Permit Application Status

PRCOM20143335


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20143335
Building Permit - Commercial
Certificate of Occupancy
200 NE MISSOURI DRIVE HOLDINGS LLC
CHANGE OF TENANT
TENANT BUILD-OUT FOR AN AMBULATORY SURGERY CENTER SPECIALIZING IN OUT PATIENT SURGERY CASES - INCLUDES NEW ENTRY CANOPY AND EXTERIOR EQUIPMENT ENCLOSURE FOR NEW MECHANICAL EQUIPMENT AND GENERATOR
12/04/2014
03/05/2015
10/27/2015
11/04/2015
Locations
Contacts
JE DUNN CONSTRUCTION CO, Address:120 S CENTRAL AVE STE 350, Phone:(816) 474-8600  
RAND CONSTRUCTION COMPANY, Address:1428 W 9TH ST, Phone:(816) 421-4143  
SHAW ELECTRIC COMPANY, Address:3600 FULLER, Phone:(816) 921-0033  
RAND CONSTRUCTION COMPANY, Address:1428 W 9TH ST, Phone:(816) 421-4143  
HEREFORD DOOLEY ARCHITECTS, Address:1720 WEST END AVENUE, SUITE 130, Phone:(615) 244-7399  
200 NE MISSOURI DRIVE HOLDINGS LLC, Address:5956 SHERRY LANE STE 1201, Phone:(301) 255-4872  
MIKE BOYD, Address:JE DUNN, Phone:(816) 564-5327  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Rejected 10/05/2015 10/02/2015
Joe Frogge
DE Corps of Engineers
Corrective Action Required
09/28/2015

Minimum parking stall width is 9'-0" Action required: Revised parking lot striping.
Fire Plan Review Approved with Conditions 07/09/2015 07/09/2015
Joe Dir
Misc
Corrective Action Required
07/09/2015

Provide Medical Gas Certifications prior to final
Construction documents for fire alarm systems
Corrective Action Required
07/09/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Alarm contractor shall provide plans for work to be performed
Construction documents - Fire protection systems
Corrective Action Required
07/09/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Sprinkler contractor shall provide plans for prionkler work to be performed
Misc
Corrective Action Required
07/09/2015

Duct detection is required for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the panel. For information only
DE Corps of Engineers
Corrective Action Required
07/09/2015

5306.2.1 One-hour exterior rooms. A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by fire barriers constructed in accordance with Section 707 of the International Building Code or horizontal assemblies constructed in accordance with Section 711 of the International Building Code, or both, with a fire-resistance rating of not less than 1 hour. Openings between the room or enclosure and interior spaces shall be self-closing smoke- and draft-control assemblies having a fire protection rating of not less than 1 hour. Rooms shall have at least one exterior wall that is provided with at least two vents. Each vent shall not be less than 36 square inches (0.023 m2) in area. One vent shall be within 6 inches (152 mm) of the floor and one shall be within 6 inches (152 mm) of the ceiling. Rooms shall be provided with at least one automatic sprinkler to provide container cooling in case of fire. 5306.2.2 One-hour interior room. When an exterior wall cannot be provided for the room, automatic sprinklers shall be installed within the room. The room shall be exhausted through a duct to the exterior. Supply and exhaust ducts shall be enclosed in a 1-hour-rated shaft enclosure from the room to the exterior. Approved mechanical ventilation shall comply with the International Mechanical Code and be provided at a minimum rate of 1 cubic foot per minute per square foot [0.00508 m3/(s · m2)] of the area of the room. Plans didn't show specs on the med gas room
Sprinkler Plan Review Released for Construction 04/30/2015
Brian Austerman
Installation acceptance testing
Corrective Action Required
04/30/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hydrostatic test
Building Plan Review Approved 03/18/2015 03/05/2015
Joe Frogge
License Tax Application
Resolved
02/27/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment for informational purposes.
Final Development Plan
Resolved
03/05/2015

