Permit Application Status

PRCOM20150474


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20150474
Building Permit - Commercial
Certificate of Occupancy
ARVEST BANNISTER REALTY COMPANY
CHANGE OF TENANT
INTERIOR ALTERATIONS FOR TENANT FINISH
03/12/2015
04/01/2015
09/19/2015
05/18/2015
Locations
Contacts
MID-WEST INTERIORS INC, Address:711 NE PILGRIM WAY, Phone:(816) 353-3100  
CHIEF HEATING & COOLING INC, Address:920 NW TECHNOLOGY DR, Phone:(816) 246-4646  
THREE DIAMOND ELECTRIC LLC, Address:27606 E PINK HILL RD, Phone:(816) 228-5470  
SCHOELLER PLUMBING INC, Address:PO BOX 1268, Phone:(816) 628-3848  
ARCVISION INC, Address:1950 CRAIG RD, STE 300, Phone:(314) 415-2400  
ARVEST BANNISTER REALTY COMPANY, Address:7401 W 135TH ST  
ARCVISION INC, Address:1950 CRAIG RD, STE 300, Phone:(314) 415-2400  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 04/30/2015
Brian Austerman
Misc
Corrective Action Required
04/30/2015

Duct detection shall initiate a supervosory signal at the panel along with unit shutdown
Installation acceptance testing
Corrective Action Required
04/30/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm testing
Misc
Corrective Action Required
04/30/2015

Provide a smoke detector within 10' of the new RPS
Sprinkler Plan Review Released for Construction 04/10/2015
Brian Austerman
Misc
Corrective Action Required
04/10/2015

Released for construction 4-10-15
Licensed Contractors Approved 03/27/2015 03/31/2015
Joe Frogge
LC - General Contractor
Resolved
03/31/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
03/31/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Building Plan Review Approved 04/03/2015 03/30/2015
Joe Frogge
License Tax Application
Corrective Action Required
03/27/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Resolved
03/30/2015

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Specify fire ratings of doors installed in 1 hour partitions.
Bldg - Accessibility - Kitchens and kitchenettes 1109.4
Resolved
03/30/2015

2012 IBC 1109.4 – Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible. Action required: Lower break room counter height to accommodate.
Fire Plan Review Approved 04/03/2015 03/30/2015
Brian Austerman
Construction documents for fire alarm systems
Corrective Action Required
03/27/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans showing work done 3/30/15 acknowledged
Construction documents - Fire protection systems
Corrective Action Required
03/27/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans showing work done 3/30/15 acknowledged
Portable fire extinguishers - general
Corrective Action Required
03/27/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type extinguisher for every 3,000 sq/ft or for 3/30/15 acknowledged
Building Plan Review Rejected 03/24/2015 03/20/2015
Joe Frogge
License Tax Application
Corrective Action Required
03/20/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
03/20/2015

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Specify fire ratings of doors installed in 1 hour partitions.
Bldg - Accessibility - Kitchens and kitchenettes 1109.4
Corrective Action Required
03/23/2015

