Permit Application Status

PRCOM20151156


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20151156
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
NEW TENANT FINISH
TENANT INFILL FOR 30 MED-SURG. PATIENT ROOMS
05/26/2015
06/15/2015
12/02/2015
12/16/2015
Locations
Contacts
JE DUNN CONSTRUCTION CO, Address:120 S CENTRAL AVE STE 350, Phone:(816) 474-8600  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
SHAW ELECTRIC COMPANY, Address:3600 FULLER, Phone:(816) 921-0033  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
ACI BOLAND, Address:1421 EAST 104TH ST; SUITE 100, Phone:(816) 763-9600  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/31/2015
Joe Dir
Sprinkler Plan Review Released for Construction 07/07/2015
Joe Dir
Fire Plan Review Approved with Conditions 06/18/2015 06/11/2015
Joe Dir
Misc
Corrective Action Required
06/11/2015

Duct detection required on units over 2,000 cfm. Show on alarm plans
Construction documents for fire alarm systems
Corrective Action Required
06/11/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Submit alarm plans for approval
Construction documents - Fire protection systems
Corrective Action Required
06/11/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Submit sprinkler plans for approval
Misc
Corrective Action Required
06/11/2015

Provide med gas certification
Licensed Contractors Approved 06/11/2015 06/11/2015
Joe Frogge
Building Plan Review Approved 06/18/2015 06/11/2015
Joe Frogge
Misc
Resolved
06/11/2015

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" at latch side of door approaches in patient rooms where opening into corridor. 6/11/15 - qualifies for exception as described in letter datd 6/11
Miscellaneous Correction
Resolved
06/11/2015

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle with 25' of new roof top HVAC equipment. 6/11/15 - receptacles are existing as installed in previous project. As stated on letter dated 6/11/15
Miscellaneous Correction
Resolved
06/11/2015

2012 IMC 607.5.2 Fire Barriers. Ducts and air transfer openings that penetrate fire barriers shall be protected with listed fire dampers installed in accordance with their listing. Ducts and air transfer openings shall not penetrate exit enclosures and exit passageways except as permitted by Sections 1022.5 and 1023.6, respectively, of the International Building Code. (see code for exceptions) 2012 IMC 607.5.4 Corridors/smoke barriers. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a smoke barrier wall or a corridor enclosure required to have smoke and draft control doors with the International Building Code. Smoke dampers and smoke damper actuation methods shall comply with Section 607.5.4.1. Action required: Provide fire dampers at penetrations of 1 hour rated walls including at 1 hour rated smoke barrier. Provide smoke dampers at penetrations of smoke barriers. 6/11/15 - qualifies for exception as described in letter datd 6/11
Fire Plan Review Approved with Conditions 06/05/2015 06/04/2015
Brian Austerman
Misc
Corrective Action Required
06/04/2015

Duct detection required on units over 2,000 cfm. Show on alarm plans
Construction documents for fire alarm systems
Corrective Action Required
06/04/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Submit alarm plans for approval
Construction documents - Fire protection systems
Corrective Action Required
06/04/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Submit sprinkler plans for approval
Misc
Corrective Action Required
06/04/2015

Provide med gas certification
Building Plan Review Rejected 06/05/2015 06/01/2015
Joe Frogge
Misc
Corrective Action Required
06/01/2015

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" at latch side of door approaches in patient rooms where opening into corridor.
Miscellaneous Correction
Corrective Action Required
06/01/2015

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle with 25' of new roof top HVAC equipment.
Miscellaneous Correction
Corrective Action Required
06/01/2015

2012 IMC 607.5.2 Fire Barriers. Ducts and air transfer openings that penetrate fire barriers shall be protected with listed fire dampers installed in accordance with their listing. Ducts and air transfer openings shall not penetrate exit enclosures and exit passageways except as permitted by Sections 1022.5 and 1023.6, respectively, of the International Building Code. (see code for exceptions) 2012 IMC 607.5.4 Corridors/smoke barriers. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a smoke barrier wall or a corridor enclosure required to have smoke and draft control doors with the International Building Code. Smoke dampers and smoke damper actuation methods shall comply with Section 607.5.4.1. Action required: Provide fire dampers at penetrations of 1 hour rated walls including at 1 hour rated smoke barrier. Provide smoke dampers at penetrations of smoke barriers.