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment for informational purposes.
Misc
Resolved
12/31/2014

2012 IBC 716.5 Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 716.5.1, 716.5.2 or 716.5.3 and the fire protection rating indicated in Table 716.5. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 716.5.6. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and the NFPA 80. Action required: Specify door ratings where required in fire/smoke barriers. 12/24/14 - Doors A100a & A133a are to be installed in 2hr barrier but are only rated for 45min. 12/31/14 - drawing updated
Final Development Plan Review Approved 03/05/2015
Joe Frogge
Licensed Contractors Approved 02/27/2015
Development Center
LC - General Contractor
Resolved
03/05/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - General Contractor
Resolved
03/05/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
03/05/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
LC - MEP Subs
Resolved
03/05/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Sprinkler Plan Review Released for Construction 02/20/2015
Brian Austerman
Misc
Corrective Action Required
02/20/2015

No FD comments
Fire Plan Review Approved with Conditions 01/08/2015 12/31/2014
Joe Frogge
Misc
Corrective Action Required
12/31/2014

Provide Medical Gas Certifications prior to final
Construction documents for fire alarm systems
Corrective Action Required
12/31/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Alarm contractor shall provide plans for work to be performed
Construction documents - Fire protection systems
Corrective Action Required
12/31/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Sprinkler contractor shall provide plans for prionkler work to be performed
Misc
Corrective Action Required
12/31/2014

Duct detection is required for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the panel. For information only
Alarm Plan Review Released for Construction 12/31/2014
Joe Dir
Building Plan Review Rejected 01/05/2015 12/24/2014
Joe Frogge
License Tax Application
Corrective Action Required
12/24/2014

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment for informational purposes.
Final Development Plan
Corrective Action Required
12/24/2014

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment for informational purposes.
Misc
Corrective Action Required
12/24/2014

2012 IBC 716.5 Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 716.5.1, 716.5.2 or 716.5.3 and the fire protection rating indicated in Table 716.5. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 716.5.6. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and the NFPA 80. Action required: Specify door ratings where required in fire/smoke barriers. 12/24/14 - Doors A100a & A133a are to be installed in 2hr barrier but are only rated for 45min.
Accessibility - Fixed sidewall grab bars 604.5.1
Resolved
12/24/2014

ICC A117.1-2009 604.5.1 – Fixed side wall grab bars. Fixed side-wall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: Specify installation of vertical grab bars at accessible toilets. 12/24/14 - drawings updated
Misc
Resolved
12/24/2014

2012 IFGC 503.6.4 Gas Vent Terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches or less in size and located not less than 8 feet from a vertical wall or similar obstruction shall terminate above the roof in accordance with Figure 503.6.4. 2. Gas vents that are over 12 inches in size or are located less than 8 feet from a vertical wall or similar obstruction shall terminate not less than 2 feet above the highest point where they pass through the roof and not less than 2 feet above any portion of a building within 10 feet horizontally. 3. As provided for industrial appliances in Section 503.2.2.2. 4. As provided for direct-vent systems in Section 503.2.3. 5. As provided for appliances with integral vents in Section 503.2.4. 6. As provided for mechanical draft systems in Section 503.3.3. 7. As provided for ventilating hoods and exhaust systems in Section 503.3.4. Action required: Modify design to depict how NG vents will be terminated in compliance with IFGC. 12/24/14 - drawings updated to specify direct vent appliances
Bldg - Accessibility - Kitchens and kitchenettes 1109.4
Resolved
12/24/2014

2012 IBC 1109.4 – Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible. Action required: Refrigerator specified (with freezer above) is not accessible. 12/24/14 - fridge is in work area, therefore is exempt
Fire Plan Review Approved with Conditions 01/05/2015 12/24/2014
Joe Frogge
Misc
Corrective Action Required
12/24/2014

