Permit Application Status

PRCOM20150463


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20150463
Building Permit - Commercial
Certificate of Occupancy
SUMMIT WOODS SPE LLC
CHANGE OF TENANT
TENANT FINISH FOR NEW RESTAURANT
03/10/2015
04/17/2015
10/03/2015
06/29/2015
Locations
Contacts
MID-AMERICA CONTRACTORS INC, Address:1400 IRON, Phone:(816) 221-4516  
LBA AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6850 W 47TH TER, Phone:(913) 268-6822  
M & S ELECTRIC, Address:PO BOX 1147, Phone:(816) 427-5913  
ACCURATE MECHANICAL LLC, Address:205 E 13TH AVE, Phone:(816) 471-2272  
DAVIDSON ARCHITECTURE & ENGINEERING - PAUL MILLER, Address:4301 INDIAN CREEK PKWY, Phone:(913) 451-9390  
SUMMIT WOODS SPE LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/31/2015
Joe Dir
Sprinkler Plan Review Released for Construction 12/31/2015
Joe Dir
Sprinkler Plan Review Released for Construction 12/31/2015
Joe Dir
Fire Plan Review Approved 04/02/2015 04/24/2015
Brian Austerman
Misc
Corrective Action Required
04/24/2015

No further FD comments
Fire Plan Review Approved 04/22/2015
Brian Austerman
Misc
Corrective Action Required
04/22/2015

No further FD comments
Licensed Contractors Approved 03/26/2015 04/09/2015
Joe Frogge
LC - General Contractor
Resolved
03/31/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
04/09/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
r
Health Department Review Approved 04/23/2015 04/09/2015
Joe Frogge
Building Plan Review Approved 04/02/2015 04/06/2015
Joe Frogge
Health Dept Inspection
Corrective Action Required
03/26/2015

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Review
Resolved
04/06/2015

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Bldg - Occupant load posting 1004.3
Corrective Action Required
03/26/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. To be verified at inspections.
Miscellaneous Correction
Resolved
03/31/2015

2012 IBC 1008.1.4.1 Revolving doors. Revolving doors shall comply with the following: 1. Each revolving door shall be capable of collapsing into a bookfold position with parallel egress paths providing an aggregate width of 36 inches (914 mm). 2. A revolving door shall not be located within 10 feet (3048 mm) of the foot of or top of stairs or escalators. A dispersal area shall be provided between the stairs or escalators and the revolving doors. 3. The revolutions per minute (rpm) for a revolving door shall not exceed those shown in Table 1008.1.4.1. 4. Each revolving door shall have a side-hinged swinging door which complies with Section 1008.1 in the same wall and within 10 feet (3048 mm) of the revolving door. 5. Revolving doors shall not be part of an accessible route required by Section 1007 and Chapter 11 of the International Building Code. Action required: Revise plans to comply with item #4. 3/31/15 - doors removed
Design loads
Resolved
04/02/2015

2012 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of new roof top equipment is less than or equal to original equipment or provide verification that existing roof structure will support additional load. 3/31/15 - acknowledged; pending 4/2/15 - engineered re-suppoort of roof structure provided
Misc 12
Resolved
03/31/2015

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide directional exit sign at east end of corridor. To be visible from entire dining area. 3/31/15 - drawing updated
Misc 13
Resolved
03/31/2015

2012 IMC 507.2.2 Type II hoods. Type II hoods shall be installed above dishwashers and appliances that produce heat or moisture and do not produce grease or smoke as a result of the cooking process, except where the heat and moisture loads from such appliances are incorporated into the HVAC system design or into the design of a separate removal system. (see code section for more specific requirements) Action required: Provide a Type II hood above dishwasher or provide verification that consequent heat and moisture loads have been compensated for in HVAC design. 3/31/15 - letter from architect attests to the fact that the heat and moisture has been accounted for in the HVAC calcs
Misc 14
Resolved
03/31/2015

2012 IMC 506.5.3 Exhaust fan mounting. An upblast fan shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning. The ductwork shall extend a minimum of 18 inches above the roof surface. Action required: Modify spec for fan serving kitchen exhaust hoods to comply with referenced code section. 3/31/15 - updated specification
Fire Plan Review Approved 04/02/2015 03/30/2015
Brian Austerman
Misc
Corrective Action Required
03/26/2015

