Permit Application Status

PRCOM20161080


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20161080
Building Permit - Commercial
Final Completion
EXPRESSIONS INVESTMENT LLC
CHANGE OF TENANT
DENTAL OFFICE IS GROWING INTO ADJACENT SUITE SUITES B & C BECOME JUST B
05/10/2016
08/03/2016
12/09/2016
Locations
Contacts
SRKO LLC, Address:24 NW CHIPMAN RD, Phone:(816) 365-0100  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
WINDSOR ELECTRIC INC, Address:PO BOX 821, Phone:(913) 709-8893  
A & E PLUMBING CONTRACTORS LLC, Address:15917 W 82ND PL, Phone:(913) 231-8639  
BRUCE BEST, Phone:(816) 525-8918  
EXPRESSIONS INVESTMENT LLC, Address:5007 W 147TH ST  
WILDCAT CONSTRUCTION, Address:106 E 63RD ST, Phone:(816) 807-2228  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 05/20/2016 08/05/2016
Joe Dir
Misc
Corrective Action Required
08/05/2016

PROPER LABELING OF ALL ROOMS THAT MAY CONTAIN MED GAS, RADIATION, BIO-HAZARDS WILL HAVE THE PROPER LABELS AND WARNING SIGNAGE POSTED ON DOORS OF OR NEAR THE AREAS OF HAZARD.
Misc
Corrective Action Required
08/05/2016

MED GAS PIPING: HAVE MED GAS PROVIDER PROVIDE A CERIFICATION OF A PASSED MED GAS LINE TEST.
Portable fire extinguishers - general
Corrective Action Required
08/05/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE FIRE EXTINGUISHER ACCORDING TO THE PLANS.
Address numbers required
Corrective Action Required
08/05/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). CONFIRM THAT THERE WILL BE A READBLE NUMERIC ADDRESS OF 521 FROM 2ND STREET. AND ANY SUITE DESIGNATIONS WILL BE POSTED ON ALL DOORS IN THE CORRIDORS LEADING INTO THE SUITE.
Misc
Corrective Action Required
08/05/2016

SECTION 5306 MEDICAL GAS SYSTEMS: 5306.1 General. Compressed gases at hospitals and similar facilities intended for inhalation or sedation including, but not limited to, analgesia systems for dentistry, podiatry, veterinary and similar uses shall comply with Sections 5306.2 through 5306.4 in addition to other requirements of this chapter. 5306.2 Interior supply location. Medical gases shall be stored in areas dedicated to the storage of such gases without other storage or uses. Where containers of medical gases in quantities greater than the permit amount are located inside buildings, they shall be in a 1-hour exterior room, a 1-hour interior room or a gas cabinet in accordance with Section 5306.2.1, 5306.2.2 or 5306.2.3, respectively. Rooms or areas where medical gases are stored or used in quantities exceeding the maximum allowable quantity per control area as set forth in Section 5003.1 shall be in accordance with the International Building Code for high-hazard Group H occupancies. IF THE ONE HOUR RATED SHAFT IS NOT BUILT THEN THE DUCT CAN BE WRAPPED IN A UL APPROVED 1 HOUR FIRE WRAP PRODUCT. MANUFACTURES SPECS SHALL BE PROVIDED FOR APPROVAL. 5306.4 Medical gas systems. Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. A] 105.6.8 Compressed gases. An operational permit is required for the storage, use or handling at normal temperature and pressure (NTP) of compressed gases in excess of the amounts listed in Table 105.6.8. OXIDIZERS STORAGE LIMITED TO 504 CUFT NTP IN A STORAGE ROOM, THAT WILL INCLUDE ANY EMPTY OR IDLE CYLINDERS.
Building Plan Review Approved with Conditions 05/20/2016 05/13/2016
Joe Frogge
Misc
Corrective Action Required
05/13/2016

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1.The grounding terminals of all receptacles. 2.Metal Boxes and enclosures containing receptacles. 3.All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2)Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Comment is for informational purposes. Patient exam room wiring is noted to use HCF conduits. It is assumed that the intent of the HCF wiring and conduits is to meet requirements of code section noted. To be field verified.
Fire Plan Review Approved with Conditions 05/20/2016 05/12/2016
Joe Dir
08/05/2016