Provide Medical Gas Certifications prior to final
Construction documents for fire alarm systems
Corrective Action Required
12/24/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Alarm contractor shall provide plans for work to be performed
Construction documents - Fire protection systems
Corrective Action Required
12/24/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Sprinkler contractor shall provide plans for prionkler work to be performed
Misc
Corrective Action Required
12/24/2014

Duct detection is required for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the panel. For information only
Licensed Contractors Rejected 12/24/2014 12/24/2014
Joe Frogge
LC - General Contractor
Corrective Action Required
12/24/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
12/24/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Building Plan Review Rejected 12/16/2014 12/11/2014
Joe Frogge
License Tax Application
Corrective Action Required
12/11/2014

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment for informational purposes.
Final Development Plan
Corrective Action Required
12/11/2014

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment for informational purposes.
Misc
Corrective Action Required
12/11/2014

2012 IBC 716.5 Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 716.5.1, 716.5.2 or 716.5.3 and the fire protection rating indicated in Table 716.5. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 716.5.6. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and the NFPA 80. Action required: Specify door ratings where required in fire/smoke barriers.
Accessibility - Fixed sidewall grab bars 604.5.1
Corrective Action Required
12/11/2014

ICC A117.1-2009 604.5.1 – Fixed side wall grab bars. Fixed side-wall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: Specify installation of vertical grab bars at accessible toilets.
Misc
Corrective Action Required
12/11/2014

2012 IFGC 503.6.4 Gas Vent Terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches or less in size and located not less than 8 feet from a vertical wall or similar obstruction shall terminate above the roof in accordance with Figure 503.6.4. 2. Gas vents that are over 12 inches in size or are located less than 8 feet from a vertical wall or similar obstruction shall terminate not less than 2 feet above the highest point where they pass through the roof and not less than 2 feet above any portion of a building within 10 feet horizontally. 3. As provided for industrial appliances in Section 503.2.2.2. 4. As provided for direct-vent systems in Section 503.2.3. 5. As provided for appliances with integral vents in Section 503.2.4. 6. As provided for mechanical draft systems in Section 503.3.3. 7. As provided for ventilating hoods and exhaust systems in Section 503.3.4. Action required: Modify design to depict how NG vents will be terminated in compliance with IFGC.
Bldg - Accessibility - Kitchens and kitchenettes 1109.4
Corrective Action Required
12/11/2014

2012 IBC 1109.4 – Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible. Action required: Refrigerator specified (with freezer above) is not accessible.
Licensed Contractors Rejected 12/16/2014 12/11/2014
Joe Frogge
LC - General Contractor
Corrective Action Required
12/11/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
12/11/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 12/16/2014 12/08/2014
Brian Austerman
Misc
Corrective Action Required
12/08/2014

Provide Medical Gas Certifications prior to final
Construction documents for fire alarm systems
Corrective Action Required
12/08/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Alarm contractor shall provide plans for work to be performed
Construction documents - Fire protection systems
Corrective Action Required
12/08/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Sprinkler contractor shall provide plans for sprinkler work to be performed
Misc
Corrective Action Required
12/08/2014

Duct detection is required for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the panel. For information only
Misc
Corrective Action Required
07/09/2015