2012 IFC [B] 1008.1.4.1 Revolving doors. Revolving doors shall comply with the following: 1. Each revolving door shall be capable of collapsing into a bookfold position with parallel egress paths providing an aggregate width of 36 inches (914 mm). 2. A revolving door shall not be located within 10 feet (3048 mm) of the foot of or top of stairs or escalators. A dispersal area shall be provided between the stairs or escalators and the revolving doors. 3. The revolutions per minute (rpm) for a revolving door shall not exceed those shown in Table 1008.1.4.1. 4. Each revolving door shall have a side-hinged swinging door which complies with Section 1008.1 in the same wall and within 10 feet (3048 mm) of the revolving door. 5. Revolving doors shall not be part of an accessible route required by Section 1007 and Chapter 11 of the International Building Code. Revise door plan to meet condition 4 above. Hinged door shall be within 10' and on the same wall as the revolving door 3/30/15 Door plan revised to remove revolving door
Construction documents for fire alarm systems
Corrective Action Required
03/26/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans showing work done, can be a deferred submittal 3/30/15 acknowledged
Construction documents - Fire protection systems
Corrective Action Required
03/26/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans showing any alterations to the system, may be a deferred submittal 3/30/15 acknowledged
Installation acceptance testing
Corrective Action Required
03/26/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hood testing 3/30/15 acknowledged
Portable fire extinguishers - general
Corrective Action Required
03/26/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide 5lb ABC type fire extinguisher(s) 3/30/15 acknowledged
Building Plan Review Rejected 03/20/2015 03/18/2015
Joe Frogge
Health Dept Inspection
Corrective Action Required
03/18/2015

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Review
Corrective Action Required
03/18/2015

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Bldg - Occupant load posting 1004.3
Corrective Action Required
03/18/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. To be verified at inspections.
Miscellaneous Correction
Corrective Action Required
03/18/2015

2012 IBC 1008.1.4.1 Revolving doors. Revolving doors shall comply with the following: 1. Each revolving door shall be capable of collapsing into a bookfold position with parallel egress paths providing an aggregate width of 36 inches (914 mm). 2. A revolving door shall not be located within 10 feet (3048 mm) of the foot of or top of stairs or escalators. A dispersal area shall be provided between the stairs or escalators and the revolving doors. 3. The revolutions per minute (rpm) for a revolving door shall not exceed those shown in Table 1008.1.4.1. 4. Each revolving door shall have a side-hinged swinging door which complies with Section 1008.1 in the same wall and within 10 feet (3048 mm) of the revolving door. 5. Revolving doors shall not be part of an accessible route required by Section 1007 and Chapter 11 of the International Building Code. Action required: Revise plans to comply with item #4.
Design loads
Corrective Action Required
03/18/2015

2012 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of new roof top equipment is less than or equal to original equipment or provide verification that existing roof structure will support additional load.
Misc 12
Corrective Action Required
03/18/2015

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide directional exit sign at east end of corridor. To be visible from entire dining area.
Misc 13
Corrective Action Required
03/18/2015

2012 IMC 507.2.2 Type II hoods. Type II hoods shall be installed above dishwashers and appliances that produce heat or moisture and do not produce grease or smoke as a result of the cooking process, except where the heat and moisture loads from such appliances are incorporated into the HVAC system design or into the design of a separate removal system. (see code section for more specific requirements) Action required: Provide a Type II hood above dishwasher or provide verification that consequent heat and moisture loads have been compensated for in HVAC design.
Misc 14
Corrective Action Required
03/18/2015

2012 IMC 506.5.3 Exhaust fan mounting. An upblast fan shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning. The ductwork shall extend a minimum of 18 inches above the roof surface. Action required: Modify spec for fan serving kitchen exhaust hoods to comply with referenced code section.
Licensed Contractors Rejected 03/20/2015 03/18/2015
Joe Frogge
LC - General Contractor
Corrective Action Required
03/18/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
03/18/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Rejected 03/20/2015 03/16/2015
Brian Austerman
Misc
Corrective Action Required
03/16/2015