Licensed Contractors Approved 06/05/2015 05/26/2015
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $15,057.58 $15,057.58 Paid 06/15/2015
7232302-Saint Lukes Road and Bridge Escrow $6,814.20 $6,814.20 Paid 06/15/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 7/13/2015 7/13/2015 at 12:00 AM 07/13/2015
Misc
Partial Correction
07/13/2015
OK TO TOP-OUT WALLS 4' WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: (C)/(3) TO (C)/(4.5); (B.3)/(3) TO (C.1)/(3);
Misc
Partial Correction
07/13/2015
In-wall Inspection Partial 7/14/2015 7/14/2015 at 12:00 AM 07/14/2015
Misc
Partial Correction
07/13/2015
OK TO TOP-OUT WALLS 4' WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: (C)/(3) TO (C)/(4.5); (B.3)/(3) TO (C.1)/(3); (B)/(2.8) TO (B)/(4.5);
Misc
Partial Correction
07/14/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5A015A;
In-wall Inspection Partial 7/22/2015 7/22/2015 at 12:00 AM 07/22/2015
Misc
Partial Correction
07/14/2015
OK TO TOP-OUT WALLS 4' WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: (C)/(3) TO (C)/(4.5); (B.3)/(3) TO (C.1)/(3); (B)/(2.8) TO (B)/(4.5);
Misc
Partial Correction
07/14/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5A015A; 5A007 THRU 009; 011 THRU 019;
In-wall Inspection Partial 7/24/2015 at 12:00 AM 07/24/2015
Misc
Partial Correction
07/24/2015
OK TO TOP-OUT WALLS 4' WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: (C)/(3) TO (C)/(4.5); (B.3)/(3) TO (C.1)/(3); (B)/(2.8) TO (B)/(4.5);
Misc
Partial Correction
07/24/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5A015A; 5A007 THRU 5A021; CORR 081 (1) THRU (5) EAST WALL; CORR 102 (1) THRU (5) WEST WALL; SPACE 070A; 087; NOTE: PATIENT ROOMS PRESENTLY EXCLUDE SHOWERS UNTIL COMPLETED AND APPROVED.
In-wall Inspection Partial 7/30/2015 7/30/2015 at 12:00 AM 07/30/2015
Misc
Resolved
07/30/2015
OK TO TOP-OUT WALLS 4' WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: (C)/(3) TO (C)/(4.5); (B.3)/(3) TO (C.1)/(3); (B)/(2.8) TO (B)/(4.5);
Misc
Partial Correction
07/24/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5A015A; 5A007 THRU 5A021; CORR 081 (1) THRU (5) EAST WALL; CORR 102 (1) THRU (5) WEST WALL; SPACE 070A; 087; [CORRIDORS 5A081A & 5A102 FROM (1) TO (7.5); PATIENT ROOMS 5A002 - 006 & 023 - 027; 5A068; 069; 081 S; 082; 083; 084; 085; 086; 087; 089; 093; 095; 097; CHASE AT B.2/2.8 NOT READY OK TO COVER SHOWERS AT PATIENT ROOMS: 5A010A - 5A020A;
Rated Assembly Inspection Partial 7/30/2015 at 12:00 AM 07/30/2015
Misc
Partial Correction
07/30/2015
OK TO COVER WHEN READY COMPONENTS OF FIRE-RATED WALLS AT LOCATIONS: FRAMING AND SHAFT LINER BOARD ON (6.1) FROM (B) TO (C);
Rated Assembly Inspection Partial 8/4/2015 8/5/2015 at 12:00 AM 08/05/2015
Misc
Partial Correction
07/30/2015
OK TO COVER WHEN READY COMPONENTS OF FIRE-RATED WALLS AT LOCATIONS: FRAMING AND SHAFT LINER BOARD ON (6.1) FROM (B) TO (C); SHAFT WALLS @ 5A095 N & 097 N;
