CEILING AND ELECTRICAL. RECALL FOR MONDAY
Above Ceiling Inspection Partial 8/8/2016 8/8/2016 08/08/2016
Misc
Corrective Action Required
08/05/2016
AREA OVER FRONT ENTRY-PARTAIL NEED TO INSTALL 3 SUPPLY VENTS. -INSIDE ENTRY,INCOMPLETE CEILING AND ELECTRICAL. 2 open boxes over south entry, electrician to complete.
In-wall Inspection Partial 8/17/2016 08/17/2016
Misc
Partial Correction
08/04/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: NEW ENTRANCE VESTIBULE; FLORAL SHOP; TALL WALL SOUTH OF ENTRY; --minute clinicwall rough: install protectionplatesat plumbing ok to rock walls with out plumbing
In-wall Inspection Partial 8/18/2016 08/18/2016
Misc
Partial Correction
08/17/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: NEW ENTRANCE VESTIBULE; FLORAL SHOP; TALL WALL SOUTH OF ENTRY; --minute clinicwall rough:ok
In-wall Inspection Partial 8/24/2016 08/24/2016
Misc
Partial Correction
08/18/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: NEW ENTRANCE VESTIBULE; FLORAL SHOP; TALL WALL SOUTH OF ENTRY; --minute clinicwall rough:ok --DEMISING WALL BETWEEN MARKET GRILL AND CASUAL DINNING. --BATHROOM GROUP WALLS FOR MARKET GRILL.
In-wall Inspection Partial 9/1/2016 9/1/2016 09/01/2016
Misc
Partial Correction
08/24/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: NEW ENTRANCE VESTIBULE; FLORAL SHOP; TALL WALL SOUTH OF ENTRY; --minute clinicwall rough:ok --DEMISING WALL BETWEEN MARKET GRILL AND CASUAL DINNING. --BATHROOM GROUP WALLS FOR MARKET GRILL. --1/2 WALL
Above Ceiling Inspection Partial 9/8/2016 9/8/2016 09/08/2016
Misc
Corrective Action Required
08/08/2016
STL CLINIC- CHECK BATH FAN AND CURCUIT TO HVAC, OK TO DROP TILE . LEAVEAREA OPEN FOR INSPECTION AT FINAL OR BEFORE.
Alarm Test Passed 9/13/2016 09/13/2016
Occupancy Inspection - Fire Passed 9/13/2016 09/13/2016
Occupancy Inspection - Codes Commercial Failed 9/13/2016 9/14/2016 09/15/2016
Misc
Corrective Action Required
09/14/2016
All areas are under one permit. Status of permit will show failed untill Market Grill is complete and ready for C of O. :Final for Saint Lukes Convenient Care is approved to Occupy. :Revised Casual Dining- ok to occupy pending completion of drink station.
Rough Electrical Inspection - Commercial Passed 9/22/2016 09/22/2016
Rough Plumbing Inspection - Commercial Passed 9/22/2016 09/22/2016
In-wall Inspection Partial 9/22/2016 09/22/2016
Misc
Partial Correction
09/01/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: NEW ENTRANCE VESTIBULE; FLORAL SHOP; TALL WALL SOUTH OF ENTRY; --minute clinicwall rough:ok --DEMISING WALL BETWEEN MARKET GRILL AND CASUAL DINNING. --BATHROOM GROUP WALLS FOR MARKET GRILL. --1/2 WALL --1/2 serving station wall.
In-wall Inspection Passed 9/27/2016 9/27/2016 09/27/2016
Misc
Resolved
09/27/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: NEW ENTRANCE VESTIBULE; FLORAL SHOP; TALL WALL SOUTH OF ENTRY; --minute clinicwall rough:ok --DEMISING WALL BETWEEN MARKET GRILL AND CASUAL DINNING. --BATHROOM GROUP WALLS FOR MARKET GRILL. --1/2 WALL --1/2 serving station wall.