2012 IFC [B] 1008.1.4.1 Revolving doors. Revolving doors shall comply with the following: 1. Each revolving door shall be capable of collapsing into a bookfold position with parallel egress paths providing an aggregate width of 36 inches (914 mm). 2. A revolving door shall not be located within 10 feet (3048 mm) of the foot of or top of stairs or escalators. A dispersal area shall be provided between the stairs or escalators and the revolving doors. 3. The revolutions per minute (rpm) for a revolving door shall not exceed those shown in Table 1008.1.4.1. 4. Each revolving door shall have a side-hinged swinging door which complies with Section 1008.1 in the same wall and within 10 feet (3048 mm) of the revolving door. 5. Revolving doors shall not be part of an accessible route required by Section 1007 and Chapter 11 of the International Building Code. Revise door plan to meet condition 4 above. Hinged door shall be within 10' and on the same wall as the revolving door
Construction documents for fire alarm systems
Corrective Action Required
03/16/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans showing work done, can be a deferred submittal
Construction documents - Fire protection systems
Corrective Action Required
03/16/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans showing any alterations to the system, may be a deferred submittal
Installation acceptance testing
Corrective Action Required
03/16/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hood testing
Portable fire extinguishers - general
Corrective Action Required
03/16/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide 5lb ABC type fire extinguisher(s)
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $1,021.25 $1,021.25 Paid 04/17/2015
8331507-Sewer Connection Fee $270.00 $270.00 Paid 04/17/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Not Ready 5/6/2015 at 12:00 AM 05/06/2015
Misc
Corrective Action Required
05/06/2015
IBC 109.1, 109.5; IRC R109.3 READINESS FOR INSPECTION: WORK REQUESTED FOR INSPECTION NOT READY FOR INSPECTION; CALL FOR INSPECTION ON DAY WHEN WORK IS READY FULL DAY.
Underslab Plumbing Inspection - Commercial Not Ready 5/7/2015 5/7/2015 at 12:00 AM 05/07/2015
Misc
Corrective Action Required
05/06/2015
IBC 109.1, 109.5; IRC R109.3 READINESS FOR INSPECTION: WORK REQUESTED FOR INSPECTION NOT READY FOR INSPECTION; CALL FOR INSPECTION ON DAY WHEN WORK IS READY FULL DAY.
Underslab Plumbing Inspection - Commercial Passed 5/11/2015 at 12:00 AM 05/11/2015
Misc
Resolved
05/11/2015
IBC 109.1, 109.5; IRC R109.3 READINESS FOR INSPECTION: WORK REQUESTED FOR INSPECTION NOT READY FOR INSPECTION; CALL FOR INSPECTION ON DAY WHEN WORK IS READY FULL DAY.
In-wall Inspection Not Ready 5/18/2015 at 12:00 AM 05/18/2015
Misc
Corrective Action Required
05/18/2015
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES). CHECK ALL.
In-wall Inspection Partial 5/19/2015 5/19/2015 at 12:00 AM 05/19/2015
Misc
Resolved
05/19/2015
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES). CHECK ALL.
Misc
Partial Correction
05/19/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 2" VERTICAL PVC AT KIT 113 NORTHEAST;
In-wall Inspection Failed 5/21/2015 5/21/2015 at 12:00 AM 05/21/2015
Misc
Partial Correction
05/19/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 2" VERTICAL PVC AT KIT 113 NORTHEAST;
Misc
Corrective Action Required
05/21/2015
NEC 300-11, 330.30 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES
In-wall Inspection Passed 5/22/2015 5/22/2015 at 12:00 AM 05/22/2015
Misc
Resolved
05/22/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: 2" VERTICAL PVC AT KIT 113 NORTHEAST; OK THFROUGHOUT
Misc
Resolved