5306.2.1 One-hour exterior rooms. A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by fire barriers constructed in accordance with Section 707 of the International Building Code or horizontal assemblies constructed in accordance with Section 711 of the International Building Code, or both, with a fire-resistance rating of not less than 1 hour. Openings between the room or enclosure and interior spaces shall be self-closing smoke- and draft-control assemblies having a fire protection rating of not less than 1 hour. Rooms shall have at least one exterior wall that is provided with at least two vents. Each vent shall not be less than 36 square inches (0.023 m2) in area. One vent shall be within 6 inches (152 mm) of the floor and one shall be within 6 inches (152 mm) of the ceiling. Rooms shall be provided with at least one automatic sprinkler to provide container cooling in case of fire. 5306.2.2 One-hour interior room. When an exterior wall cannot be provided for the room, automatic sprinklers shall be installed within the room. The room shall be exhausted through a duct to the exterior. Supply and exhaust ducts shall be enclosed in a 1-hour-rated shaft enclosure from the room to the exterior. Approved mechanical ventilation shall comply with the International Mechanical Code and be provided at a minimum rate of 1 cubic foot per minute per square foot [0.00508 m3/(s · m2)] of the area of the room. Plans did not show the specs on the med gas room, room shall be constructed according to IFC 2012 Information only
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $12,826.90 $12,826.90 Paid 03/05/2015
Water Meter Fee $2,266.44 $2,266.44 Paid 03/05/2015
Water Tap Fee $21,320.00 $21,320.00 Paid 03/05/2015
8331507-Sewer Connection Fee $1,080.00 $1,080.00 Paid 03/05/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 4/16/2015 4/16/2015 at 12:00 AM 04/16/2015
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
04/16/2015
TOILET A102; A103; A124 MECH A111
Underslab Plumbing Inspection - Commercial Not Ready 4/21/2015 at 12:00 AM 04/21/2015
Underslab Plumbing Inspection - Commercial Partial 4/22/2015 4/21/2015 at 12:00 AM 04/21/2015
Misc
Partial Correction
04/21/2015
TOILET A102; A103; A124 MECH A111
Misc
Partial Correction
04/21/2015
OK TO COVER WHEN READY UNDER-SLAB PVC DWV PIPING AT: (A) TO (B.3) FROM (1.5) TO (6.8);
Underslab Electrical Inspection - Commercial Partial 4/28/2015 at 12:00 AM 04/28/2015
Misc
Partial Correction
04/28/2015
OK TO COVER WHEN READY UNDER-SLAB ELECTRICAL CONDUIT & FLOOR BOXES AT: 4 CONDUITS FROM NURSE STATION TO 16' NORTH;
Underslab Plumbing Inspection - Commercial Partial 4/28/2015 at 12:00 AM 04/28/2015
Misc
Partial Correction
04/28/2015
TOILET A102; A103; A124 MECH A111
Misc
Partial Correction
04/28/2015
OK TO COVER WHEN READY UNDER-SLAB PVC DWV PIPING AT: (A) TO (B.3) FROM (1.5) TO (6.8); BUILDING DRAIN FROM (6.8) SOUTH UNDER FOOTING;
Underslab Plumbing Inspection - Commercial Partial 5/1/2015 5/1/2015 at 12:00 AM 05/01/2015
Misc
Partial Correction
04/28/2015