Misc
Partial Correction
08/05/2015
SMOKE WALL GWB ON (3.5) FROM (A) TO (B) & FROM (C) TO (D);
In-wall Inspection Partial 8/5/2015 8/5/2015 at 12:00 AM 08/05/2015
Misc
Partial Correction
07/30/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5A015A; 5A007 THRU 5A021; CORR 081 (1) THRU (5) EAST WALL; CORR 102 (1) THRU (5) WEST WALL; SPACE 070A; 087; CORRIDORS 5A081A & 5A102 FROM (1) TO (7.5); PATIENT ROOMS 5A002 - 006 & 023 - 027; 5A068; 069; 081 S; 082; 083; 084; 085; 086; 087; 089; 093; 095; 097; [072 - 078; OK TO COVER SHOWERS AT PATIENT ROOMS: 5A010A - 5A020A; 001-009; 021-030; PROVIDE CERTIFICATION THAT ALL FLOOR PENETRATIONS ARE FIRE-STOPPED;
Above Ceiling Inspection Partial 8/5/2015 at 12:00 AM 08/05/2015
Misc
Partial Correction
08/05/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SHOWERS AT 015-017;
Above Ceiling Inspection Partial 8/7/2015 at 12:00 AM 08/08/2015
Misc
Partial Correction
08/08/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SHOWERS AT 015-017; [008-014; 018; 019;
Rated Assembly Inspection Passed 8/10/2015 8/5/2015 at 12:00 AM 08/08/2015
Misc
Partial Correction
08/05/2015
OK TO COVER WHEN READY COMPONENTS OF FIRE-RATED WALLS AT LOCATIONS: FRAMING AND SHAFT LINER BOARD ON (6.1) FROM (B) TO (C); SHAFT WALLS @ 5A095 N & 097 N;
Rated Assembly Inspection Partial 8/7/2015 at 12:00 AM 08/08/2015
Misc
Partial Correction
08/07/2015
OK TO COVER WHEN READY COMPONENTS OF FIRE-RATED WALLS AT LOCATIONS: FRAMING AND SHAFT LINER BOARD ON (6.1) FROM (B) TO (C); SHAFT WALLS @ 5A095 N & 097 N; 5A095 E,S,W BOTH FACES + N WALL; 5A096 E,N,W BOTH FACES + S WALL; 5A097 E,S,W BOTH FACES + N WALL + FIRE CAULK @ SW CORNER;
Misc
Partial Correction
08/08/2015
SMOKE WALL GWB ON (3.5) FROM (A) TO (B) TO (C) TO (D);
Above Ceiling Inspection Partial 8/12/2015 8/12/2015 at 12:00 AM 08/12/2015
Misc
Partial Correction
08/08/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SHOWERS AT 008-014; 015-017; 018; 019; [006; 020-026;
Above Ceiling Inspection Partial 8/14/2015 8/14/2015 at 12:00 AM 08/14/2015
Misc
Partial Correction
08/12/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SHOWERS: 006; 008-026; [003; 004; 005; 027;
Misc
Partial Correction
08/14/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS AT SOFFITS @ FOLLOWING LOCATIONS: NURSE STATION 5A080; C.2/4.5; A.8/4.5;
Rated Assembly Inspection Partial 8/14/2015 8/14/2015 at 12:00 AM 08/14/2015
Misc
Partial Correction
08/08/2015
OK TO COVER WHEN READY COMPONENTS OF FIRE-RATED WALLS AT LOCATIONS: FRAMING AND SHAFT LINER BOARD ON (6.1) FROM (B) TO (C); SHAFT WALLS @ 5A095 N & 097 N; 5A095 E,S,W BOTH FACES + N WALL; 5A096 E,N,W BOTH FACES + S WALL; 5A097 E,S,W BOTH FACES + N WALL + FIRE CAULK @ SW CORNER; [076, 077, 078 INTERIOR FACE ONLY; 074 & 075 S WALL;
In-wall Inspection Partial 8/7/2015 at 12:00 AM 08/19/2015
Misc
Partial Correction