05/22/2015
NEC 300-11, 330.30 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES
Above Ceiling Inspection Partial 6/3/2015 6/3/2015 at 12:00 AM 06/03/2015
Misc
Partial Correction
06/03/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ TWO RESTROOMS.
Gas Piping Inspection - Commercial Passed 6/8/2015 at 12:00 AM 06/08/2015
Above Ceiling Inspection Not Ready 6/8/2015 6/9/2015 at 12:00 AM 06/09/2015
Misc
Partial Correction
06/03/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ TWO RESTROOMS.
Above Ceiling Inspection Partial 6/10/2015 at 12:00 AM 06/10/2015
Misc
Partial Correction
06/09/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ TWO RESTROOMS.
Misc
Partial Correction
06/09/2015
OK TO COVER WHEN READY ACT CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: BORDERS ONLY
Misc
Corrective Action Required
06/10/2015
SMACNA / AIR DIFUSSION COUNCIL / MANUFACTURER'S INSTRUCTIONS > INSTALLATION OF HVAC FLEXIBLE DUCT & CONNECTORS: VERIFY THAT INNER LAYER AND OUTER LAYER ARE SEPARATELY BANDED PER INSTRUCTIONS
Above Ceiling Inspection Passed 6/12/2015 6/12/2015 at 12:00 AM 06/12/2015
Misc
Resolved
06/12/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ TWO RESTROOMS.
Misc
Resolved
06/12/2015
OK TO COVER WHEN READY ACT CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: BORDERS ONLY
Misc
Resolved
06/12/2015
SMACNA / AIR DIFUSSION COUNCIL / MANUFACTURER'S INSTRUCTIONS > INSTALLATION OF HVAC FLEXIBLE DUCT & CONNECTORS: VERIFY THAT INNER LAYER AND OUTER LAYER ARE SEPARATELY BANDED PER INSTRUCTIONS
Miscellaneous Inspection Passed 6/15/2015 at 12:00 AM 06/15/2015
Alarm Test Not Ready 6/16/2015 at 12:00 AM 06/16/2015
Alternate Protection Systems Inspection Not Ready 6/16/2015 at 12:00 AM 06/16/2015
Occupancy Inspection - Fire Not Ready 6/17/2015 6/17/2015 at 12:00 AM 06/17/2015
Alarm Test Not Ready 6/17/2015 at 12:00 AM 06/17/2015
Alternate Protection Systems Inspection Not Ready 6/17/2015 at 12:00 AM 06/17/2015
Occupancy Inspection - Codes Commercial Not Ready 6/17/2015 6/17/2015 at 12:00 AM 06/17/2015
Occupancy Inspection - Codes Commercial Failed 6/22/2015 6/22/2015 at 12:00 AM 06/22/2015
Misc
Corrective Action Required
06/22/2015
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Misc
Corrective Action Required
06/22/2015
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE; 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. SEE AT TO-COUNTER AND BACK WALL OF BAR.
Misc
Corrective Action Required
06/22/2015
NEC 380-10; 410-56(f) SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: SOME NOT TIGHT TO BOX; CHECK ALL AND ENSURE NONE ARE "SOFT" OR LOOSE SIDE-TO-SIDE.
Misc
Corrective Action Required
06/22/2015
IDENTIFICATION OF ELECTRICAL SERVICE PANELS: AFFIX PERMANENT LABELS @ FACE OF PANEL FRONT PER DRAWINGS OR OCCUPANT PREFERENCE.
Misc
Corrective Action Required
06/22/2015
NEC 408.4 ELECTRICAL SERVICE INSTALLATION: ENSURE ALL CIRCUIT POSITIONS ARE PROPERLY LABELED. MUST BE LEGIBLE, COMPLETE, CURRENT, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Corrective Action Required
06/22/2015
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Misc
Corrective Action Required
06/22/2015
TWO ELECTRICAL RECEPTACLES ABOVE WALK-IN COOLER EQUIPMENT NOT HOT FOR TEST.
Misc
Corrective Action Required
06/22/2015
SEAL MOP SINK TO WALL.
Misc
Corrective Action Required
06/22/2015
ICC A117.1, 303 CHANGES IN LEVEL OF FLOOR SURFACES GREATER THAN 1/2" SHALL COMPLY WITH REQUIREMENTS FOR RAMPS. 1:12 MAXIMUM SLOPE.
Misc
Corrective Action Required
06/22/2015
APPROVAL OF JACKSON COUNTY HEALTH DEPARTMENT MUST BE OBTAINED. PROVIDE DOCUMENTATION.
Misc
Corrective Action Required
06/22/2015
