Permit Application Status

PRCOM20152455


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20152455
Building Permit - Commercial
Final Completion
RED LEES SUMMIT EAST LLC
NEW SHELL BUILDING
NEW RETAIL BUILDING SHELL
10/21/2015
08/24/2016
01/08/2017
05/26/2017
Locations
Contacts
WDS CONSTRUCTION INC, Address:100 TOWER DR, Phone:(920) 356-1255  
CENTRAL SYSTEMS HEATING & A/C INC, Address:2857 WESTBOUND US HWY 40, Phone:(816) 228-2022  
S & S ELECTRICAL CONTRACTING LLC, Address:574 NW 1921 RD, Phone:(816) 847-2433  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
YAEGER ARCHITECTURE, Address:7780 WEST 119TH STREET, Phone:(913) 742-8000  
RED LEES SUMMIT EAST LLC, Address:1 E WASHINGTON ST STE 300  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
STACO ELECTRIC CONSTRUCTION COMPANY INC, Address:11030 HICKMAN MILLS DR, Phone:(816) 765-7112  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 03/17/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
03/17/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the system will be required prior to the final occupancy inspection. to schedule a test contact the fire department at 816-969-1300
Alarm Plan Review Released for Construction 01/20/2017
Joe Dir
01/20/2017

Misc
Corrective Action Required
01/20/2017

System must be able to communicate back to the Summit Fair's shopping centers main Fire alarm Panel located in building D 860 NW blue Parkway. (VERIFIED AT TESTING)
Installation acceptance testing
Corrective Action Required
01/20/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACCEPTANCE TESTING OF THE FIRE ALARM SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL SHELL / OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Misc
Corrective Action Required
01/20/2017

THE SYSTEM OUTPUT GRAPG INDICATES THAT THE DUCT DETECTION IA SUPERVISORY SIGNAL AND WILL ACTIVATE THE HORN/STROBE DEVICES. MAKE THE CHANGE TO INDICATE THAT DUCT DETECTION IS A SUPERVISORY SIGNAL ONLY NO ACTIVATION OF THE HORN STROBE DEVICES. (VERIFIED AT TESTING)
Alarm Plan Review Rejected 01/17/2017
Joe Dir
Misc
Corrective Action Required
01/17/2017

Plans shall include entire shell building and tenant spaces. FACP to be located in the landlord room located behind the tenant spaces.
Misc
Corrective Action Required
01/17/2017

System must be able to communicate back to the Summit Fair's shopping centers main Fire alarm Panel located in building D 860 NW blue Parkway.
Alarm Plan Review Rejected 01/09/2017
Joe Dir
Misc
Corrective Action Required
01/09/2017

Plans shall include entire shell building and tenant spaces
Misc
Corrective Action Required
01/09/2017

System must be able to communicate back to the Summit Fair's shopping centers main Fire alarm Panel located in building D 860 NW blue Parkway.
Sprinkler Plan Review Released for Construction 11/09/2016
Joe Dir
Misc
Corrective Action Required
11/09/2016

ADDRESS ON PLANS INCORRECT: ADDRESSING ON THE PLANS SHOULD SHOW BUILDING ADDRESS AS 820 NW BLUE PARKWAY
Installation acceptance testing
Corrective Action Required
11/09/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD TESTS AND ACCEPCEPTANCE TESTS WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
Misc
Corrective Action Required
11/09/2016

INSTALL A CHECK VALVE ON THE BASE OF THE RISER.
Misc
Corrective Action Required
11/09/2016

903.3.7 Fire Department connections. The location of the fire department connection shall be approved by the code official. Connections shall be a 4inch storz type fitting (include a 30 degree elbow) Location shall be within 100 feet of a fire hydrant. CONFIRM THE LOCATION OF THE FDC WITH THE PROJECT GENERAL TO BE WITHIN 100 FEET OF A FIRE HYDRANT.
Fire Plan Review Approved with Conditions 12/18/2015 10/11/2016
Joe Dir
10/11/2016

10/11/2016

Knox box required
Corrective Action Required
10/11/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. KNOX BOX CAN BE OBTAINED ON LINE AT knoxbox.com. KNOX BOX TO BE MOUNTED ABOVE THE FDC APPROX. 6' OFF OF FINISH GRADE.
Construction documents - Fire protection systems
Corrective Action Required
10/11/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE ENGINEERED SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
10/11/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD TESTING AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE ALARM SYSTEM AND SPRINKLER SYSTEM PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE ADEPARTMENT AT 816-969-1300.
Construction documents for fire alarm systems
Corrective Action Required
10/11/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ENGINEERED SHOP DRAWINGS FOR THE ALARM SYSTEM TO BE INSTALLED.
Misc
Corrective Action Required
10/11/2016

NO KEYED CYLINDER LOCKS ON THE EGRESS SIDE OF AN EXIT. ( INFORMATION PURPOSES)
Address numbers required
Corrective Action Required
10/11/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). PROVIDE A NUMERIC ADDRESS OF 820 ON THE MAIN BUILDING ON ALL DOORS LEADING INTO THE MAIN BUILDING POST THE SUITE ADDRESSING FOR THE POTENTIAL NEW OCCUPANT SUITES ON THE FRONT AND REAR DOORS, READABLE FROM THE ROADWAY. (VERIFIED AT INSPECTION)
Fire Plan Review Rejected 09/09/2016 09/14/2016
Joe Dir
Address numbers required
Corrective Action Required
09/09/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). PROVIDE A NUMERIC ADDRESS OF 820 ON THE MAIN BUILDING ON ALL DOORS LEADING INTO THE MAIN BUILDING POST THE SUITE ADDRESSING FOR THE POTENTIAL NEW OCCUPANT SUITES ON THE FRONT AND REAR DOORS, READABLE FROM THE ROADWAY
Knox box required
Corrective Action Required
09/09/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. KNOX BOX CAN BE OBTAINED ON LINE AT knoxbox.com. KNOX BOX TO BE MOUNTED ABOVE THE FDC APPROX. 6' OFF OF FINISH GRADE.
Construction documents - Fire protection systems
Corrective Action Required
09/09/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE ENGINEERED SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
09/09/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD TESTING AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE ALARM SYSTEM AND SPRINKLER SYSTEM PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE ADEPARTMENT AT 816-969-1300.
Construction documents for fire alarm systems
Corrective Action Required
09/09/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ENGINEERED SHOP DRAWINGS FOR THE ALARM SYSTEM TO BE INSTALLED.
Misc
Corrective Action Required
09/09/2016

NO KEYED CYLINDER LOCKS ON THE EGRESS SIDE OF AN EXIT. ( INFORMATION PURPOSES)
Misc
Corrective Action Required
09/14/2016

