Permit Application Status

PRCOM20150869


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20150869
Building Permit - Commercial
Certificate of Occupancy
ROCKY TOP HOLDINGS LLC
NEW TENANT FINISH
TENANT FINISH FOR KARATE STUDIO
04/23/2015
06/05/2015
11/16/2015
08/21/2015
Locations
Contacts
SCHARHAG ARCHITECTS, Address:310 ARMOR RD, #22, Phone:(816) 221-9297  
ROCKY TOP HOLDINGS LLC, Address:244 W MILL ST STE 101  
PHOENIX CONSTRUCTION INC, Address:1305 HOLLY CT, Phone:(816) 716-8208  
4SIGHT GROUP LLC, Address:7920 WARD PKWY, Phone:(816) 802-8400  
BRADLEY-READE INC, Address:810 W 7TH AVE, Phone:(816) 898-2947  
ALWAYS PLUMBING LLC, Address:807 NASHUA ROAD, Phone:(819) 781-7749  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 07/08/2015
Joe Dir
Misc
Corrective Action Required
07/08/2015

No FD Comments
Licensed Contractors Approved 06/19/2015 06/02/2015
Joe Frogge
LC - General Contractor
Corrective Action Required
05/20/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
05/20/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Licensed Contractors Rejected 05/14/2015 06/02/2015
Joe Frogge
LC - General Contractor
Corrective Action Required
05/14/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
05/14/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Building Plan Review Approved 05/28/2015 05/20/2015
Joe Frogge
Miscellaneous Correction
Resolved
05/20/2015

2012 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010. Action required: Update drawings to demonstrate compliance. 5/15/15 - specification note in question has not changed. 5/20/15 - plans corrected
Fire Plan Review Approved with Conditions 05/28/2015 05/20/2015
Development Center
Construction documents for fire alarm systems
Corrective Action Required
05/20/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for any work done to the system
Address numbers required
Corrective Action Required
05/20/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on all doors leading into the space
Construction documents - Fire protection systems
Corrective Action Required
05/20/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Submit sprinkler plans for approval for any work done to the system
Portable fire extinguishers - general
Corrective Action Required
05/20/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type extinguisher
Misc
Corrective Action Required
05/20/2015

5/18/15 No further FD comments
Fire Plan Review Approved with Conditions 05/21/2015 05/18/2015
Brian Austerman
Construction documents for fire alarm systems
Corrective Action Required
05/14/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for any work done to the system
Address numbers required
Corrective Action Required
05/14/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on all doors leading into the space
Construction documents - Fire protection systems
Corrective Action Required
05/14/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Submit sprinkler plans for approval for any work done to the system
Portable fire extinguishers - general
Corrective Action Required
05/14/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type extinguisher
Misc
Corrective Action Required
05/18/2015

5/18/15 No further FD comments
Building Plan Review Rejected 05/21/2015 05/15/2015
Joe Frogge
Misc
Resolved
05/15/2015

Incomplete information. Action required: Label use of each space. Room north of storage not identified. 5/15/15 - labelled as office on new plans
Misc 13
Resolved
05/15/2015

ICC A117.1-209 Section 303 Changes in Level 303.1 General. Changes in level in floor surfaces hall comply with Section 303. Action required: Provide section cut at floor material change (VCT to Wood) to verify compliance with code section cited. 5/15/15 - detail added and compliant
Misc 14
Resolved
05/15/2015

2012 IBC 2408.3 Gymnasiums and basketball courts. Glazing in multipurpose gymnasiums, basketball courts and similar athletic facilities subject to human impact loads shall comply with Category II of CPSC 16 CFR Part 1201 or Class A of ANSI Z97.1. Action required: Specify compliant glazing where facing open gym area. 5/15/15 - clarification note added to drawings
Bldg - Accessibility - Where required 1103.1
Resolved
05/15/2015

2012 IBC 1109.9 Storage. Where fixed or built-in storage elements such as cabinets, coat hooks, shelves, medicine cabinets, lockers, closets and drawers are provided in required accessible spaces, at least 5 percent, but not less than one of each type shall be accessible. Action required: Modify drawings to demonstrate compliance. 5/15/15 - note added to drawings
Miscellaneous Correction
Corrective Action Required
05/14/2015

2012 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010. Action required: Update drawings to demonstrate compliance. 5/15/15 - specification note in question has not changed.
Building Plan Review Rejected 05/05/2015 05/04/2015
Joe Frogge
Misc
Corrective Action Required
05/04/2015

Incomplete information. Action required: Label use of each space. Room north of storage not identified.
Misc 13
Corrective Action Required
05/04/2015