08/08/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5A015A; 5A007 THRU 5A021; CORR 081 (1) THRU (5) EAST WALL; CORR 102 (1) THRU (5) WEST WALL; SPACE 070A; 087; CORRIDORS 5A081A & 5A102 FROM (1) TO (7.5); PATIENT ROOMS 5A002 - 006 & 023 - 027; 5A068; 069; 072; 078; 081 S; 082; 083; 084; 085; 086; 087; 089; 093; 095; 097; [ OK TO COVER SHOWERS AT PATIENT ROOMS: 5A010A - 5A020A; 001-009; 021-030; PROVIDE CERTIFICATION THAT ALL FLOOR PENETRATIONS ARE FIRE-STOPPED;
Misc
Partial Correction
08/08/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: BATHROOMS @ 028-030;
Rated Assembly Inspection Partial 8/18/2015 8/18/2015 at 12:00 AM 08/21/2015
Misc
Partial Correction
08/14/2015
OK TO COVER WHEN READY COMPONENTS OF FIRE-RATED WALLS AT LOCATIONS: FRAMING AND SHAFT LINER BOARD ON (6.1) FROM (B) TO (C); SHAFT WALLS @ 5A095 N & 097 N; 5A095 E,S,W BOTH FACES + N WALL; 5A096 E,N,W BOTH FACES + S WALL; 5A097 E,S,W BOTH FACES + N WALL + FIRE CAULK @ SW CORNER; 076, 077, 078 INTERIOR FACE ONLY; 074 & 075 S WALL; [CORR FACE ON (B) & (C) FROM (6) TO (7);
Rated Assembly Inspection Partial 8/21/2015 at 12:00 AM 08/21/2015
Misc
Partial Correction
08/21/2015
OK TO COVER WHEN READY COMPONENTS OF FIRE-RATED WALLS AT LOCATIONS: FRAMING AND SHAFT LINER BOARD ON (6.1) FROM (B) TO (C); SHAFT WALLS @ 5A095 N & 097 N; 5A095 E,S,W BOTH FACES + N WALL; 5A096 E,N,W BOTH FACES + S WALL; 5A097 E,S,W BOTH FACES + N WALL + FIRE CAULK @ SW CORNER; 076, 077, 078 INTERIOR FACE ONLY; 074 & 075 S WALL; [CORR FACE ON (B) & (C) FROM (6) TO (7); 5A001 VERTICAL SHAFT AT N WALL;
In-wall Inspection Partial 8/19/2015 at 12:00 AM 08/21/2015
Misc
Partial Correction
08/19/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5A015A; 5A007 THRU 5A021; CORR 081 (1) THRU (5) EAST WALL; CORR 102 (1) THRU (5) WEST WALL; SPACE 070A; 087; CORRIDORS 5A081A & 5A102 FROM (1) TO (7.5); PATIENT ROOMS 5A002 - 006 & 023 - 027; 5A068; 069; 072; 078; 081 S; 082; 083; 084; 085; 086; 087; 089; 093; 095; 097; [028 AFTER P1 CORRECTS COPPER-TO-STEEL CONTACT/PROXIMITY ON THREE COPPER PIPE RUNS AT SOUTH WALL; 029; 030 N WALL; OK TO COVER SHOWERS AT PATIENT ROOMS: 5A010A - 5A020A; 001-009; 021-030; PROVIDE CERTIFICATION THAT ALL FLOOR PENETRATIONS ARE FIRE-STOPPED;
In-wall Inspection Partial 8/21/2015 at 12:00 AM 08/21/2015
Above Ceiling Inspection Partial 8/24/2015 8/24/2015 at 12:00 AM 08/24/2015
Misc
Partial Correction
08/14/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SHOWERS: 003-006; 008-027; [001; 002; 028; 030
Misc
Partial Correction
08/14/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS AT SOFFITS @ FOLLOWING LOCATIONS: NURSE STATION 5A080; C.2/4.5; A.8/4.5;
Rated Assembly Inspection Partial 8/26/2015 8/26/2015 at 12:00 AM 08/26/2015
Misc
Partial Correction
08/26/2015