903.3.7 Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch stortz fitting and located witin 100 feet of a fire hydrant, or as approved by the code official. SHOW THE LOCATION OF THE FIRE DEPARTMENT CONNECTION AND FIRE HYDRANTS.
Misc
Corrective Action Required
09/14/2016

DUE TO THE ADDENDUM PLANS SHOWING ADDITIONAL SUITES. SHOW THE LOCATION OF THE FIRE SPRINKLER RISER AND FIRE ALARM SYSTEM. NEEDS TO BE IN A CENTRAL LOCATION WITH EXTERIOR ACCESS.
Fire Plan Review Approved with Conditions 09/06/2016 09/01/2016
Joe Dir
09/01/2016

09/01/2016

09/01/2016

09/01/2016

Construction documents for fire alarm systems
Corrective Action Required
09/01/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ENGINEERED SHOP DRAWINGS FOR THE ALARM SYSTEM TO BE INSTALLED.
Address numbers required
Corrective Action Required
09/01/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). PROVIDE A NUMERIC ADDRESS OF 820 ON THE MAIN BUILDING AND ADDRESSING FOR THE POTENTIAL NEW OCCUPANT SUITES ON THE FRONT AND REAR DOORS, READABLE FROM THE ROADWAY
Knox box required
Corrective Action Required
09/01/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. KNOX BOX CAN BE OBTAINED ON LINE AT knoxbox.com. KNOX BOX TO BE MOUNTED ABOVE THE FDC APPROX. 6' OFF OF FINISH GRADE.
Construction documents - Fire protection systems
Corrective Action Required
09/01/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE ENGINEERED SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
09/01/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD TESTING AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE ALARM SYSTEM AND SPRINKLER SYSTEM PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE ADEPARTMENT AT 816-969-1300.
Final Development Plan Review Approved 05/02/2016 08/23/2016
Development Center
Sprinkler Plan Review Released for Construction 08/16/2016
Joe Dir
Misc
Corrective Action Required
08/16/2016

INSTALL A CHECK VALVE AT THE BASE OF THE RISER.
Installation acceptance testing
Corrective Action Required
08/16/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE SYSTEM PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE TESTING CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
Building Plan Review Approved with Conditions 12/18/2015 07/19/2016
Joe Frogge
Final Development Plan
Resolved
09/08/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 12/16/15 - acknowledged in letter
Misc
Resolved
07/19/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections. 12/16/15 - acknowledged in letter
License Tax Application
Resolved
07/14/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 12/16/15 - acknowledged in letter
Bldg - Safety glazing - Hazardous locations 2406.4
Resolved
12/16/2015

2012 IBC 2406.4 - Hazardous locations. The locations specified in Sections 2406.4.1 through 2406.4.7 shall be considered specific hazardous locations requiring safety glazing materials. Action required: Specify safety glazing at all appropriate fenestration. Currently only windows at and next to doors are designated as tempered. 12/16/15 - drawings revised to demonstrate compliance. Note: per letter, the windows shown w/o saftey glazing are >18 aff
Bldg - Types I and II construction allowable materials 602.2
Resolved
12/16/2015

2012 IBC 602.2 – Types I and II. Types I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials, except as permitted in Section 603 and elsewhere in this code. Action required: Non-fire-retardant-treated wood is not allowed in locations not specifically exempted. Reference the following: - wood blocking at detail C5/A411 - wood blocking at detail D5/A412 - wood sheathing on sheet S100 (note #10) 12/16/15 - notes added to details
Mech - Duct detectors - Return air systems 606.2.1
Resolved
12/16/2015

2012 IMC 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm, in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4. Action required: Provide smoke detectors at hvac units. 12/16/15 - SDs added to drawings
NEC - Grounding electrode System
Resolved
12/18/2015

Electrical diagram incomplete. Action required: Include grounding. Provide wire sizes for rtu circuits. 12/16/15 - Grounding shown, but wire sizes for rtu circuits remain without wire sizes. 12/18/15 - clarification via email. wire sizes were in rtu schedule
Special Inspections Review Approved 07/19/2016
Joe Frogge
Fire Plan Review Approved with Conditions 12/18/2015 07/15/2016
Joe Dir
Misc
Corrective Action Required
12/11/2015

503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm). D102.1 Access and loading. Facilities, buildings or portions of buildings hereafter constructed shall be accessible to fire department apparatus by way of an approved fire apparatus access road with an asphalt, concrete or other approved driving surface capable of supporting the imposed load of fire apparatus weighing at least 75,000 pounds (34 050 kg). D103.1 Access road width with a hydrant. Where a fire hydrant is located on a fire apparatus access road, the minimum road width shall be 26 feet (7925 mm), exclusive of shoulders.
Construction documents for fire alarm systems
Corrective Action Required
12/11/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ENGINEERED SHOP DRAWINGS FOR THE ALARM SYSTEM. INORMATION PURPOSES.
Fire access roads or water supply required
Corrective Action Required
12/11/2015

2012 IFC 501.4- Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided. Temporary street signs shall be installed at each street intersection when construction of new roadways allows passage by vehicles in accordance with Section 505.2.
Access roads required for building and facilities
Corrective Action Required
12/11/2015

2012IFC 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 150 feet (45,720 mm) where: 1.The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. 3. There are not more than two Group R-3 or Group U occupancies.
Address numbers required
Corrective Action Required
12/11/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). PROVIDE A NUMERIC ADDRESS OF 820 ON OR NEAR THE BUILDING READABLE FROM THE ROADWAY DURING AND AFTER CONSTRUCTION. VERIFIED AT INSPECTION (ACKNOWLEDGED IN LETTER AND PLANS)
Knox box required
Corrective Action Required
12/11/2015

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. KNOX BOX CAN BE OBTAINED ON LINE AT knoxbox.com or contact the fire department for an application. (ACKNOWLEDGED IN LETTER AND PLANS)
Hydrant required
Corrective Action Required
12/11/2015

2012 IFC 508.5.1 -Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Exceptions: 1. For Group R-3 and Group U occupancies, the distance requirement shall be 600 feet (183 m). D103.1 Access road width with a hydrant. Where a fire hydrant is located on a fire apparatus access road, the minimum road width shall be 26 feet (7925 mm), exclusive of shoulders (see Figure D103.1). PROVIDE A HYDRANT WITHIN 100' OF THE FDC. ( ACKNOWLEDGED IN LETTER)
Construction documents - Fire protection systems
Corrective Action Required
12/11/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE ENGINEERED SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM. INFORMATION PURPOSES
Installation acceptance testing
Corrective Action Required
12/11/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD TESTING AND ACCEPTANCE TESTING REQUIRED FOR THE ALARM SYSTEM AND SPRINKLER SYSTEM. TO SCHEDULE TESTING CONTACT THE FIRE DEPARTMENT AT 816-969-1300. INFORMATION PURPOSES.
Licensed Contractors Approved 12/11/2015 07/14/2016
Joe Frogge
LC - General Contractor
Resolved
07/14/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 12/16/15 - acknowledged in letter
LC - MEP Subs
Resolved
07/14/2016