OK TO COVER WHEN READY UNDER-SLAB PVC DWV PIPING AT: (A) TO (B.3) FROM (1.5) TO (6.8); BUILDING DRAIN FROM (6.8) SOUTH UNDER FOOTING; COMPLETE INCLUDING AT A124, 126 & 130 -- BUT NOT READY AT RECOVERY A125;
Misc
Partial Correction
05/01/2015
DOMESTIC WATER SERVICE ENTRY TO BUILDING AT A125 IS 3" D.I. IN LIEU OF 2-1/2" COPPER PER DRAWINGS. RFI TO BE SUBMITTED TO CODES.
Underslab Electrical Inspection - Commercial Partial 5/1/2015 at 12:00 AM 05/01/2015
Misc
Partial Correction
05/01/2015
OK TO COVER WHEN READY UNDER-SLAB ELECTRICAL CONDUIT & FLOOR BOXES AT: 4 CONDUITS FROM NURSE STATION TO 16' NORTH; AT PAIN MANAGEMENT ROOMS A139-A142;
Underslab Plumbing Inspection - Commercial Partial 5/5/2015 5/5/2015 at 12:00 AM 05/05/2015
Misc
Partial Correction
05/01/2015
OK TO COVER WHEN READY UNDER-SLAB PVC DWV PIPING AT: (A) TO (B.3) FROM (1.5) TO (6.8); BUILDING DRAIN FROM (6.8) SOUTH UNDER FOOTING; COMPLETE INCLUDING AT A124, 126, 130 AND A125 -- WHERE 3" DUCTILE IRON WATER PIPE IS APPROVED FOR WATER SERVICE IN LIEU OF 2-1/2" TYPE K COPPER
Misc
Resolved
05/05/2015
DOMESTIC WATER SERVICE ENTRY TO BUILDING AT A125 IS 3" D.I. IN LIEU OF 2-1/2" COPPER PER DRAWINGS. RFI TO BE SUBMITTED TO CODES.
In-wall Inspection Not Ready 5/14/2015 5/14/2015 at 12:00 AM 05/14/2015
Misc
Corrective Action Required
05/14/2015
IBC 109.1, 109.5; IRC R109.3 INSPECTION ACCESS: PROPERTY LOCKED; INTERIOR NOT ACCESSIBLE. CALL FOR INSPECTION ON DAY WHEN JOBSITE IS ACCESSIBLE.
In-wall Inspection Partial 5/15/2015 5/15/2015 at 12:00 AM 05/15/2015
Misc
Partial Correction
05/15/2015
OK TO TOP-OUT WALLS 4' WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: A104; 105; 106; 107; 108; 109; 110; 111; 113; 114; 116; 119; 131S; 138; [139; 140; 141; 142]B/F;
Rated Assembly Inspection Partial 5/19/2015 at 12:00 AM 05/19/2015
Misc
Partial Correction
05/19/2015
ONE LAYER 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A116 NORTH; SAME AT CORR A110 O/S A116 W; SAME @ A150 W, 152 W&S, ABOVE DOOR #A133b;
Misc
Partial Correction
05/19/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
In-wall Inspection Partial 6/5/2015 at 12:00 AM 06/05/2015
Misc
Partial Correction
05/15/2015
OK TO TOP-OUT WALLS 4' WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: A104; 105; 106; 107; 108; 109; 110; 111; 113; 114; 116; 119; 131S; 138; [139; 140; 141; 142]B/F; A111; A143 WEST;
In-wall Inspection Partial 6/5/2015 at 12:00 AM 06/05/2015
Misc
Partial Correction
06/05/2015
OK TO TOP-OUT WALLS 4' WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: A104; 105; 106; 107; 108; 109; 110; 111; 113; 114; 116; 119; 131S; 138; [139; 140; 141; 142]B/F;
Misc
Partial Correction
06/05/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: A111; A143 WEST;
Rated Assembly Inspection Partial 6/9/2015 6/9/2015 at 12:00 AM 06/09/2015
Misc
Partial Correction
06/08/2015
ONE LAYER 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A116 NORTH; SAME AT CORR A110 O/S A116 W; SAME @ A150 W, 152 W&S, ABOVE DOOR #A133b;
Misc
Partial Correction
06/08/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Misc
Partial Correction
06/09/2015
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: A111; EXISTING LOBBY EAST WALL OPPOSITE A143;