OK TO COVER WHEN READY COMPONENTS OF FIRE-RATED WALLS AT LOCATIONS: FRAMING AND SHAFT LINER BOARD ON (6.1) FROM (B) TO (C); SHAFT WALLS @ 5A095 N & 097 N; 5A095 E,S,W BOTH FACES + N WALL; 5A096 E,N,W BOTH FACES + S WALL; 5A097 E,S,W BOTH FACES + N WALL + FIRE CAULK @ SW CORNER; 076, 077, 078 INTERIOR FACE ONLY; 074 & 075 S WALL; CORR FACE ON (B) & (C) FROM (6) TO (7); 5A001 VERTICAL SHAFT AT N WALL; {WALL @ 5A029 N & 030 S, BUT HARD CORNER REQUIRED AT INTERSECION W/ CORRIDOR WALL; AT CORR 5A102 BULKHEAD AT DOUBLE DOOR NOT READY FOR INSPECTION;
Above Ceiling Inspection Partial 8/26/2015 at 12:00 AM 08/26/2015
Misc
Partial Correction
08/24/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SHOWERS: 003-006; 008-027; [001; 002; 028; 030; 029
Misc
Partial Correction
08/24/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS AT SOFFITS @ FOLLOWING LOCATIONS: NURSE STATION 5A080; C.2/4.5; A.8/4.5;
Rated Assembly Inspection Partial 8/28/2015 8/28/2015 at 12:00 AM 08/28/2015
Misc
Partial Correction
08/26/2015
OK TO COVER WHEN READY COMPONENTS OF FIRE-RATED WALLS AT LOCATIONS: FRAMING AND SHAFT LINER BOARD ON (6.1) FROM (B) TO (C); SHAFT WALLS @ 5A095 N & 097 N; 5A095 E,S,W BOTH FACES + N WALL; 5A096 E,N,W BOTH FACES + S WALL; 5A097 E,S,W BOTH FACES + N WALL + FIRE CAULK @ SW CORNER; 076, 077, 078 INTERIOR FACE ONLY; 074 & 075 S WALL; CORR FACE ON (B) & (C) FROM (6) TO (7); 5A001 VERTICAL SHAFT AT N WALL; WALL @ 5A029 N & 030 S INCLUDING HARD CORNER AT INTERSECION W/ CORRIDOR WALL; CORR 5A102 NORTH BULKHEAD AT DOUBLE DOOR; 5A086 NE AT VERTICAL MECHANICAL CHASE: FRAMING + SHAFT LINER OK TO COVER W/ 5/8" TYPE X GWB
Rated Assembly Inspection Partial 8/31/2015 8/31/2015 at 12:00 AM 08/31/2015
Misc
Partial Correction
08/28/2015
OK TO COVER WHEN READY COMPONENTS OF FIRE-RATED WALLS AT LOCATIONS: FRAMING AND SHAFT LINER BOARD ON (6.1) FROM (B) TO (C); SHAFT WALLS @ 5A095 N & 097 N; 5A095 E,S,W BOTH FACES + N WALL; 5A096 E,N,W BOTH FACES + S WALL; 5A097 E,S,W BOTH FACES + N WALL + FIRE CAULK @ SW CORNER; 076, 077, 078 INTERIOR FACE ONLY; 074 & 075 S WALL; CORR FACE ON (B) & (C) FROM (6) TO (7); 5A001 VERTICAL SHAFT AT N WALL; WALL @ 5A029 N & 030 S INCLUDING HARD CORNER AT INTERSECION W/ CORRIDOR WALL; CORR 5A102 NORTH BULKHEAD AT DOUBLE DOOR; 5A086 NE AT VERTICAL MECHANICAL CHASE OK TO COVER: FRAMING + SHAFT LINER; 5/8" TYPE X GWB AT CORRIDOR RECESS ON (2.8) FROM (A.9) TO (B.1);
Rated Assembly Inspection Partial 9/1/2015 at 12:00 AM 09/01/2015
Misc
Partial Correction
09/01/2015
OK TO COVER WHEN READY COMPONENTS OF FIRE-RATED WALLS AT LOCATIONS: FRAMING AND SHAFT LINER BOARD ON (6.1) FROM (B) TO (C); SHAFT WALLS @ 5A095 N & 097 N; 5A095 E,S,W BOTH FACES + N WALL; 5A096 E,N,W BOTH FACES + S WALL; 5A097 E,S,W BOTH FACES + N WALL + FIRE CAULK @ SW CORNER; 076, 077, 078 INTERIOR FACE ONLY; 074 & 075 S WALL; CORR FACE ON (B) & (C) FROM (6) TO (7); 5A001 VERTICAL SHAFT AT N WALL; WALL @ 5A029 N & 030 S INCLUDING HARD CORNER AT INTERSECION W/ CORRIDOR WALL; CORR 5A102 NORTH BULKHEAD AT DOUBLE DOOR; 5A086 NE AT VERTICAL MECHANICAL CHASE OK TO COVER: FRAMING + SHAFT LINER; 5/8" TYPE X GWB AT CORRIDOR RECESS ON (2.8) FROM (A.9) TO (B.1) + 5/8" TYPE X AT BOTH WALL PLANES IN 5A086;