MEP Subs: No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 12/16/15 - acknowledged in letter
Building Plan Review Rejected 11/04/2015 11/02/2015
Joe Frogge
Final Development Plan
Corrective Action Required
11/02/2015

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
11/02/2015

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
License Tax Application
Corrective Action Required
11/02/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Bldg - Safety glazing - Hazardous locations 2406.4
Corrective Action Required
11/02/2015

2012 IBC 2406.4 - Hazardous locations. The locations specified in Sections 2406.4.1 through 2406.4.7 shall be considered specific hazardous locations requiring safety glazing materials. Action required: Specify safety glazing at all appropriate fenestration. Currently only windows at and next to doors are designated as tempered.
Bldg - Types I and II construction allowable materials 602.2
Corrective Action Required
11/02/2015

2012 IBC 602.2 – Types I and II. Types I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials, except as permitted in Section 603 and elsewhere in this code. Action required: Non-fire-retardant-treated wood is not allowed in locations not specifically exempted. Reference the following: - wood blocking at detail C5/A411 - wood blocking at detail D5/A412 - wood sheathing on sheet S100 (note #10)
Mech - Duct detectors - Return air systems 606.2.1
Corrective Action Required
11/02/2015

2012 IMC 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm, in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4. Action required: Provide smoke detectors at hvac units.
NEC - Grounding electrode System
Corrective Action Required
11/02/2015

Electrical diagram incomplete. Action required: Include grounding. Provide wire sizes for rtu circuits.
Licensed Contractors Rejected 11/04/2015 11/02/2015
Joe Frogge
LC - General Contractor
Corrective Action Required
11/02/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
11/02/2015

MEP Subs: No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 11/04/2015 10/29/2015
Joe Dir
Misc
Corrective Action Required
10/29/2015

503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm). D102.1 Access and loading. Facilities, buildings or portions of buildings hereafter constructed shall be accessible to fire department apparatus by way of an approved fire apparatus access road with an asphalt, concrete or other approved driving surface capable of supporting the imposed load of fire apparatus weighing at least 75,000 pounds (34 050 kg). D103.1 Access road width with a hydrant. Where a fire hydrant is located on a fire apparatus access road, the minimum road width shall be 26 feet (7925 mm), exclusive of shoulders.
Construction documents for fire alarm systems
Corrective Action Required
10/29/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ENGINEERED SHOP DRAWINGS FOR THE ALARM SYSTEM. INORMATION PURPOSES.
Fire access roads or water supply required
Corrective Action Required
10/29/2015

2012 IFC 501.4- Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided. Temporary street signs shall be installed at each street intersection when construction of new roadways allows passage by vehicles in accordance with Section 505.2.
Access roads required for building and facilities
Corrective Action Required
10/29/2015

2012IFC 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 150 feet (45,720 mm) where: 1.The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. 3. There are not more than two Group R-3 or Group U occupancies.
Address numbers required
Corrective Action Required
10/29/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). PROVIDE A NUMERIC ADDRESS OF 820 ON OR NEAR THE BUILDING READABLE FROM THE ROADWAY DURING AND AFTER CONSTRUCTION. VERIFIED AT INSPECTION
Knox box required
Corrective Action Required
10/29/2015

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. KNOX BOX CAN BE OBTAINED ON LINE AT knoxbox.com or contact the fire department for an application.
Hydrant required
Corrective Action Required
10/29/2015

2012 IFC 508.5.1 -Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Exceptions: 1. For Group R-3 and Group U occupancies, the distance requirement shall be 600 feet (183 m). D103.1 Access road width with a hydrant. Where a fire hydrant is located on a fire apparatus access road, the minimum road width shall be 26 feet (7925 mm), exclusive of shoulders (see Figure D103.1). PROVIDE A HYDRANT WITHIN 100' OF THE FDC.
Construction documents - Fire protection systems
Corrective Action Required
10/29/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE ENGINEERED SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM. INFORMATION PURPOSES
Installation acceptance testing
Corrective Action Required
10/29/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD TESTING AND ACCEPTANCE TESTING REQUIRED FOR THE ALARM SYSTEM AND SPRINKLER SYSTEM. TO SCHEDULE TESTING CONTACT THE FIRE DEPARTMENT AT 816-969-1300. INFORMATION PURPOSES.
10/29/2015

Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Shell Building $3,536.61 $3,536.61 Paid 08/22/2016
8350015-Water Meter Fee $556.04 $556.04 Paid 08/22/2016
8331401-Water Tap Fee $8,571.00 $8,571.00 Paid 08/22/2016
9110078-Valuation Fee for New Shell Building $907.65 $907.65 Paid 10/28/2016
$4,444.26
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 9/19/2016 (1:00) 9/19/2016 09/19/2016
Misc
Partial Correction
09/19/2016
EXTERIOR GRADE BEAM & COLUMN PADS OK: -FROM A.1/7 TO C.5/7
Footing Inspection - Commercial Failed 9/20/2016 (2:00) 9/20/2016 09/20/2016
Misc
Resolved
09/20/2016
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS: FROM A.1/7 TO C.5/7;
Misc
Corrective Action Required
09/20/2016
ACI 7.7.1 MINIMUM RE-BAR COVERAGE: 3" TO BOTTOMS/BANKS NOT PROVIDED CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS: FROM A.1/7 TO E/7;
Electrical Service Inspection Partial 9/20/2016 9/20/2016 09/20/2016
Misc
Partial Correction
09/20/2016
RELEASE TEMPORARY ELECTRICAL SERVICE
Footing Inspection - Commercial Partial 9/21/2016 9/21/2016 09/21/2016
Misc
Partial Correction
09/21/2016
OK TO COVER WHEN READY CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS: FROM A/7 TO E/7 TO E/6.8;
Footing Inspection - Commercial Partial 9/22/2016 (1:00) 9/22/2016 09/22/2016
Misc
Partial Correction
09/21/2016
OK TO COVER WHEN READY CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS: FROM A/7 TO E/7 TO E/6.8; E/6.8 TO E/2 TO D.3/1.2;
Footing Inspection - Commercial Partial 9/23/2016 (1:00) 9/23/2016 09/23/2016
Misc
Partial Correction
09/22/2016
OK TO COVER WHEN READY CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS: FROM A/7 TO E/7 TO E/6.8; E/6.8 TO E/2 TO D.3/1.2; D.3/1.2 to D/1 TO 1/B.2;
Footing Inspection - Commercial Partial 9/27/2016 (1:00) 9/27/2016 09/27/2016
Misc
Partial Correction
09/23/2016
OK TO COVER WHEN READY CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS: FROM A/7 TO E/7 TO E/6.8; E/6.8 TO E/2 TO D.3/1.2; D.3/1.2 to D/1 TO 1/B.2; 1/B.2 TO A/1 TO A/2.8;
Misc
Partial Correction
09/27/2016
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: B/2; B/3; B/5; C/2; C/3; C/5;
Underslab Plumbing Inspection - Commercial Partial 9/27/2016 09/27/2016
Misc
Partial Correction
09/27/2016
6" PVC ROOF DRAIN PIPE TOBE CAST INTO BUILDING GRADE BEAM/FOOTING AT
Footing Inspection - Commercial Failed 9/28/2016 (1:00) 9/28/2016 09/28/2016
Misc
Partial Correction
09/27/2016
OK TO COVER WHEN READY CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS: FROM A/7 TO E/7 TO E/6.8; E/6.8 TO E/2 TO D.3/1.2; D.3/1.2 to D/1 TO 1/B.2;
Misc
Partial Correction
09/27/2016
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: B/2; B/3; B/5; C/2; C/3; C/5;
Misc
Corrective Action Required
09/28/2016
ACI 7.7.1 MINIMUM RE-BAR COVERAGE: 3" TO BOTTOMS/BANKS
Underslab Plumbing Inspection - Commercial Partial 9/28/2016 9/28/2016 09/28/2016
Misc
Partial Correction
09/27/2016
6" PVC ROOF DRAIN PIPE TOBE CAST INTO BUILDING GRADE BEAM/FOOTING AT
Misc
Partial Correction
09/28/2016
4" SANITARY BUILDING SEWER FROM BUILDING ENTRY TO EAST 35';
Footing Inspection - Commercial Partial 9/29/2016 (9:00) 9/29/2016 09/29/2016
Misc
Resolved
09/29/2016
OK TO COVER WHEN READY CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS: FROM A/7 TO E/7 TO E/6.8; E/6.8 TO E/2 TO D.3/1.2; D.3/1.2 to D/1 TO 1/B.2; 1/B.2 TO A/1 TO A/2.8; A/2.8 TO A/7 TO COMPLETE PERIMETER GRADE BEAM
Misc
Partial Correction
09/27/2016
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: B/2; B/3; B/5; C/2; C/3; C/5;
Rough Framing Inspection - Commercial Passed 9/29/2016 9/30/2016 09/30/2016
Misc
Resolved
09/30/2016
6" PVC ROOF DRAIN PIPE TOBE CAST INTO BUILDING GRADE BEAM/FOOTING AT
Misc
Resolved
09/30/2016
4" SANITARY BUILDING SEWER FROM BUILDING ENTRY TO EAST 35';
Underslab Electrical Inspection - Commercial Passed 9/30/2016 09/30/2016
Foundation Inspection - Commercial Passed 10/4/2016 10/04/2016
Rough Framing Inspection - Commercial Partial 11/3/2016 11/3/2016 11/03/2016
Misc
Partial Correction
11/03/2016
OK TO COVER WHEN READY SECTIONS OF LIGHT-GAUGE STEEL ELEVATED WALL FRAMING AT: ON (B) FROM (3) TO (4) AND (6) TO (7) ON (1) FROM (B) TO (C) ON (C) FROM (1) TO (3) ON (3) FROM (C) TO (E)
Misc
Corrective Action Required
11/03/2016
SOFFIT FRAMING PER DETAIL C4/A413 AT (A) FROM (2) TO (7): SCREW BOTH FLANGES AT OUTLOOKER CONNECTIONS TO HEADER TRACK MEMBER
Rough Framing Inspection - Commercial Partial 11/7/2016 11/7/2016 11/07/2016
Misc
Partial Correction
11/03/2016
OK TO COVER WHEN READY SECTIONS OF LIGHT-GAUGE STEEL ELEVATED WALL FRAMING AT: ON (B) FROM (3) TO (4) AND (6) TO (7) ON (1) FROM (B) TO (C) ON (C) FROM (1) TO (3) ON (3) FROM (C) TO (E)
Misc
Partial Correction
11/07/2016
EXTERIOR EAVE SOFFIT FRAMING OK AT COVER AT: EAST WALL;
Rough Framing Inspection - Commercial Partial 11/8/2016 11/08/2016
Misc
Partial Correction
11/07/2016