OK TO SET UP FOR BUSINESS. NO PUBLIC ENTRY OR BUSINESS OPERATIONS PRIOR TO APPROVAL.
Occupancy Inspection - Fire Not Ready 6/22/2015 at 12:00 AM 06/22/2015
Occupancy Inspection - Fire Temporary C of O 6/23/2015 at 12:00 AM 06/23/2015
Alarm Test Passed 6/23/2015 at 12:00 AM 06/23/2015
Alternate Protection Systems Inspection Passed 6/23/2015 at 12:00 AM 06/23/2015
Occupancy Inspection - Codes Commercial Failed 6/25/2015 6/25/2015 at 12:00 AM 06/25/2015
Misc
Corrective Action Required
06/22/2015
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Misc
Resolved
06/25/2015
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE; 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. SEE AT TO-COUNTER AND BACK WALL OF BAR.
Misc
Resolved
06/25/2015
NEC 380-10; 410-56(f) SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: SOME NOT TIGHT TO BOX; CHECK ALL AND ENSURE NONE ARE "SOFT" OR LOOSE SIDE-TO-SIDE.
Misc
Resolved
06/25/2015
IDENTIFICATION OF ELECTRICAL SERVICE PANELS: AFFIX PERMANENT LABELS @ FACE OF PANEL FRONT PER DRAWINGS OR OCCUPANT PREFERENCE.
Misc
Resolved
06/25/2015
NEC 408.4 ELECTRICAL SERVICE INSTALLATION: ENSURE ALL CIRCUIT POSITIONS ARE PROPERLY LABELED. MUST BE LEGIBLE, COMPLETE, CURRENT, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Resolved
06/25/2015
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Misc
Resolved
06/25/2015
TWO ELECTRICAL RECEPTACLES ABOVE WALK-IN COOLER EQUIPMENT NOT HOT FOR TEST.
Misc
Corrective Action Required
06/22/2015
SEAL MOP SINK TO WALL.
Misc
Resolved
06/25/2015
ICC A117.1, 303 CHANGES IN LEVEL OF FLOOR SURFACES GREATER THAN 1/2" SHALL COMPLY WITH REQUIREMENTS FOR RAMPS. 1:12 MAXIMUM SLOPE.
Misc
Resolved
06/25/2015
APPROVAL OF JACKSON COUNTY HEALTH DEPARTMENT MUST BE OBTAINED. PROVIDE DOCUMENTATION.
Misc
Corrective Action Required
06/22/2015
OK TO SET UP FOR BUSINESS. NO PUBLIC ENTRY OR BUSINESS OPERATIONS PRIOR TO APPROVAL.
Misc
Resolved
06/25/2015
ICC 117.1 INSTALL HANDICAPPED-ACCESSIBLE RESTROOM SIGNS
Misc
Corrective Action Required
06/25/2015
ROOFTOP: DESIGNATE THE TWO GREASE HOOD EXHAUST FANS AND REFLECT DESIGNATIONS AT ELECTRICAL PANEL.
Occupancy Inspection - Fire Passed 6/25/2015 at 12:00 AM 06/25/2015
Occupancy Inspection - Codes Commercial Full C of O 6/29/2015 6/29/2015 at 12:00 AM 06/29/2015
Misc
Resolved
06/29/2015
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Misc
Resolved
06/29/2015
SEAL MOP SINK TO WALL.
Misc
Resolved
06/29/2015
OK TO SET UP FOR BUSINESS. NO PUBLIC ENTRY OR BUSINESS OPERATIONS PRIOR TO APPROVAL.
Misc
Resolved
06/29/2015
ROOFTOP: DESIGNATE THE TWO GREASE HOOD EXHAUST FANS AND REFLECT DESIGNATIONS AT ELECTRICAL PANEL.
Documents & Images
Date Uploaded File Type Document Name
03/16/2015 Letter Fire Building Plan Review
03/18/2015 Letter Codes P/R Corrections Document
03/30/2015 Letter Fire Building Plan Review
03/31/2015 Letter Codes P/R Corrections Document
04/09/2015 Letter Codes Plan Review Conditions
04/17/2015 Receipt Receipt for transaction: 2015-000628
04/17/2015 Letter Codes Building Permit
04/22/2015 Letter Fire Building Plan Review
04/24/2015 Letter Fire Building Plan Review
05/06/2015 Letter Inspection Summary
05/11/2015 Letter Inspection Summary
05/18/2015 Letter Inspection Summary
05/19/2015 Letter Inspection Summary
05/21/2015 Letter Inspection Summary
05/22/2015 Letter Inspection Summary
06/03/2015 Letter Inspection Summary
06/08/2015 Letter Inspection Summary
06/10/2015 Letter Inspection Summary
06/12/2015 Letter Inspection Summary
06/22/2015 Letter Inspection Summary
06/25/2015 Letter Inspection Summary
06/29/2015 Letter Field Certificate of Occupancy
06/30/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home