Misc
Corrective Action Required
05/12/2016

SECTION 5306 MEDICAL GAS SYSTEMS: 5306.1 General. Compressed gases at hospitals and similar facilities intended for inhalation or sedation including, but not limited to, analgesia systems for dentistry, podiatry, veterinary and similar uses shall comply with Sections 5306.2 through 5306.4 in addition to other requirements of this chapter. 5306.2 Interior supply location. Medical gases shall be stored in areas dedicated to the storage of such gases without other storage or uses. Where containers of medical gases in quantities greater than the permit amount are located inside buildings, they shall be in a 1-hour exterior room, a 1-hour interior room or a gas cabinet in accordance with Section 5306.2.1, 5306.2.2 or 5306.2.3, respectively. Rooms or areas where medical gases are stored or used in quantities exceeding the maximum allowable quantity per control area as set forth in Section 5003.1 shall be in accordance with the International Building Code for high-hazard Group H occupancies. IF THE ONE HOUR RATED SHAFT IS NOT BUILT THEN THE DUCT CAN BE WRAPPED IN A UL APPROVED 1 HOUR FIRE WRAP PRODUCT. MANUFACTURES SPECS SHALL BE PROVIDED FOR APPROVAL. 5306.4 Medical gas systems. Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. A] 105.6.8 Compressed gases. An operational permit is required for the storage, use or handling at normal temperature and pressure (NTP) of compressed gases in excess of the amounts listed in Table 105.6.8. OXIDIZERS STORAGE LIMITED TO 504 CUFT NTP IN A STORAGE ROOM, THAT WILL INCLUDE ANY EMPTY OR IDLE CYLINDERS.
Address numbers required
Corrective Action Required
05/12/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). CONFIRM THAT THERE WILL BE A READBLE NUMERIC ADDRESS OF 521 FROM 2ND STREET. AND ANY SUITE DESIGNATIONS WILL BE POSTED ON ALL DOORS IN THE CORRIDORS LEADING INTO THE SUITE.
Portable fire extinguishers - general
Corrective Action Required
05/12/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE FIRE EXTINGUISHER ACCORDING TO THE PLANS.
Misc
Corrective Action Required
05/12/2016

MED GAS PIPING: HAVE MED GAS PROVIDER PROVIDE A CERIFICATION OF A PASSED MED GAS LINE TEST.
Misc
Corrective Action Required
05/12/2016