OK TO COVER WHEN READY SECTIONS OF LIGHT-GAUGE STEEL ELEVATED WALL FRAMING AT: ON (B) FROM (3) TO (4) AND (6) TO (7) ON (1) FROM (B) TO (C) ON (C) FROM (1) TO (3) ON (3) FROM (C) TO (E) ON (1) FROM (C) TO (D) ON (E) FROM (2) TO (3)
Misc
Partial Correction
11/07/2016
EXTERIOR EAVE SOFFIT FRAMING OK AT COVER AT: EAST WALL;
Footing Inspection - Commercial Partial 11/9/2016 (10:30) 11/9/2016 11/09/2016
Misc
Resolved
11/09/2016
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: B/2; B/3; B/5; C/2; C/3; C/5;
Misc
Partial Correction
11/09/2016
PHASE II: AFTER TRENCH IS CLEANED FOR RE-BAR COVERAGE AT NE CORNER OK TO POUR WHEN READY PERIMETER GRADE BEAM & INTEGRAL COLUMN FOOTINGS + ISOLATED FOOTING C.2/8 FOOTING C.2/7.1 NOT READY
Footing Inspection - Commercial Partial 11/10/2016 (11:00) 11/10/2016 11/10/2016
Misc
Partial Correction
11/09/2016
PHASE II: AFTER TRENCH IS CLEANED FOR RE-BAR COVERAGE AT NE CORNER OK TO POUR WHEN READY PERIMETER GRADE BEAM & INTEGRAL COLUMN FOOTINGS + ISOLATED FOOTING C.2/8 FOOTING C.2/7.1 NOT READY
Foundation Inspection - Commercial Not Ready 11/10/2016 11/10/2016
Misc
Corrective Action Required
11/10/2016
CURB WALLS NOT READY FOR INSPECTION
Footing Inspection - Commercial Not Ready 11/11/2016 (8:00) 11/11/2016 11/11/2016
Misc
Partial Correction
11/10/2016
PHASE II: AFTER TRENCH IS CLEANED FOR RE-BAR COVERAGE AT NE CORNER OK TO POUR WHEN READY PERIMETER GRADE BEAM & INTEGRAL COLUMN FOOTINGS + ISOLATED FOOTING C.2/8 FOOTING C.2/7.1 NOT READY
Rough Framing Inspection - Commercial Partial 11/11/2016 11/11/2016 11/11/2016
Misc
Partial Correction
11/08/2016
OK TO COVER WHEN READY SECTIONS OF LIGHT-GAUGE STEEL HIGH/ELEVATED WALL FRAMING AT: ON (B) FROM (3) TO (4) AND (6) TO (7) ON (1) FROM (B) TO (C) ON (C) FROM (1) TO (3) ON (3) FROM (C) TO (E) ON (1) FROM (C) TO (D) ON (E) FROM (2) TO (3) ON (A) FROM (1) TO (2) ON (1) FROM (A) TO (A.4) SOFFIT BOX-OUT ON (1) FROM (C.1) TO (C.9)
Misc
Partial Correction
11/08/2016
EXTERIOR EAVE SOFFIT FRAMING OK AT COVER AT: EAST WALL;
Foundation Inspection - Commercial Partial 11/14/2016 11/14/2016
Misc
Partial Correction
11/14/2016
OK TO POUR WHEN READY SHORT WALLS AT NW AND NE CORNERS
Rough Electrical Inspection - Commercial Partial 11/15/2016 11/15/2016
Misc
Partial Correction
11/15/2016
MC ELECTRICAL CABLE AND METALLIC FLEX CONDUIT EXTENDED FROM INSIDE CMU WALL THROUGH PLYWOOD SHEATHING AT NE CORNER OF BLDG;
Rough Framing Inspection - Commercial Partial 11/17/2016 11/21/2016 11/21/2016
Misc
Partial Correction
11/11/2016
OK TO COVER WHEN READY SECTIONS OF LIGHT-GAUGE STEEL HIGH/ELEVATED WALL FRAMING AT: ON (B) FROM (3) TO (4) AND (6) TO (7) ON (1) FROM (B) TO (C) ON (C) FROM (1) TO (3) ON (3) FROM (C) TO (E) ON (1) FROM (C) TO (D) ON (E) FROM (2) TO (3) ON (A) FROM (1) TO (2) ON (1) FROM (A) TO (A.4) SOFFIT BOX-OUT ON (1) FROM (C.1) TO (C.9) ON (E) FROM (2) TO (3) COLUMN BOX-OUTS ON (E) AT (3), (4.5) & (5.9)** **CROSS-BRACING TO BE INSTALLED AT 8' & 16" AFF
Misc
Partial Correction
11/11/2016
EXTERIOR EAVE SOFFIT FRAMING OK AT COVER AT: EAST WALL;
Rough Framing Inspection - Commercial Partial 11/23/2016 11/23/2016 11/23/2016
Misc
Partial Correction
11/21/2016
OK TO COVER WHEN READY SECTIONS OF LIGHT-GAUGE STEEL HIGH/ELEVATED WALL FRAMING AT: ON (B) FROM (3) TO (4) AND (6) TO (7) ON (1) FROM (B) TO (C) ON (C) FROM (1) TO (3) ON (3) FROM (C) TO (E) ON (1) FROM (C) TO (D) ON (E) FROM (2) TO (3) ON (A) FROM (1) TO (2) ON (1) FROM (A) TO (A.4) SOFFIT BOX-OUT ON (1) FROM (C.1) TO (C.9) ON (E) FROM (2) TO (3) COLUMN BOX-OUTS ON (E) AT (3), (4.5) & (5.9)** TALL & ELEVATED FRAMING @ NW CORNER **CROSS-BRACING TO BE INSTALLED AT 8' & 16" AFF
Misc
Partial Correction
11/21/2016
EXTERIOR EAVE SOFFIT FRAMING OK AT COVER AT: EAST WALL;
Rough Framing Inspection - Commercial Partial 11/29/2016 11/29/2016 11/29/2016
Misc
Partial Correction
11/23/2016
OK TO COVER WHEN READY SECTIONS OF LIGHT-GAUGE STEEL HIGH/ELEVATED WALL FRAMING AT: ON (B) FROM (3) TO (4) AND (6) TO (7) ON (1) FROM (B) TO (C) ON (C) FROM (1) TO (3) ON (3) FROM (C) TO (E) ON (1) FROM (C) TO (D) ON (E) FROM (2) TO (3) ON (A) FROM (1) TO (2) ON (1) FROM (A) TO (A.4) SOFFIT BOX-OUT ON (1) FROM (C.1) TO (C.9) ON (E) FROM (2) TO (3) COLUMN BOX-OUTS ON (E) AT (3), (4.5) & (5.9)** TALL & ELEVATED FRAMING @ NW CORNER ON (E) FROM (5) TO (5.8) **CROSS-BRACING TO BE INSTALLED AT 8' & 16" AFF
Misc
Partial Correction
11/23/2016
EXTERIOR EAVE EYEBROW FRAMING OK AT COVER AT: EAST WALL; OK AT COVER FRAMING FOR EXTERIOR EYEBROWS ABOVE WINDOW-WALL ON (A) SECTIONS CENTERED AT: (2.6); (3.3); (4.2);
Rough Framing Inspection - Commercial Partial 12/2/2016 12/2/2016 12/02/2016
Misc
Partial Correction
11/29/2016
OK TO COVER WHEN READY SECTIONS OF LIGHT-GAUGE STEEL HIGH/ELEVATED WALL FRAMING AT: ON (B) FROM (3) TO (4) AND (6) TO (7) ON (1) FROM (B) TO (C) ON (C) FROM (1) TO (3) ON (3) FROM (C) TO (E) ON (1) FROM (C) TO (D) ON (E) FROM (2) TO (3) ON (A) FROM (1) TO (2) ON (1) FROM (A) TO (A.4) SOFFIT BOX-OUT ON (1) FROM (C.1) TO (C.9) ON (E) FROM (2) TO (3) COLUMN BOX-OUTS ON (E) AT (3), (4.5) & (5.9)** TALL & ELEVATED FRAMING @ NW CORNER ON (E) FROM (5) TO (5.8) **CROSS-BRACING TO BE INSTALLED AT 8' & 16" AFF