2012 IBC 1109.4 – Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible. Action required: Lower break room counter height to accommodate.
Licensed Contractors Rejected 03/24/2015 03/20/2015
Joe Frogge
LC - General Contractor
Resolved
03/31/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
03/31/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 03/24/2015 03/16/2015
Brian Austerman
Construction documents for fire alarm systems
Corrective Action Required
03/16/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans showing work done
Construction documents - Fire protection systems
Corrective Action Required
03/16/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans showing work done
Portable fire extinguishers - general
Corrective Action Required
03/16/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type extinguisher for every 3,000 sq/ft or for
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $1,348.05 $1,348.05 Paid 04/01/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 4/17/2015 4/17/2015 at 12:00 AM 04/17/2015
In-wall Inspection Failed 4/28/2015 at 12:00 AM 04/28/2015
Misc
Corrective Action Required
04/28/2015
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS
Misc
Corrective Action Required
04/28/2015
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES AT TRACKS). CHECK ALL.
In-wall Inspection Partial 4/29/2015 4/29/2015 at 12:00 AM 04/29/2015
Misc
Resolved
04/29/2015
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS
Misc
Resolved
04/29/2015
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES AT TRACKS). CHECK ALL.
Misc
Partial Correction
04/29/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3RD FLOOR INCLUDING 302-4 SOUTH WALL;
Above Ceiling Inspection Partial 5/7/2015 5/7/2015 at 12:00 AM 05/07/2015
Misc
Corrective Action Required
05/07/2015
DEMO/REMOVALS: REMOVE ABANDONED MATERIALS
Misc
Corrective Action Required
05/07/2015
BUCKET ABOVE CEILING MAY INDICATE PAST OR PRESENT ROOF LEAK. INVESTIGATE AND RESOLVE.
Misc
Corrective Action Required
05/07/2015
ENSURE ALL CEILING SUPPORT WIRES EXTEND STRAIGHT FROM STRUCTURE ABOVE TO MAIN TEE.
Misc
Corrective Action Required
05/07/2015
SMACNA / AIR DIFUSSION COUNCIL / MANUFACTURER'S INSTRUCTIONS > INSTALLATION OF HVAC FLEXIBLE DUCT AND INSULATION: SEE INSTRUCTION SHEET IN EACH BOX OF MATERIAL. CLAMPS & TAPING OF INNER AND OUTER LAYER MUST BE PER INSTRUCTIONS. NON-METALLIC CLAMPS OK ONLY WITH BEADED FITTINGS.
Misc
Corrective Action Required
05/07/2015
NEC 300.11: SECURING AND SUPPORTING OF ELECTRICAL CABLE ASSEMBLIES: MAY NOT BE SUPPORTED BY CEILING SUPPORT HANGER WIRES; SUPPORT FROM STRUCTURE, FROM OTHER COMPONENTS OF ELECTRICAL SYSTEM, OR FROM HANGERS INSTALLED FOR SUPPORT OF THE ELECTRICAL SYSTEM. SECURE BOTH ENDS OF INDEPENDENT SUPPORT WIRES.
Misc
Corrective Action Required
05/07/2015
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER. COLORADO JIMS DO NOT SECURE MC TO RESIST TUGGING. USE CLAMPS THAT FASTEN MC IN PLACE WITHIN 12" OF BOX ENTRY.
Misc
Corrective Action Required
05/07/2015
CLOSE ALL ELECTRICAL JUNCTION BOXES AND UNUSED JBOX OPENINGS
Misc
Corrective Action Required
05/07/2015
ONE UNUSED MC CABLE WHIP TO BE SECURED WITH ENDS IN JBOX.
Misc
Corrective Action Required
05/07/2015
REMOVE TEMPORARY ELECTRICAL WIRING.
Misc
Corrective Action Required
05/07/2015