PROPER LABELING OF ALL ROOMS THAT MAY CONTAIN MED GAS, RADIATION, BIO-HAZARDS WILL HAVE THE PROPER LABELS AND WARNING SIGNAGE POSTED ON DOORS OF OR NEAR THE AREAS OF HAZARD.
Licensed Contractors Approved 05/20/2016 05/10/2016
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $212.42 $212.42 Paid 08/03/2016
8331507-Sewer Connection Fee $90.00 $90.00 Paid 08/03/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 8/15/2016 08/15/2016
In-wall Inspection Failed 9/13/2016 09/13/2016
Misc
Corrective Action Required
09/13/2016
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER.
Misc
Corrective Action Required
09/13/2016
IPC 305 PROTECTION OF COPPER PIPING AT PENETRATION OF STEEL FRAMING MEMBERS: INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL. SEE NITROUS OXIDE AND OXYGEN PIPING ONE LOCATION.
Misc
Corrective Action Required
09/13/2016
HOLE NOT CUT FOR ONE ELECT RECEPTACLE BOX.
Misc
Corrective Action Required
09/13/2016
ENSURE STEEL BOCA PLATES ARE NOT IN CONTACT WITH COPPER WATER PIPE -- DISSIMILAR METALS
Above Ceiling Inspection Not Ready 9/13/2016 09/13/2016
Misc
Corrective Action Required
09/13/2016
COMPLETE ALL WORK ABOVE CEILING INCLUDING S.A. DIFFUSERS BEFORE REQUESTING ABOVE-CEILING INSPECTION. PLACE NO TILE BEFORE INSPECTION EXCEPT THOSE THAT ARE REQUIRED TO MOUNT DEVICES SUCH AS EXIT SIGNS, ETC. ENSURE HVAC FLEX DUCT IS INSTALLED PER AIR DIFFUSION COUNCIL GUIDELINES (ATTACHED).
In-wall Inspection Not Ready 9/15/2016 9/15/2016 09/15/2016
Misc
Corrective Action Required
09/13/2016
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER.
Misc
Corrective Action Required
09/13/2016
IPC 305 PROTECTION OF COPPER PIPING AT PENETRATION OF STEEL FRAMING MEMBERS: INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL. SEE NITROUS OXIDE AND OXYGEN PIPING ONE LOCATION.
Misc
Corrective Action Required
09/13/2016
HOLE NOT CUT FOR ONE ELECT RECEPTACLE BOX.
Misc
Corrective Action Required
09/13/2016
ENSURE STEEL BOCA PLATES ARE NOT IN CONTACT WITH COPPER WATER PIPE -- DISSIMILAR METALS
Misc
Corrective Action Required
09/15/2016
NO ACCESS.
In-wall Inspection Passed 9/16/2016 9/16/2016 09/16/2016
Misc
Resolved
09/16/2016
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER.
Misc
Resolved
09/16/2016
IPC 305 PROTECTION OF COPPER PIPING AT PENETRATION OF STEEL FRAMING MEMBERS: INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL. SEE NITROUS OXIDE AND OXYGEN PIPING ONE LOCATION.
Misc
Resolved
09/16/2016
HOLE NOT CUT FOR ONE ELECT RECEPTACLE BOX.
Misc
Resolved
09/16/2016
ENSURE STEEL BOCA PLATES ARE NOT IN CONTACT WITH COPPER WATER PIPE -- DISSIMILAR METALS.
Misc
Resolved
09/16/2016
NO ACCESS.
Underslab Electrical Inspection - Commercial Passed 9/26/2016 9/26/2016 09/26/2016
Above Ceiling Inspection Partial 10/6/2016 10/6/2016 10/06/2016
Misc
Partial Correction
10/06/2016
CONTRARY TO EARLIER DIRECTION AND AGREEMENT BORDER TILES HAVE BEEN PLACED BEFORE ABOVE-CEILING INSPECTION. CLOSE ALL ELECTRICAL JUNCTION BOXES BEFORE PLACING CEILING TILE. DO NOT PLACE CEILING TILE AT RESTROOM OR AT MED GAS CLOSET.
Misc
Corrective Action Required
10/06/2016
MED GAS VENT MAY NOT BE EXHAUSTED THROUGH PLASTIC VENT TUBE -- AS DISCUSSED EARLIER, USE SHEET METAL DUCT.
Investigation Inspection Complete 12/7/2016 11/22/2016
Final Inspection - Commercial Failed 11/22/2016 11/22/2016
Misc
Corrective Action Required
11/22/2016
LICENSE TAX DUE AND OWING
Misc
Corrective Action Required
11/22/2016
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
11/22/2016
CHECK ALL ELECTRICAL RECEPTACLES TO ENSURE ALL ARE MOUNTED SOLID TO BOX -- NONE "SOFT" OR LOOSE SIDE-TO-SIDE. USE SPACERS WHERE NEEDED.
Misc
Corrective Action Required
11/22/2016
PROVIDE INFORMATION TO OCCUPANT ON LOCATION OF RE-SETS FOR ALL GFI-PROTECTED ELECTRICAL RECEPTACLES.
Misc
Corrective Action Required
11/22/2016