Misc
Partial Correction
11/29/2016
EXTERIOR EAVE EYEBROW FRAMING OK AT COVER AT: EAST WALL; SOUTH WALL OK AT COVER FRAMING FOR EXTERIOR EYEBROWS ABOVE WINDOW-WALL ON (A) SECTIONS CENTERED AT: (2.6); (3.3); (4.2);
Gas Piping Inspection - Commercial Not Ready 12/27/2016 12/27/2016
Misc
Corrective Action Required
12/27/2016
PLUMBING CONTRACTOR NOT FOUND ON SITE. ACCESS TO GAS PIPING REQURED FOR INSPECTION. CALL FOR INSPECTION WHEN PERSONNEL ARE ON SITE.
Gas Piping Inspection - Commercial Failed 12/28/2016 12/28/2016
Misc
Resolved
12/28/2016
PLUMBING CONTRACTOR NOT FOUND ON SITE. ACCESS TO GAS PIPING REQURED FOR INSPECTION. CALL FOR INSPECTION WHEN PERSONNEL ARE ON SITE.
Misc
Corrective Action Required
12/28/2016
IFGC 407.2 & 415; IRC G2423 SUPPORT OF HORIZONTAL RUNS OF RIGID STEEL PIPING: SPACING OF BLOCKS/HANGERS -- : 1/2" PIPE -- 6' MAX SPACING; 3/4" OR 1" PIPE -- 8' MAX SPACING; 1-1/4" OR LARGER PIPE -- 10' MAX SPACING. SUPPORT AT 90'S, TEES, AND JOINTS. ENSURE PIPE IS STRAPPED AT ALL BLOCKS
Misc
Corrective Action Required
12/28/2016
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED AND RE-INSTALLED FOR CLEANING.
Misc
Corrective Action Required
12/28/2016
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS.
Gas Service Inspection - Commercial Passed 12/28/2016 12/28/2016
Gas Service Inspection - Commercial Not Ready 12/27/2016 12/28/2016
Foundation Inspection - Commercial Passed 11/14/2016 12/28/2016
Misc
Resolved
12/28/2016
OK TO POUR WHEN READY SHORT WALLS AT NW AND NE CORNERS
Footing Inspection - Commercial Passed 11/11/2016 12/28/2016
Misc
Resolved
12/28/2016
6" PVC ROOF DRAIN PIPE TOBE CAST INTO BUILDING GRADE BEAM/FOOTING AT
Misc
Resolved
12/28/2016
4" SANITARY BUILDING SEWER FROM BUILDING ENTRY TO EAST 35';
Misc
Resolved
12/28/2016
OK TO COVER WHEN READY 4" PVC UNDER SLAB SANITARY DRAIN, WASTE, & VENT PIPING ON (B.25) FROM (7.1) TO (9) + BRANCH TO FD-1 AT LANDLORD'S RM NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM
Rough Framing Inspection - Commercial Passed 12/2/2016 12/28/2016
Misc
Resolved
12/28/2016
OK TO COVER WHEN READY SECTIONS OF LIGHT-GAUGE STEEL HIGH/ELEVATED WALL FRAMING AT: ON (B) FROM (3) TO (4) AND (6) TO (7) ON (1) FROM (B) TO (C) ON (C) FROM (1) TO (3) ON (3) FROM (C) TO (E) ON (1) FROM (C) TO (D) ON (E) FROM (2) TO (3) ON (A) FROM (1) TO (2) ON (1) FROM (A) TO (A.4) SOFFIT BOX-OUT ON (1) FROM (C.1) TO (C.9) ON (E) FROM (2) TO (3) COLUMN BOX-OUTS ON (E) AT (3), (4.5) & (5.9)** TALL & ELEVATED FRAMING @ NW CORNER ON (E) FROM (5) TO (5.8) **CROSS-BRACING TO BE INSTALLED AT 8' & 16" AFF
Misc
Resolved
12/28/2016
EXTERIOR EAVE EYEBROW FRAMING OK AT COVER AT: EAST WALL; SOUTH WALL OK AT COVER FRAMING FOR EXTERIOR EYEBROWS ABOVE WINDOW-WALL ON (A) SECTIONS CENTERED AT: (2.6); (3.3); (4.2);
Footing Inspection - Commercial Passed 11/14/2016 (8:30) 11/11/2016 12/28/2016
Misc
Resolved
12/28/2016
PHASE II: AFTER TRENCH IS CLEANED FOR RE-BAR COVERAGE AT NE CORNER OK TO POUR WHEN READY PERIMETER GRADE BEAM & INTEGRAL COLUMN FOOTINGS + ISOLATED FOOTING C.2/8 FOOTING C.2/7.1 NOT READY
Rough Electrical Inspection - Commercial Passed 11/15/2016 12/28/2016
Misc
Resolved
12/28/2016
MC ELECTRICAL CABLE AND METALLIC FLEX CONDUIT EXTENDED FROM INSIDE CMU WALL THROUGH PLYWOOD SHEATHING AT NE CORNER OF BLDG;
Rough Framing Inspection - Commercial Passed 1/12/2017 1/12/2017 01/12/2017
Misc
Resolved
01/12/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING FOR CORNICE AT B.1/8.3 TO B.1/9 TO 9/B.7
Underground Electrical Inspection - Commercial Partial 1/25/2017 1/25/2017 01/25/2017
Misc
Corrective Action Required
01/25/2017
GOING FROM THE BLDG TO THE TRANSFORMER
Rough Framing Inspection - Commercial Not Ready 1/25/2017 1/25/2017 01/25/2017
Misc
Corrective Action Required
01/25/2017
BOTH FLANGES OF STRUCTURAL STUDS MUST BE SCREWED TO TRACKS. THREE SCREWS REQUIRED AT MID-HEIGHT OF DEFLECTION CLIPS
Rough Framing Inspection - Commercial Partial 1/27/2017 1/27/2017 01/27/2017
Misc
Partial Correction
01/27/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING AT EXTERIOR WALLS AND PILASTERS
Electrical Service Inspection Not Ready 1/27/2017 1/27/2017 01/27/2017
Misc
Partial Correction
09/20/2016
RELEASE TEMPORARY ELECTRICAL SERVICE
Footing Inspection - Commercial Not Ready 1/30/2017 (1:00) 1/30/2017 01/30/2017
Footing Inspection - Commercial Not Ready 1/31/2017 (8:00) 1/31/2017 01/31/2017
Electrical Service Inspection Partial 1/31/2017 1/31/2017 01/31/2017
Misc
Resolved
01/31/2017
RELEASE TEMPORARY ELECTRICAL SERVICE
Misc
Partial Correction
01/31/2017
SERVICE RLEASED CONTINGENT ON G.E.C. BEING CAD-WELDED TO GROUND ROD PER APPROVED DRAWING
Footing Inspection - Commercial Passed 1/31/2017 (11:00) 1/31/2017 01/31/2017
Underground Electrical Inspection - Commercial Not Ready 2/22/2017 2/22/2017 02/22/2017
Misc
Partial Correction
02/22/2017