ICC A117.1-209 Section 303 Changes in Level 303.1 General. Changes in level in floor surfaces hall comply with Section 303. Action required: Provide section cut at floor material change (VCT to Wood) to verify compliance with code section cited.
Misc 14
Corrective Action Required
05/04/2015

2012 IBC 2408.3 Gymnasiums and basketball courts. Glazing in multipurpose gymnasiums, basketball courts and similar athletic facilities subject to human impact loads shall comply with Category II of CPSC 16 CFR Part 1201 or Class A of ANSI Z97.1. Action required: Specify compliant glazing where facing open gym area.
Bldg - Accessibility - Where required 1103.1
Corrective Action Required
05/04/2015

2012 IBC 1109.9 Storage. Where fixed or built-in storage elements such as cabinets, coat hooks, shelves, medicine cabinets, lockers, closets and drawers are provided in required accessible spaces, at least 5 percent, but not less than one of each type shall be accessible. Action required: Modify drawings to demonstrate compliance.
Miscellaneous Correction
Corrective Action Required
05/04/2015

2012 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010. Action required: Update drawings to demonstrate compliance.
Licensed Contractors Rejected 05/05/2015 05/04/2015
Joe Frogge
LC - General Contractor
Corrective Action Required
05/04/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
05/04/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 05/05/2015 04/23/2015
Brian Austerman
Construction documents for fire alarm systems
Corrective Action Required
04/23/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for any work done to the system
Address numbers required
Corrective Action Required
04/23/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on all doors leading into the space
Construction documents - Fire protection systems
Corrective Action Required
04/23/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Submit sprinkler plans for approval for any work done to the system
Portable fire extinguishers - general
Corrective Action Required
04/23/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type extinguisher
Zoning Review Approved 05/05/2015 04/23/2015
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $105.50 $105.50 Paid 06/05/2015
8331507-Sewer Connection Fee $30.00 $30.00 Paid 06/05/2015
8331506-EFHB Maybrook, Full $42.61 $42.61 Paid 06/05/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 6/17/2015 at 12:00 AM 06/17/2015
Misc
Corrective Action Required
06/17/2015
-INSTALL EM LIGHT PER PLAN **OK TO ROCK
Underslab Plumbing Inspection - Commercial Passed 6/18/2015 at 12:00 AM 06/18/2015
In-wall Inspection Passed 6/18/2015 6/18/2015 at 12:00 AM 06/18/2015
Misc
Resolved
06/18/2015
-INSTALL EM LIGHT PER PLAN **OK TO ROCK
Occupancy Inspection - Codes Commercial Failed 8/12/2015 8/12/2015 at 12:00 AM 08/12/2015
Misc
Corrective Action Required
08/12/2015
-OBTAIN FIRE APPROVAL -INSTALL RESTROOM SIGNAGE -ADJUST RESTROOM DOORS
Above Ceiling Inspection Passed 8/12/2015 at 12:00 AM 08/12/2015
Alarm Test Failed 8/12/2015 at 12:00 AM 08/12/2015
Occupancy Inspection - Fire Failed 8/12/2015 at 12:00 AM 08/12/2015
Gas Service Inspection - Commercial Passed 8/21/2015 at 12:00 AM 08/21/2015
Occupancy Inspection - Codes Commercial Full C of O 8/21/2015 8/21/2015 at 12:00 AM 08/21/2015
Misc
Corrective Action Required
08/12/2015
-OBTAIN FIRE APPROVAL
Alarm Test Passed 8/21/2015 at 12:00 AM 08/21/2015
Occupancy Inspection - Fire Passed 8/21/2015 8/21/2015 at 12:00 AM 08/21/2015
Documents & Images
Date Uploaded File Type Document Name
04/23/2015 Letter Fire Building Plan Review
05/04/2015 Letter Codes P/R Corrections Document
05/18/2015 Letter Fire Building Plan Review
05/18/2015 Letter Codes P/R Corrections Document
06/02/2015 Letter Codes Plan Review Conditions
06/02/2015 approved constr drawings
06/05/2015 Letter Codes Building Permit
06/05/2015 Receipt Receipt for transaction: 2015-002397
06/17/2015 Letter Inspection Summary
06/18/2015 Letter Inspection Summary
07/08/2015 Letter Fire (Sprinkler) Plan Review
08/12/2015 Letter Inspection Summary
08/21/2015 Letter Field Certificate of Occupancy
08/24/2015 Letter Codes Final Certificate of Occupancy
08/25/2015 Plan drawings
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home