In-wall Inspection Partial 9/1/2015 at 12:00 AM 09/01/2015
Misc
Partial Correction
09/01/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5A015A; 5A007 THRU 5A021; CORR 081 (1) THRU (5) EAST WALL; CORR 102 (1) THRU (5) WEST WALL; SPACE 070A; 087; CORRIDORS 5A081A & 5A102 FROM (1) TO (7.5); PATIENT ROOMS 5A002 - 006 & 023 - 027; 5A068; 069; 072; 078; 081 S; 082; 083; 084; 085; 086; 087; 089; 093; 095; 097; 028; 029; 030 N WALL; 5A085 SE AT MECH SHAFT OK TO COVER SHOWERS AT PATIENT ROOMS: 5A010A - 5A020A; 001-009; 021-030; PROVIDE CERTIFICATION THAT ALL FLOOR PENETRATIONS ARE FIRE-STOPPED;
Above Ceiling Inspection Partial 9/25/2015 9/25/2015 at 12:00 AM 09/25/2015
Misc
Partial Correction
08/26/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SHOWERS: 003-006; 008-027; [001; 002; 028; 030; 029
Misc
Partial Correction
08/26/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS AT SOFFITS @ FOLLOWING LOCATIONS: NURSE STATION 5A080; C.2/4.5; A.8/4.5;
Misc
Partial Correction
09/25/2015
REMOVE ALL TEMPORARY ELECTRICAL WIRING FROM ABOVE CEILING; THEN OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PATIENT ROOMS 5A008-5A021;
Above Ceiling Inspection Partial 10/1/2015 at 12:00 AM 10/01/2015
Misc
Partial Correction
10/01/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SHOWERS: 003-006; 008-027; [001; 002; 028; 030; 029
Misc
Partial Correction
10/01/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS AT SOFFITS @ FOLLOWING LOCATIONS: NURSE STATION 5A080; C.2/4.5; A.8/4.5;
Misc
Partial Correction
10/01/2015
REMOVE ALL TEMPORARY ELECTRICAL WIRING FROM ABOVE CEILING; THEN OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PATIENT ROOMS 5A008-5A021; 5A068; 069; 081A S OF DOOR (5A081A); 082; 083; 084; 085; 087; 089; 095; 097; 102 S OF DOOR (5A102); PATIENT ROOMS 5A001-5A007 AND 5A022-5A030 EXCEPT BATHROOMS; PATIENT ROOM BATHROOMS: COMPLETE EXHAUST DUCT & GRILLES; COMPLETE SPRINKLER HEADS 102 N OF DOOR (5A102) AND 081A N OF DOOR (5A081A) NOT READY; ELECTRICAL WORK IN PROGRESS -- OPEN BOXES
Above Ceiling Inspection Partial 10/8/2015 at 12:00 AM 10/08/2015
Misc
Partial Correction
10/08/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SHOWERS: 003-006; 008-027; [001; 002; 028; 030; 029
Misc
Partial Correction
10/08/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS AT SOFFITS @ FOLLOWING LOCATIONS: NURSE STATION 5A080; C.2/4.5; A.8/4.5;
Misc
Partial Correction
10/08/2015