PLACEMENT / SUPPORT / SECURING OF LOW VOLTAGE ELECTRICAL CABLE: ROUTE HIGH IN INTERSTITIAL SPACE >= 18" ABOVE CEILING GRID; NOT TO BE LAID LOOSE ON CEILING GRID; DROP TO TERMINATIONS WHERE LOCATED. SUPPORT FROM STRUCTURE -- NOT FROM OTHER M/E/P SYSTEMS.
Above Ceiling Inspection Partial 5/8/2015 5/8/2015 at 12:00 AM 05/08/2015
Misc
Resolved
05/08/2015
DEMO/REMOVALS: REMOVE ABANDONED MATERIALS
Misc
Resolved
05/08/2015
BUCKET ABOVE CEILING MAY INDICATE PAST OR PRESENT ROOF LEAK. INVESTIGATE AND RESOLVE.
Misc
Resolved
05/08/2015
ENSURE ALL CEILING SUPPORT WIRES EXTEND STRAIGHT FROM STRUCTURE ABOVE TO MAIN TEE.
Misc
Resolved
05/08/2015
SMACNA / AIR DIFUSSION COUNCIL / MANUFACTURER'S INSTRUCTIONS > INSTALLATION OF HVAC FLEXIBLE DUCT AND INSULATION: SEE INSTRUCTION SHEET IN EACH BOX OF MATERIAL. CLAMPS & TAPING OF INNER AND OUTER LAYER MUST BE PER INSTRUCTIONS. NON-METALLIC CLAMPS OK ONLY WITH BEADED FITTINGS.
Misc
Resolved
05/08/2015
NEC 300.11: SECURING AND SUPPORTING OF ELECTRICAL CABLE ASSEMBLIES: MAY NOT BE SUPPORTED BY CEILING SUPPORT HANGER WIRES; SUPPORT FROM STRUCTURE, FROM OTHER COMPONENTS OF ELECTRICAL SYSTEM, OR FROM HANGERS INSTALLED FOR SUPPORT OF THE ELECTRICAL SYSTEM. SECURE BOTH ENDS OF INDEPENDENT SUPPORT WIRES.
Misc
Resolved
05/08/2015
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER. COLORADO JIMS DO NOT SECURE MC TO RESIST TUGGING. USE CLAMPS THAT FASTEN MC IN PLACE WITHIN 12" OF BOX ENTRY.
Misc
Resolved
05/08/2015
CLOSE ALL ELECTRICAL JUNCTION BOXES AND UNUSED JBOX OPENINGS
Misc
Resolved
05/08/2015
ONE UNUSED MC CABLE WHIP TO BE SECURED WITH ENDS IN JBOX.
Misc
Resolved
05/08/2015
REMOVE TEMPORARY ELECTRICAL WIRING.
Misc
Resolved
05/08/2015
PLACEMENT / SUPPORT / SECURING OF LOW VOLTAGE ELECTRICAL CABLE: ROUTE HIGH IN INTERSTITIAL SPACE >= 18" ABOVE CEILING GRID; NOT TO BE LAID LOOSE ON CEILING GRID; DROP TO TERMINATIONS WHERE LOCATED. SUPPORT FROM STRUCTURE -- NOT FROM OTHER M/E/P SYSTEMS.
Misc
Corrective Action Required
05/08/2015
CORRIDOR WALLS ARE REQUIRED TO MEET UL465. RE-INSPECTION REQUIRED FOR SEALING OF PENETRATIONS AND AT DOOR RECESS TO BE RATED ASSEMBLY. LEAVE TILE OUT ALONG CORRIDOR WALLS BOTH FACES.
Above Ceiling Inspection Partial 5/11/2015 5/11/2015 at 12:00 AM 05/11/2015
Misc
Corrective Action Required
05/08/2015
3RD FLOOR: CORRIDOR WALLS ARE REQUIRED TO MEET UL465. RE-INSPECTION REQUIRED FOR SEALING OF PENETRATIONS AND AT DOOR RECESS TO BE RATED ASSEMBLY. LEAVE TILE OUT ALONG CORRIDOR WALLS BOTH FACES. NOT READY FOR RE-INSPECTION 5/11.
Misc
Corrective Action Required
05/11/2015
OK TO COVER WHEN READY ABOVE CEILING SYSTEMS AT: 203-1;
Occupancy Inspection - Codes Commercial Not Ready 5/11/2015 5/11/2015 at 12:00 AM 05/11/2015
Alarm Test Passed 5/12/2015 at 12:00 AM 05/12/2015
Above Ceiling Inspection Partial 5/13/2015 5/13/2015 at 12:00 AM 05/13/2015
Misc
Corrective Action Required
05/11/2015
3RD FLOOR: OK TO CLOSE CEILING EXCEPT AT RECESSES TO DOORS #302-3 & #302-4 WHERE RATED ASSEMBLY HAS YET TO BE APPROVED.
Misc
Resolved
05/13/2015
OK TO COVER WHEN READY ABOVE CEILING SYSTEMS AT: 203-1;
Rated Assembly Inspection Partial 5/13/2015 at 12:00 AM 05/13/2015
Misc
Corrective Action Required
05/13/2015
FIRE BARRIER WALLS OR LID(S) AT RECESSES FOR DOORS #302-3 AND #302-4 MUST CLOSE TO DECK OR TO APPROVED WALL STRUCTURE.
Occupancy Inspection - Fire Not Ready 5/11/2015 5/14/2015 at 12:00 AM 05/14/2015