Rated Assembly Inspection Not Ready 6/18/2015 6/18/2015 at 12:00 AM 06/18/2015
Misc
Partial Correction
06/09/2015
ONE LAYER 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A116 NORTH; SAME AT CORR A110 O/S A116 W; SAME @ A150 W, 152 W&S, ABOVE DOOR #A133b;
Misc
Partial Correction
06/09/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Misc
Partial Correction
06/09/2015
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: A111 E & S; EXISTING LOBBY EAST WALL OPPOSITE A143;
Misc
Partial Correction
06/18/2015
CONSTRUTION NOTED, BUT NOT SHOWN ON APPROVED DRAWINGS: FRAMING & 1" SHAFT LINER BOARD AT UPPER 4' OF EAST WALL OF SPACES 100/102/103. REIVSED DRAWINGS MUST BE SUBMITTED TO LS CODES ADMINISTRATION FOR APPROVAL AND INSERTION IN FIELD AND OFFICE SETS.
Underslab Electrical Inspection - Commercial Partial 6/19/2015 at 12:00 AM 06/19/2015
Misc
Partial Correction
05/01/2015
OK TO COVER WHEN READY UNDER-SLAB ELECTRICAL CONDUIT & FLOOR BOXES AT: 4 CONDUITS FROM NURSE STATION TO 16' NORTH; AT PAIN MANAGEMENT ROOMS A139-A142; NUMEROUS CONDUITS ENTERING BUILDING THROUGH 8" BORE THROUGH FOOTING AND EXTENDING TO VARIOUS LOCATIONS IN SPACES A117 & A118;
Footing Inspection - Commercial Failed 6/23/2015 at 12:00 AM 06/23/2015
Misc
Corrective Action Required
06/23/2015
CORNER BARS MUST BE FULL SIZE
Misc
Corrective Action Required
06/23/2015
SPLICES MUST BE 40 DIAMETERS
Misc
Corrective Action Required
06/23/2015
3" RE-BAR CLEARANCE REQUIRED AT BOTTOMS AND BANKS
Footing Inspection - Commercial Passed 6/23/2015 (3:30) 6/23/2015 at 12:00 AM 06/23/2015
Misc
Resolved
06/23/2015
CORNER BARS MUST BE FULL SIZE
Misc
Resolved
06/23/2015
SPLICES MUST BE 40 DIAMETERS
Misc
Resolved
06/23/2015
3" RE-BAR CLEARANCE REQUIRED AT BOTTOMS AND BANKS
Foundation Inspection - Commercial Partial 6/29/2015 (9:30) 6/29/2015 at 12:00 AM 06/29/2015
Misc
Partial Correction
06/29/2015
OK TO POUR WHEN READY 5" THICK EQUIPMENT SLAB AT 1.2/A.5 PREPED WITH MAT OF #4 REBAR AT MID-DEPTH @ 16" O/C E/W
In-wall Inspection Partial 6/30/2015 6/30/2015 at 12:00 AM 06/30/2015
Misc
Partial Correction
06/05/2015
OK TO TOP-OUT WALLS 4' WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: A104; 105; 106; 107; 108; 109; 110; 111; 113; 114; 116; 119; 131S; 138; [139; 140; 141; 142]B/F;
Misc
Partial Correction
06/05/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: A111; 143 WEST; 136; 137; 139-142;
In-wall Inspection Partial 7/7/2015 7/7/2015 at 12:00 AM 07/07/2015
Misc
Resolved
07/07/2015
OK TO TOP-OUT WALLS 4' WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: A104; 105; 106; 107; 108; 109; 110; 111; 113; 114; 116; 119; 131S; 138; 139; 140; 141; 142]B/F;
Misc
Partial Correction
06/30/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: A111; 143 WEST; 136; 137; 139-142; [102; 103; 105; 106; 107; 108; 113; 117; 121; 123; 134; 135; 145; 147; 148;
Rated Assembly Inspection Partial 7/8/2015 at 12:00 AM 07/08/2015
Misc
Partial Correction
06/18/2015
ONE LAYER 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A116 NORTH; SAME AT CORR A110 O/S A116 W; SAME @ A150 W, 152 W&S, ABOVE DOOR #A133b;