REMOVE ALL TEMPORARY ELECTRICAL WIRING FROM ABOVE CEILING; THEN OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PATIENT ROOMS 5A008-5A021; 5A068; 069; 081A S OF DOOR (5A081A); 082; 083; 084; 085; 087; 089; 095; 097; 102 S OF DOOR (5A102); PATIENT ROOMS 5A001-5A007 AND 5A022-5A030 EXCEPT BATHROOMS; PATIENT ROOM BATHROOMS: COMPLETE EXHAUST DUCT & GRILLES; COMPLETE SPRINKLER HEADS 102 N OF DOOR (5A102) AND 081A N OF DOOR (5A081A) NOT READY; ELECTRICAL WORK IN PROGRESS -- OPEN BOXES
Above Ceiling Inspection Partial 10/8/2015 at 12:00 AM 10/08/2015
Misc
Partial Correction
10/08/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SHOWERS: 003-006; 008-027; [001; 002; 028; 030; 029
Misc
Partial Correction
10/08/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS AT SOFFITS @ FOLLOWING LOCATIONS: NURSE STATION 5A080; C.2/4.5; A.8/4.5;
Misc
Partial Correction
10/08/2015
REMOVE ALL TEMPORARY ELECTRICAL WIRING FROM ABOVE CEILING; THEN OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PATIENT ROOMS 5A008-5A021; 5A068; 069; 081A S OF DOOR (5A081A); 082; 083; 084; 085; 087; 089; 095; 097; 102 S OF DOOR (5A102); 086; PATIENT ROOMS 5A001-5A007 AND 5A022-5A030 EXCEPT BATHROOMS; PATIENT ROOM BATHROOMS: COMPLETE EXHAUST DUCT & GRILLES; COMPLETE SPRINKLER HEADS 102 N OF DOOR (5A102) AND 081A N OF DOOR (5A081A) NOT READY; ELECTRICAL WORK IN PROGRESS -- OPEN BOXES
Above Ceiling Inspection Partial 10/15/2015 10/15/2015 at 12:00 AM 10/15/2015
Misc
Resolved
10/15/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SHOWERS: 003-006; 008-027; [001; 002; 028; 030; 029
Misc
Resolved
10/15/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS AT SOFFITS @ FOLLOWING LOCATIONS: NURSE STATION 5A080; C.2/4.5; A.8/4.5;
Misc
Partial Correction
10/08/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PATIENT ROOMS 5A008-5A021; 5A068; 069; 081A S OF DOOR (5A081A); 082; 083; 084; 085; 087; 089; 095; 097; 102 S OF DOOR (5A102); 086; PATIENT ROOMS 5A001-5A007 AND 5A022-5A030 EXCEPT BATHROOMS; ALL REMAINING ACT CEILING AREAS EXCEPT CORRIDOR 5A081A OUTSIDE ISOLATION ROOM
In-wall Inspection Passed 9/1/2015 at 12:00 AM 10/15/2015
Rated Assembly Inspection Passed 9/1/2015 at 12:00 AM 10/15/2015
Above Ceiling Inspection Partial 10/22/2015 10/22/2015 at 12:00 AM 10/22/2015
Misc
Partial Correction
10/15/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PATIENT ROOMS 5A008-5A021; 5A068; 069; 081A S OF DOOR (5A081A); 082; 083; 084; 085; 087; 089; 095; 097; 102 S OF DOOR (5A102); 086; PATIENT ROOMS 5A001-5A007 AND 5A022-5A030 EXCEPT BATHROOMS; ALL REMAINING ACT CEILING AREAS INCLUDING CORRIDOR 5A081A OUTSIDE ISOLATION ROOM
Miscellaneous Inspection Passed 12/7/2015 at 12:00 AM 12/07/2015
Alarm Test Passed 12/7/2015 at 12:00 AM 12/07/2015
Occupancy Inspection - Codes Commercial Temporary C of O 12/7/2015 at 12:00 AM 12/07/2015
Misc
Corrective Action Required
12/07/2015
FIVE EMERGENCY CIRCUIT ELECTRICAL RECEPTACLES (WITHIN 6' OF EDGE OF SINKS) FOR WATER COOLERS AND REFRIGERATORS AT 5A078, 081 AND 083 NOT GFCI-PROTECTED. EXCEPTION ALLOWABLE IN THIS CASE ONLY IS TO REPLACE DUPLEXES WITH SINGLE RECEPTACLES.