Occupancy Inspection - Codes Commercial Failed 5/14/2015 5/14/2015 at 12:00 AM 05/14/2015
Misc
Corrective Action Required
05/14/2015
RATED ASSEMBLIES AT CORRIDOR DOOR RECESSES TO BE INSPECTED WHEN READY.
Misc
Corrective Action Required
05/14/2015
SOME UNITS OF SAFETY GLASS YET TO BE INSTALLED AND APPROVED.
Misc
Corrective Action Required
05/14/2015
WORK IN PROGRESS AT ELECTRICAL ROOM. ALL ELEMENTS SUBJECT TO APPROVAL WHEN ALL READY FOR INSPECTION.
Misc
Corrective Action Required
05/14/2015
ELECTRICAL RECEPTACLES AT DEMOUNTABLE OFFICE CUBICLES SUBJECT TO TEST & APPROVAL WHEN READY.
Misc
Corrective Action Required
05/14/2015
ENSURE ALL ELECTRICAL RECEPTACLES ARE SECURED SOLID TO BOXES. NON "SOFT" OR LOOSE SIDE-TO-SIDE.
Misc
Corrective Action Required
05/14/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES.
Misc
Corrective Action Required
05/14/2015
ELECTRICAL PANEL SCHEDULE(S) SUBJECT TO APPROVAL. ENSURE ALL LABELING IS CURRENT, SPECIFIC, AND LEGIBLE.
Occupancy Inspection - Codes Commercial Full C of O 5/18/2015 5/18/2015 at 12:00 AM 05/18/2015
Misc
Resolved
05/18/2015
RATED ASSEMBLIES AT CORRIDOR DOOR RECESSES TO BE INSPECTED WHEN READY.
Misc
Resolved
05/18/2015
SOME UNITS OF SAFETY GLASS YET TO BE INSTALLED AND APPROVED.
Misc
Resolved
05/18/2015
WORK IN PROGRESS AT ELECTRICAL ROOM. ALL ELEMENTS SUBJECT TO APPROVAL WHEN ALL READY FOR INSPECTION.
Misc
Resolved
05/18/2015
ELECTRICAL RECEPTACLES AT DEMOUNTABLE OFFICE CUBICLES SUBJECT TO TEST & APPROVAL WHEN READY.
Misc
Resolved
05/18/2015
ENSURE ALL ELECTRICAL RECEPTACLES ARE SECURED SOLID TO BOXES. NON "SOFT" OR LOOSE SIDE-TO-SIDE.
Misc
Resolved
05/18/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES.
Misc
Resolved
05/18/2015
ELECTRICAL PANEL SCHEDULE(S) SUBJECT TO APPROVAL. ENSURE ALL LABELING IS CURRENT, SPECIFIC, AND LEGIBLE.
Above Ceiling Inspection Passed 5/18/2015 at 12:00 AM 05/18/2015
Misc
Resolved
05/18/2015
3RD FLOOR: OK TO CLOSE CEILING EXCEPT AT RECESSES TO DOORS #302-3 & #302-4 WHERE RATED ASSEMBLY HAS YET TO BE APPROVED.
In-wall Inspection Passed 5/18/2015 at 12:00 AM 05/18/2015
Misc
Resolved
05/18/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3RD FLOOR INCLUDING 302-4 SOUTH WALL;
Rated Assembly Inspection Passed 5/18/2015 at 12:00 AM 05/18/2015
Misc
Resolved
05/18/2015
FIRE BARRIER WALLS OR LID(S) AT RECESSES FOR DOORS #302-3 AND #302-4 MUST CLOSE TO DECK OR TO APPROVED WALL STRUCTURE.
Occupancy Inspection - Fire Passed 5/18/2015 at 12:00 AM 05/18/2015
Documents & Images
Date Uploaded File Type Document Name
03/16/2015 Letter Fire Building Plan Review
03/23/2015 Letter Codes P/R Corrections Document
03/30/2015 Letter Fire Building Plan Review
03/30/2015 Letter Codes P/R Corrections Document
04/01/2015 Letter Codes Plan Review Conditions
04/01/2015 Letter Codes Building Permit
04/01/2015 Receipt Receipt for transaction: 2015-000508
04/10/2015 Letter Fire (Sprinkler) Plan Review
04/17/2015 Letter Inspection Summary
04/28/2015 Letter Inspection Summary
04/29/2015 Letter Inspection Summary
04/30/2015 Letter Fire (Alarm) Plan Review Notice
05/07/2015 Letter Inspection Summary
05/08/2015 Letter Inspection Summary
05/11/2015 Letter Inspection Summary
05/13/2015 Letter Inspection Summary
05/14/2015 Letter Inspection Summary
05/18/2015 Letter Field Certificate of Occupancy
05/20/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home