Misc
Partial Correction
06/18/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Misc
Partial Correction
06/18/2015
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: A111 E & S; EXISTING LOBBY EAST WALL OPPOSITE A143;
Misc
Partial Correction
06/18/2015
CONSTRUTION NOTED, BUT NOT SHOWN ON APPROVED DRAWINGS: FRAMING & 1" SHAFT LINER BOARD + ONE LAYER 5/8" TYPE X GWB AT UPPER 4' OF EAST WALL OF SPACES 100/102/103; RECENTLY REVISED DRAWINGS CALL FOR UL DESIGN U465, CONTRARY TO WHAT HAS BEEN BUILT. APPROVAL PENDING A/E CLARIFICATION OF WALL TYPE FOR APPROVAL AND POSTING TO FIELD AND OFFICE SETS.
Underslab Plumbing Inspection - Commercial Passed 5/5/2015 at 12:00 AM 07/08/2015
Misc
Resolved
07/08/2015
OK TO COVER WHEN READY UNDER-SLAB PVC DWV PIPING AT: (A) TO (B.3) FROM (1.5) TO (6.8); BUILDING DRAIN FROM (6.8) SOUTH UNDER FOOTING; COMPLETE INCLUDING AT A124, 126, 130 AND A125 -- WHERE 3" DUCTILE IRON WATER PIPE IS APPROVED FOR WATER SERVICE IN LIEU OF 2-1/2" TYPE K COPPER
Underslab Electrical Inspection - Commercial Passed 6/19/2015 at 12:00 AM 07/08/2015
Misc
Resolved
07/08/2015
OK TO COVER WHEN READY UNDER-SLAB ELECTRICAL CONDUIT & FLOOR BOXES AT: 4 CONDUITS FROM NURSE STATION TO 16' NORTH; AT PAIN MANAGEMENT ROOMS A139-A142; NUMEROUS CONDUITS ENTERING BUILDING THROUGH 8" BORE THROUGH FOOTING AND EXTENDING TO VARIOUS LOCATIONS IN SPACES A117 & A118;
Rated Assembly Inspection Partial 7/8/2015 at 12:00 AM 07/08/2015
Misc
Partial Correction
07/08/2015
ONE LAYER 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A116 NORTH; SAME AT CORR A110 O/S A116 W; SAME @ A150 W, 152 W&S, ABOVE DOOR #A133b;
Misc
Partial Correction
07/08/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Misc
Partial Correction
07/08/2015
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: A111 E & S; EXISTING LOBBY EAST WALL OPPOSITE A143;
Misc
Partial Correction
07/08/2015
CONSTRUCTION NOTED, BUT NOT SHOWN ON APPROVED DRAWINGS: FRAMING & 1" SHAFT LINER BOARD + ONE LAYER 5/8" TYPE X GWB AT UPPER 4' OF EAST WALL OF SPACES 100/102/103; RECENTLY REVISED DRAWINGS CALL FOR UL DESIGN U465, CONTRARY TO WHAT HAS BEEN BUILT. APPROVAL PENDING A/E CLARIFICATION OF WALL TYPE FOR APPROVAL AND POSTING TO FIELD AND OFFICE SETS.
Rated Assembly Inspection Partial 7/9/2015 7/9/2015 at 12:00 AM 07/09/2015
Misc
Partial Correction
07/08/2015
ONE LAYER 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A116 NORTH; SAME AT CORR A110 O/S A116 W; SAME @ A150 W, 152 W&S, ABOVE DOOR #A133b;
Misc
Partial Correction
07/08/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Misc
Partial Correction
07/08/2015
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: A111 E & S; EXISTING LOBBY EAST WALL OPPOSITE A143; ELECT A117 W, S, E WALLS; WALL SEPARATING A139 & A140; RECESSES/INFILLS AT EX CORR 11 @ NEW D.F. & THREE LOCATIONS @ EX CORR 7 N END;
In-wall Inspection Partial 7/9/2015 7/9/2015 at 12:00 AM 07/09/2015
Misc
Partial Correction
07/07/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: A102; 103; 105; 106; 107; 108; 111; 113; 117; 121; 123; 134; 135; 136; 137; 139-142; 143 WEST; 145; 147; 148; [A125 BAYS 6,7,8; A133 BAYS 7,8; 154; 155; 156;