Above Ceiling Inspection Passed 12/7/2015 at 12:00 AM 12/07/2015
Misc
Resolved
12/07/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PATIENT ROOMS 5A008-5A021; 5A068; 069; 081A S OF DOOR (5A081A); 082; 083; 084; 085; 087; 089; 095; 097; 102 S OF DOOR (5A102); 086; PATIENT ROOMS 5A001-5A007 AND 5A022-5A030 EXCEPT BATHROOMS; ALL REMAINING ACT CEILING AREAS INCLUDING CORRIDOR 5A081A OUTSIDE ISOLATION ROOM
Occupancy Inspection - Fire Passed 12/16/2015 12/16/2015
Occupancy Inspection - Codes Commercial Full C of O 12/16/2015 12/16/2015
Misc
Resolved
12/16/2015
FIVE EMERGENCY CIRCUIT ELECTRICAL RECEPTACLES (WITHIN 6' OF EDGE OF SINKS) FOR WATER COOLERS AND REFRIGERATORS AT 5A078, 081 AND 083 NOT GFCI-PROTECTED. EXCEPTION ALLOWABLE IN THIS CASE ONLY IS TO REPLACE DUPLEXES WITH SINGLE RECEPTACLES.
Documents & Images
Date Uploaded File Type Document Name
06/04/2015 Letter Fire Building Plan Review
06/05/2015 Letter Codes P/R Corrections Document
06/12/2015 Letter Fire Building Plan Review
06/12/2015 Letter Codes Plan Review Conditions
06/15/2015 Letter Codes Building Permit
06/15/2015 Receipt Receipt for transaction: 2015-002895
07/07/2015 Letter Fire (Sprinkler) Plan Review
07/13/2015 Letter Inspection Summary
07/14/2015 Letter Inspection Summary
07/22/2015 Letter Inspection Summary
07/24/2015 Letter Inspection Summary
07/30/2015 Letter Inspection Summary
08/05/2015 Letter Inspection Summary
08/08/2015 Letter Inspection Summary
08/12/2015 Letter Inspection Summary
08/14/2015 Letter Inspection Summary
08/18/2015 Letter Inspection Summary
08/19/2015 Letter Inspection Summary
08/21/2015 Letter Inspection Summary
08/24/2015 Letter Inspection Summary
08/26/2015 Letter Inspection Summary
08/28/2015 Letter Inspection Summary
08/31/2015 Letter Inspection Summary
09/01/2015 Letter Inspection Summary
09/25/2015 Letter Inspection Summary
10/01/2015 Letter Inspection Summary
10/08/2015 Letter Inspection Summary
10/08/2015 Letter Inspection Summary
10/15/2015 Letter Inspection Summary
10/22/2015 Letter Inspection Summary
12/07/2015 Letter Codes Temporary Certificate of Occupancy
12/16/2015 Letter Field Certificate of Occupancy
12/17/2015 Letter Codes Final Certificate of Occupancy
12/22/2015 Letter DOC122215-001
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home