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". LABEL UNOCCUPIED POSITIONS "SPACE".
Misc
Corrective Action Required
11/22/2016
POWER NOT INSTALLED FOR TV'S AT PATIENT CHAIRS
Misc
Corrective Action Required
11/22/2016
DOOR FOR MED GAS ROOM NOT SHOP-LABELED 1HR RATED
Misc
Corrective Action Required
11/22/2016
SEAL BASE OF RESTROOM WATER CLOSET TO FLOOR
Occupancy Inspection - Fire Not Ready 11/22/2016 11/23/2016
Final Inspection - Commercial Partial 11/23/2016 11/23/2016 11/23/2016
Misc
Resolved
11/23/2016
LICENSE TAX DUE AND OWING
Misc
Resolved
11/23/2016
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Resolved
11/23/2016
CHECK ALL ELECTRICAL RECEPTACLES TO ENSURE ALL ARE MOUNTED SOLID TO BOX -- NONE "SOFT" OR LOOSE SIDE-TO-SIDE. USE SPACERS WHERE NEEDED.
Misc
Resolved
11/23/2016
PROVIDE INFORMATION TO OCCUPANT ON LOCATION OF RE-SETS FOR ALL GFI-PROTECTED ELECTRICAL RECEPTACLES.
Misc
Resolved
11/23/2016
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". LABEL UNOCCUPIED POSITIONS "SPACE".
Misc
Corrective Action Required
11/22/2016
POWER NOT INSTALLED FOR TV'S AT PATIENT CHAIRS
Misc
Resolved
11/23/2016
DOOR FOR MED GAS ROOM NOT SHOP-LABELED 1HR RATED
Misc
Resolved
11/23/2016
SEAL BASE OF RESTROOM WATER CLOSET TO FLOOR
Misc
Corrective Action Required
11/23/2016
PEX TUBING AT MECHANICAL ROOM NOT APPROVED -- POINTED OUT TO G.C.
Misc
Partial Correction
11/23/2016
OK FOR USE AND OCCUPANCY THROUGH 12/8/16 WITHIN WHICH TIME REMAINING ISSUES ARE TO BE CORRECTED.
Above Ceiling Inspection Passed 10/6/2016 11/23/2016
Misc
Resolved
11/23/2016
CONTRARY TO EARLIER DIRECTION AND AGREEMENT BORDER TILES HAVE BEEN PLACED BEFORE ABOVE-CEILING INSPECTION. CLOSE ALL ELECTRICAL JUNCTION BOXES BEFORE PLACING CEILING TILE. DO NOT PLACE CEILING TILE AT RESTROOM OR AT MED GAS CLOSET.
Misc
Resolved
11/23/2016
MED GAS VENT MAY NOT BE EXHAUSTED THROUGH PLASTIC VENT TUBE -- AS DISCUSSED EARLIER, USE SHEET METAL DUCT.
Occupancy Inspection - Fire Passed 11/23/2016 11/23/2016
Final Inspection - Commercial Failed 12/6/2016 12/6/2016 12/06/2016
Misc
Corrective Action Required
11/23/2016
ELECTRICAL WIRING AND BOXES TO POWER TV'S AT PATIENT CHAIRS NOT EXPOSED FOR INSPECTION. ELECTRICAL CONTRACTOR TO MAKE ARRANGEMENTS WITH INSPECTOR TO INSPECT ABOVE CEILING.
Misc
Resolved
12/06/2016
PEX TUBING AT MECHANICAL ROOM NOT APPROVED -- POINTED OUT TO G.C.
Misc
Partial Correction
11/23/2016
OK FOR USE AND OCCUPANCY THROUGH 12/8/16 WITHIN WHICH TIME REMAINING ISSUES ARE TO BE CORRECTED.
Final Inspection - Commercial Not Ready 12/7/2016 12/7/2016 12/07/2016
Misc
Corrective Action Required
12/06/2016
ELECTRICAL WIRING AND BOXES TO POWER TV'S AT PATIENT CHAIRS NOT EXPOSED FOR INSPECTION. LICENSED ELECTRICAL CONTRACTOR TO MAKE ARRANGEMENTS WITH INSPECTOR TO INSPECT ABOVE CEILING.
Misc
Resolved
12/07/2016
OK FOR USE AND OCCUPANCY THROUGH 12/8/16 WITHIN WHICH TIME REMAINING ISSUES ARE TO BE CORRECTED.
Final Inspection - Commercial Passed 12/8/2016 12/08/2016
Misc
Resolved
12/08/2016
ELECTRICAL WIRING AND BOXES TO POWER TV'S AT PATIENT CHAIRS NOT EXPOSED FOR INSPECTION. LICENSED ELECTRICAL CONTRACTOR TO MAKE ARRANGEMENTS WITH INSPECTOR TO INSPECT ABOVE CEILING.
Documents & Images
Date Uploaded File Type Document Name
05/12/2016 Letter Fire Building Plan Review
05/13/2016 Letter Codes Plan Review Conditions
08/03/2016 Receipt Receipt for transaction: 2016-005200
08/03/2016 Letter Codes Building Permit
08/04/2016 Bhoot Addendum 1
08/05/2016 Letter Fire Building Plan Review
08/15/2016 Letter Inspection Summary
09/13/2016 Letter Inspection Summary
09/16/2016 Letter Inspection Summary
09/26/2016 Letter Inspection Summary
10/06/2016 Letter Inspection Summary
11/22/2016 Letter Inspection Summary
11/23/2016 Letter Inspection Summary
12/06/2016 Letter Inspection Summary
12/07/2016 Letter Inspection Summary
12/08/2016 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home