GOING FROM THE BLDG TO THE TRANSFORMER
Misc
Corrective Action Required
02/22/2017
INSPECTION REQUESTED BY STACO FOR SITE ELECTRICAL. STACO NOT LISTED ON PERMIT. NO PERMIT DRAWING FOUND FOR WORK IN QUESTION.
Underground Electrical Inspection - Commercial Partial 2/23/2017 2/23/2017 02/23/2017
Misc
Partial Correction
02/22/2017
GOING FROM THE BLDG TO THE TRANSFORMER
Misc
Partial Correction
02/23/2017
SITE ELECTRICAL TRENCHED CONDUIT: FROM PERMIT PRINT MARK (2) TO (3) TO (4) APPROX 30% COVERED BEFORE INSPECTION -- 70% APPROVED; FROM PERMIT PRINT MARK (1) TO (1) SUBSTANTIALLY COVERED -- NOT APPROVED.
Underground Electrical Inspection - Commercial Partial 2/24/2017 2/24/2017 02/24/2017
Misc
Resolved
02/24/2017
GOING FROM THE BLDG TO THE TRANSFORMER
Misc
Partial Correction
02/23/2017
SITE ELECTRICAL TRENCHED CONDUIT: FROM PERMIT PRINT MARK (2) TO (3) TO (4) APPROX 30% COVERED BEFORE INSPECTION -- 70% APPROVED; WITHIN 20' OF/AT J.B. AT (9); FROM (3) TO (10); IN PROGRESS FROM (10) TO (11); FROM PERMIT PRINT MARK (1) TO (1) SUBSTANTIALLY COVERED -- NOT APPROVED.
Underground Electrical Inspection - Commercial Partial 2/27/2017 2/27/2017 02/27/2017
Misc
Partial Correction
02/24/2017
SITE ELECTRICAL TRENCHED CONDUIT: FROM PERMIT PRINT MARK (2) TO (3) TO (4) APPROX 30% COVERED BEFORE INSPECTION -- 70% APPROVED; WITHIN 20' OF/AT J.B. AT (9); FROM (3) TO (10); FROM (10) TO (11); FROM (4) TO (8); FROM PERMIT PRINT MARK (1) TO (1) SUBSTANTIALLY COVERED -- NOT APPROVED.
Underground Electrical Inspection - Commercial Partial 2/27/2017 02/27/2017
Misc
Partial Correction
02/27/2017
SITE ELECTRICAL TRENCHED CONDUIT: FROM PERMIT PRINT MARK (2) TO (3) TO (4) APPROX 30% COVERED BEFORE INSPECTION -- 70% APPROVED; WITHIN 20' OF/AT J.B. AT (9); FROM (3) TO (10); FROM (10) TO (11); FROM (4) TO (8); FROM (5) TO (6) TO (7) TO (9); FROM PERMIT PRINT MARK (1) TO (2) SUBSTANTIALLY COVERED -- NOT APPROVED.
Underground Electrical Inspection - Commercial Not Ready 2/28/2017 2/28/2017 02/28/2017
Misc
Partial Correction
02/27/2017
SITE ELECTRICAL TRENCHED CONDUIT: FROM PERMIT PRINT MARK (2) TO (3) TO (4) APPROX 30% COVERED BEFORE INSPECTION -- 70% APPROVED; WITHIN 20' OF/AT J.B. AT (9); FROM (3) TO (10); FROM (10) TO (11); FROM (4) TO (8); FROM (5) TO (6) TO (7) TO (9); FROM PERMIT PRINT MARK (1) TO (2) SUBSTANTIALLY COVERED -- NOT APPROVED.
Misc
Corrective Action Required
02/28/2017
NO ENGINEER DRAWING FOR LIGHT POLE BASES
Final Inspection - Commercial Partial 3/1/2017 03/01/2017
Misc
Partial Correction
03/01/2017
SCOPE OF DEVELOPMENT AGREEMENT + PERMIT (BUILDING + SITE) IS NOT COMPLETED FOR FULL FINAL INSPECTION. HOWEVER, NO REASON FOUND WHY WORK SHOULD NOT PROCEED ON INTERIOR FINISH FOR H&M. SOME EXTERIOR SIDELIGHT UNITS MAY NOT BE APPROVABLE RE SAFETY GLAZING. PAPER-FACED INSULATION MAY NOT BE LEFT EXPOSED. REQUEST FULL FINAL INSPECTION WHEN WORK IS COMPLETED.
Underground Electrical Inspection - Commercial Partial 3/2/2017 3/2/2017 03/02/2017
Misc
Partial Correction
02/28/2017
SITE ELECTRICAL TRENCHED CONDUIT: FROM PERMIT PRINT MARK (2) TO (3) TO (4) APPROX 30% COVERED BEFORE INSPECTION -- 70% APPROVED; WITHIN 20' OF/AT J.B. AT (9); FROM (3) TO (10); FROM (10) TO (11); FROM (4) TO (8); FROM (5) TO (6) TO (7) TO (9); FROM PERMIT PRINT MARK (1) TO (2) SUBSTANTIALLY COVERED -- NOT APPROVED.
Misc
Corrective Action Required
02/28/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT PRINT MARKS: #1; 2; 4; 9;
Sprinkler - Hydrostatic Test Passed 3/3/2017 03/03/2017
Final Inspection - Commercial Partial 3/7/2017 3/7/2017 03/07/2017
Misc
Partial Correction
03/01/2017
SCOPE OF DEVELOPMENT AGREEMENT + PERMIT (BUILDING + SITE) IS NOT COMPLETED FOR FULL FINAL INSPECTION. HOWEVER, NO REASON FOUND WHY WORK SHOULD NOT PROCEED ON INTERIOR FINISH FOR H&M. SOME EXTERIOR SIDELIGHT UNITS MAY NOT BE APPROVABLE RE SAFETY GLAZING. PAPER-FACED INSULATION MAY NOT BE LEFT EXPOSED. REQUEST FULL FINAL INSPECTION WHEN WORK IS COMPLETED.
Misc
Corrective Action Required
03/07/2017
SUBMIT SPECIAL INSPECTION APPROVAL DOCUMENTATION. OKAY TO PROCEED WITH TENANT PERMITS.
Electrical Service Inspection Passed 3/23/2017 3/22/2017 03/22/2017
Misc
Resolved
03/22/2017
SERVICE RLEASED CONTINGENT ON G.E.C. BEING CAD-WELDED TO GROUND ROD PER APPROVED DRAWING
Rough Framing Inspection - Commercial Passed 1/27/2017 04/02/2017
Misc
Resolved
04/02/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING AT EXTERIOR WALLS AND PILASTERS
Underslab Plumbing Inspection - Commercial Passed 11/11/2016 04/02/2017
Misc
Resolved
04/02/2017
6" PVC ROOF DRAIN PIPE TO BE CAST INTO BUILDING GRADE BEAM/FOOTING AT
Misc
Resolved
04/02/2017
4" SANITARY BUILDING SEWER FROM BUILDING ENTRY TO EAST 35';
Misc
Resolved
04/02/2017
OK TO COVER WHEN READY 4" PVC UNDER SLAB SANITARY DRAIN, WASTE, & VENT PIPING ON (B.25) FROM (7.1) TO (9) + BRANCH TO FD-1 AT LANDLORD'S RM NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM
Underground Electrical Inspection - Commercial Passed 3/2/2017 04/02/2017