Above Ceiling Inspection Partial 9/30/2016 9/30/2016 09/30/2016
Misc
Corrective Action Required
09/08/2016
CLINIC APPROVED MARKET GRILL- ONLY REMAINING AREA IS EXISTING KITCHEN AND STORE TIE IN CEILING AREAS.
Occupancy Inspection - Codes Commercial Failed 10/4/2016 10/4/2016 10/04/2016
Misc
Corrective Action Required
09/15/2016
MARKET GRILLE- PRE-FINAL-- COMPLETE ELECTRICAL SOUTH WALL INSTALLCOVER PLATES AT CEILING BOXESEATING AREA TIE IN CEILING FROM STORE AREA. LOAD SIGN PENDING FIRE INSPECTION ( COMPLETE NEW ENTRANCE TO N.E. CORNER)
Occupancy Inspection - Fire Temporary C of O 10/04/2016
Alarm Test Passed 10/04/2016
Occupancy Inspection - Codes Commercial Temporary C of O 10/6/2016 10/06/2016
Misc
Corrective Action Required
10/04/2016
MARKET GRILLE CODES APPROVED FOR TCO . FIRE DEPARTMENT APPROVED FOR TCO. ( COMPLETE NEW ENTRANCE TO N.E. CORNER) ST LUKES MINUTE CLINIC APPROVED. FLORAL WALLS APPROVED.
Underslab Plumbing Inspection - Commercial Partial 10/18/2016 10/18/2016 10/18/2016
Misc
Corrective Action Required
10/18/2016
partail for rear produce area. ok to cover
In-wall Inspection Passed 10/20/2016 10/20/2016 10/20/2016
Underslab Plumbing Inspection - Commercial Passed 8/5/2016 02/02/2017
Misc
Corrective Action Required
10/18/2016
partail for rear produce area. ok to cover
Occupancy Inspection - Codes Commercial Full C of O 8/17/2017 at 10:30 AM 08/17/2017
Misc
Resolved
08/17/2017
MARKET GRILLE CODES APPROVED FOR TCO . FIRE DEPARTMENT APPROVED FOR TCO. ( COMPLETE NEW ENTRANCE TO N.E. CORNER) ST LUKES MINUTE CLINIC APPROVED. FLORAL WALLS APPROVED.
Above Ceiling Inspection Passed 08/17/2017
Misc
Resolved
08/17/2017
CLINIC APPROVED MARKET GRILL- ONLY REMAINING AREA IS EXISTING KITCHEN AND STORE TIE IN CEILING AREAS.
Documents & Images
Date Uploaded File Type Document Name
06/03/2016 Letter Fire Building Plan Review
06/09/2016 Letter Codes P/R Corrections Document
06/17/2016 Letter Fire Building Plan Review
07/05/2016 Letter Codes Plan Review Conditions
07/05/2016 Receipt Receipt for transaction: 2016-004518
07/05/2016 Letter Codes Building Permit
07/15/2016 Letter Inspection Summary
07/19/2016 Letter Inspection Summary
07/21/2016 Letter Inspection Summary
07/25/2016 Letter Fire (Sprinkler) Plan Review
07/28/2016 Letter Inspection Summary
08/04/2016 Letter Inspection Summary
08/05/2016 Letter Inspection Summary
08/08/2016 Letter Inspection Summary
08/17/2016 Letter Inspection Summary
08/18/2016 Letter Inspection Summary
08/24/2016 Letter Inspection Summary
09/01/2016 Letter Inspection Summary
09/08/2016 Letter Inspection Summary
09/15/2016 Letter Inspection Summary
09/22/2016 Letter Inspection Summary
09/26/2016 Letter Fire Building Plan Review
09/26/2016 Letter Codes Plan Review Conditions
09/27/2016 Letter Inspection Summary
09/30/2016 Letter Inspection Summary
10/06/2016 Letter Codes Temporary Certificate of Occupancy
10/10/2016 Letter Fire (Sprinkler) Plan Review
10/18/2016 Letter Inspection Summary
10/20/2016 Letter Inspection Summary
08/17/2017 Letter Codes Final Certificate of Occupancy
08/18/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home