Permit Application Status

PRCOM20151723


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20151723
Building Permit - Commercial
Certificate of Occupancy
ROCKY TOP HOLDINGS LLC
CHANGE OF TENANT
TENANT FINISH FOR NEW SANDWICH RESTAURANT
07/29/2015
10/13/2015
12/18/2015
Locations
Contacts
ACT CONSTRUCTION , Address:350 MCDONNELL STREET, Phone:(972) 436-1144  
SET POINT MECHANICAL LLC, Address:PO BOX 24011, Phone:(913) 213-9465  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
MAYES PLUMBING INC, Address:501 S MCCLEARY RD STE A, Phone:(816) 792-5400  
ARIZADO DESIGN, Address:1255 W RIO SALADO PARKWAY, SUITE 207, Phone:(480) 268-2900  
PAUL MCMAHON, Address:9003 W 149TH ST  
ROCKY TOP HOLDINGS LLC, Address:244 W MILL ST STE 101  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 10/27/2015 10/27/2015
Joe Dir
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
10/27/2015

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. FIRE SPRINKLER SYSTEM SHALL HAVE A CURRENT SERVICE TAG ON THE RISER. VERIFIED AT INSPECTION
Licensed Contractors Approved 08/10/2015 10/09/2015
Joe Frogge
LC - General Contractor
Resolved
10/09/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
10/09/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Building Plan Review Approved with Conditions 08/10/2015 09/14/2015
Joe Frogge
Health Dept Inspection
Corrective Action Required
09/14/2015

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action Required: Comment is for informational purposes.
Health Dept Review
Resolved
09/14/2015

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action Required: Comment is for informational purposes.
Health Department Review Approved 08/20/2015
Joe Frogge
Fire Plan Review Approved with Conditions 08/10/2015 08/04/2015
Joe Dir
Misc
Corrective Action Required
08/04/2015

Duct detection required for AHU-1, to be connected to the alarm system as a supervisory signal. verified on inspection
Posting of occupant load
Corrective Action Required
08/04/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Post the occupant load in the dining area (44) verified on inspection
Construction documents for fire alarm systems
Corrective Action Required
08/04/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for any alterations to the alarm system within the space. For information purposes
Address numbers required
Corrective Action Required
08/04/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Post the suite address on all doors leading into the space / suite. verified on inspection
Construction documents - Fire protection systems
Corrective Action Required
08/04/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provied shop drawings for any alterations of the sprinkler system within the space For information purposes
Installation acceptance testing
Corrective Action Required
08/04/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Acceptance testing required for the alarm system alterations and the type-1 hood system. To schedule a test please call 816-969-1300 For information purposes
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
08/04/2015

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Sprinkler system required to have a current service tag on the riser. Verified on inspection
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
08/04/2015

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Provide a K-Class fire extinguisher for the Type -1 hood system. Verified on inspection
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/04/2015

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Provide (1) 2A-10BC (5 pound) fire extinguisher Verified on inpsection
Misc
Corrective Action Required
08/04/2015

Walk-in coolers required to have sprinkler heads installed. For information purposes, verified on inspection
08/04/2015

Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $1,429.75 $1,429.75 Paid 10/13/2015
8331507-Sewer Connection Fee $210.00 $210.00 Paid 10/13/2015
8331506-EFHB Maybrook, Full $298.27 $298.27 Paid 10/13/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 10/20/2015 at 12:00 AM 10/20/2015
In-wall Inspection Passed 10/30/2015 10/30/2015 at 12:00 AM 10/30/2015
Underground Plumbing Inspection - Commercial Passed 11/9/2015 at 12:00 AM 11/09/2015
Above Ceiling Inspection Not Ready 11/17/2015 at 12:00 AM 11/17/2015
Above Ceiling Inspection Passed 12/1/2015 12/1/2015 at 12:00 AM 12/01/2015
Alarm Test Passed 12/8/2015 at 12:00 AM 12/08/2015
Occupancy Inspection - Fire Passed 12/8/2015 at 12:00 AM 12/08/2015
Gas Piping Inspection - Commercial Passed 12/8/2015 at 12:00 AM 12/08/2015
Occupancy Inspection - Codes Commercial Temporary C of O 12/8/2015 at 12:00 AM 12/08/2015
Misc
Corrective Action Required
12/08/2015
-SECURE FLEXIBLE RACEWAY WITHN 12" OF THE OVEN DISCONNECT -PROTECT WATER SUPPLY TO BEVERAGE DISPENSER AND ICE MAKER
Occupancy Inspection - Codes Commercial Failed 12/16/2015 12/16/2015 12/16/2015
Misc
Corrective Action Required
12/08/2015
-SECURE FLEXIBLE RACEWAY WITHN 12" OF THE OVEN DISCONNECT -PROTECT WATER SUPPLY TO BEVERAGE DISPENSER AND ICE MAKER
Occupancy Inspection - Codes Commercial Full C of O 12/18/2015 12/18/2015 12/18/2015
Misc
Resolved
12/18/2015
-SECURE FLEXIBLE RACEWAY WITHN 12" OF THE OVEN DISCONNECT -PROTECT WATER SUPPLY TO BEVERAGE DISPENSER AND ICE MAKER
Documents & Images
Date Uploaded File Type Document Name
08/04/2015 Letter Fire Building Plan Review
08/06/2015 Letter Codes P/R Corrections Document
08/20/2015 Letter Codes P/R Corrections Document
10/09/2015 Letter Codes Plan Review Conditions
10/13/2015 Receipt Receipt for transaction: 2015-005728
10/13/2015 Letter Codes Building Permit
10/20/2015 Letter Inspection Summary
10/27/2015 Letter Fire (Sprinkler) Plan Review
10/30/2015 Letter Inspection Summary
11/05/2015 Approval to remove grease trap
11/09/2015 Letter Inspection Summary
11/17/2015 Letter Inspection Summary
12/01/2015 Letter Inspection Summary
12/08/2015 Letter Codes Temporary Certificate of Occupancy
12/16/2015 Letter Inspection Summary
12/18/2015 Letter Field Certificate of Occupancy
12/21/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home