Misc
Resolved
04/02/2017
SITE ELECTRICAL TRENCHED CONDUIT: FROM PERMIT PRINT MARK (2) TO (3) TO (4) APPROX 30% COVERED BEFORE INSPECTION -- 70% APPROVED; WITHIN 20' OF/AT J.B. AT (9); FROM (3) TO (10); FROM (10) TO (11); FROM (4) TO (8); FROM (5) TO (6) TO (7) TO (9); FROM PERMIT PRINT MARK (1) TO (2) SUBSTANTIALLY COVERED -- NOT APPROVED.
Misc
Resolved
04/02/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT PRINT MARKS: #1; 2; 4; 9;
Alarm Test Partial 5/5/2017 05/05/2017
Sprinkler - Flow Test Passed 5/5/2017 05/05/2017
Occupancy Inspection - Planning Passed 05/31/2017
Occupancy Inspection - Fire Temporary C of O 5/31/2017 05/31/2017
Alarm Test Passed 5/30/2017 05/31/2017
Occupancy Inspection - Fire Temporary C of O 5/31/2017 05/31/2017
Occupancy Inspection - Water Utilities Passed 05/31/2017
Final Inspection - Commercial Failed 5/31/2017 5/31/2017 05/31/2017
Misc
Corrective Action Required
05/31/2017
HANDRAILS REQUIRED AT SIDEWALK STAIR NORTH OF NORTH END OF BUILDING. DECORATIVE STONEWORK IN PROGRESS WEST AND NORTH OF THE BUILDING
Misc
Corrective Action Required
05/31/2017
Misc
Corrective Action Required
05/31/2017
ROOFTOP GAS PIPING: - DIRT LEG CAPS MUST CLEAR ROOF SURFACE FOR REMOVAL AND REPLACEMENT AND MAINTENANCE - PIPE CLAMPS MISSING AT SOME PIPE SUPPORTS
Final Inspection - Commercial Partial 6/6/2017 06/06/2017
Misc
Corrective Action Required
06/05/2017
PERMANENT COMPLIANT HANDRAILS REQUIRED AT SIDEWALK STAIRS AT NW MAIN ENTRANCE AND AT NORTH OF NORTH END OF BUILDING.
Misc
Resolved
06/06/2017
Misc
Resolved
06/06/2017
ROOFTOP GAS PIPING: - DIRT LEG CAPS MUST CLEAR ROOF SURFACE FOR REMOVAL AND REPLACEMENT AND MAINTENANCE - PIPE CLAMPS MISSING AT SOME PIPE SUPPORTS
Gas Piping Inspection - Commercial Passed 6/6/2017 06/06/2017
Misc
Resolved
06/06/2017
IFGC 407.2 & 415; IRC G2423 SUPPORT OF HORIZONTAL RUNS OF RIGID STEEL PIPING: SPACING OF BLOCKS/HANGERS -- : 1/2" PIPE -- 6' MAX SPACING; 3/4" OR 1" PIPE -- 8' MAX SPACING; 1-1/4" OR LARGER PIPE -- 10' MAX SPACING. SUPPORT AT 90'S, TEES, AND JOINTS. ENSURE PIPE IS STRAPPED AT ALL BLOCKS
Misc
Resolved
06/06/2017
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED AND RE-INSTALLED FOR CLEANING.
Misc
Resolved
06/06/2017
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS.
Investigation Inspection Complete 7/7/2017 09/19/2017
Final Inspection - Commercial Passed 9/19/2017 at 10:20 AM 09/19/2017
Misc
Resolved
09/19/2017
PERMANENT COMPLIANT HANDRAILS REQUIRED AT SIDEWALK STAIRS AT NW MAIN ENTRANCE AND AT NORTH OF NORTH END OF BUILDING.
Documents & Images
Date Uploaded File Type Document Name
10/29/2015 Letter Fire Building Plan Review
11/17/2015 Letter Codes P/R Corrections Document
12/15/2015 Letter Fire Building Plan Review
12/16/2015 Letter Codes P/R Corrections Document
07/29/2016 SF - H&M - Special Inspections Letter
08/16/2016 Letter Fire (Sprinkler) Plan Review
08/22/2016 Receipt Receipt for transaction: 2016-005548
08/23/2016 Letter Codes Building Permit
09/01/2016 Letter Fire Building Plan Review
09/09/2016 Letter Fire Building Plan Review
09/14/2016 Letter Fire Building Plan Review
09/19/2016 Letter Inspection Summary
09/20/2016 Letter Inspection Summary
09/21/2016 Letter Inspection Summary
09/22/2016 Letter Inspection Summary
09/23/2016 Letter Inspection Summary
09/27/2016 Letter Inspection Summary
09/28/2016 Letter Inspection Summary
09/29/2016 Letter Inspection Summary
09/30/2016 Letter Inspection Summary
10/04/2016 Letter Inspection Summary
10/11/2016 Letter Fire Building Plan Review
10/28/2016 Receipt Receipt for transaction: 2016-006629
10/28/2016 Letter Codes Building Permit
11/03/2016 Letter Inspection Summary
11/08/2016 Letter Inspection Summary
11/09/2016 Letter Fire (Sprinkler) Plan Review
11/09/2016 Letter Inspection Summary
11/11/2016 Letter Inspection Summary
11/11/2016 Letter Inspection Summary
11/14/2016 Letter Inspection Summary
11/15/2016 Letter Inspection Summary
11/21/2016 Letter Inspection Summary
11/23/2016 Letter Inspection Summary
11/29/2016 Letter Inspection Summary
12/02/2016 Letter Inspection Summary
12/27/2016 Letter Inspection Summary
12/28/2016 Letter Inspection Summary
01/09/2017 Letter Fire (Alarm) Plan Review Notice
01/09/2017 Letter Fire (Alarm) Plan Review Notice
01/12/2017 Letter Inspection Summary
01/17/2017 Letter Fire (Alarm) Plan Review Notice
01/17/2017 Letter Fire (Alarm) Plan Review Notice
01/17/2017 Letter Fire (Alarm) Plan Review Notice
01/20/2017 Letter Fire (Alarm) Plan Review Notice
01/27/2017 Letter Inspection Summary
01/31/2017 Letter Inspection Summary
02/22/2017 Letter Inspection Summary
02/23/2017 Letter Inspection Summary
02/24/2017 Letter Inspection Summary
02/27/2017 Letter Inspection Summary
03/01/2017 Letter Inspection Summary
03/02/2017 Letter Inspection Summary
03/07/2017 Letter Inspection Summary
03/22/2017 Letter Inspection Summary
05/31/2017 Letter Inspection Summary
09/19/2017 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home