Underground Electrical Inspection - Commercial Passed 7/16/2015 7/16/2015 at 12:00 AM 07/16/2015
Footing Inspection - Commercial Passed 7/17/2015 (11:00) 7/17/2015 at 12:00 AM 07/17/2015
Rated Assembly Inspection Partial 7/17/2015 at 12:00 AM 07/17/2015
Misc
Resolved
07/17/2015
Misc
Partial Correction
07/09/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Misc
Partial Correction
07/09/2015
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: A111 E & S; EXISTING LOBBY EAST WALL OPPOSITE A143; ELECT A117 W, S, E WALLS; WALL SEPARATING A139 & A140; RECESSES/INFILLS AT EX CORR 11 @ NEW D.F. & THREE LOCATIONS @ EX CORR 7 N END; A148 OPPOSITE D.F. @ CORRIDOR; A108 N WALL; A135 S, E, N(EXCEPT WF STEEL BEAM @ TOP); A124 N WALL;
In-wall Inspection Partial 7/17/2015 at 12:00 AM 07/17/2015
Misc
Partial Correction
07/09/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: A102; 103; 105; 106; 107; 108; 111; 113; 117; 121; 123; 134; 135; 136; 137; 139-142; 143 WEST; 145; 147; 148; [A125 BAYS 6,7,8; A133 BAYS 7,8; 154; 155; 156;
Misc
Partial Correction
07/17/2015
OK TO HANG ONE LAYER 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A116 NORTH; SAME AT CORR A110 O/S A116 W; SAME @ A150 W, 152 W&S, ABOVE DOOR #A133b; A118 S WALL FOR 4' TOP-OUT AT BOTH FACES;
In-wall Inspection Partial 7/17/2015 at 12:00 AM 07/17/2015
Misc
Partial Correction
07/17/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: A102; 103; 105; 106; 107; 108; 111; 113; 117; 121; 123; 134; 135; 136; 137; 139-142; 143 WEST; 145; 147; 148; [A125 BAYS 6,7,8; A133 BAYS 7,8; 154; 155; 156; PAIN PRE-OP A120 BAYS 1-4;
Misc
Partial Correction
07/17/2015
OK TO TOP-OUT GWB AT CORR A112 OUTSIDE A116 NORTH; SAME AT CORR A110 O/S A116 W; SAME @ A150 W, 152 W&S, ABOVE DOOR #A133b; A118 S WALL FOR 4' TOP-OUT AT BOTH FACES;
Underground Plumbing Inspection - Commercial Passed 7/21/2015 (2:00) 7/21/2015 at 12:00 AM 07/21/2015
Rated Assembly Inspection Partial 7/22/2015 at 12:00 AM 07/22/2015
Misc
Partial Correction
07/17/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Misc
Partial Correction
07/17/2015
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: A111 E & S; EXISTING LOBBY EAST WALL OPPOSITE A143; ELECT A117 W, S, E WALLS; WALL SEPARATING A139 & A140; RECESSES/INFILLS AT EX CORR 11 @ NEW D.F. & THREE LOCATIONS @ EX CORR 7 N END; A148 OPPOSITE D.F. @ CORRIDOR; A108 N WALL; A135 S, E, N(EXCEPT WF STEEL BEAM @ TOP); A124 N WALL; [S WALL OF SPACES 120 BAYS 5 & 6, 123, 122; BEAM WRAP @ 108 N; 113 E & W;
In-wall Inspection Partial 7/22/2015 7/22/2015 at 12:00 AM 07/22/2015
Misc
Partial Correction
07/17/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: A102; 103; 105; 106; 107; 108; 111; 113; 117; 121; 123; 134; 135; 136; 137; 139-142; 143 WEST; 145; 147; 148; A125 BAYS 6,7,8; A133 BAYS 7,8; 154; 155; 156; PAIN PRE-OP A120 BAYS 1-4; [100 E, N, W; 116; 120; A125 BAYS 2-5; 131; 132; 138; 143;
Misc
Partial Correction
07/17/2015
OK TO TOP-OUT GWB AT CORR A112 OUTSIDE A116 NORTH; SAME AT CORR A110 O/S A116 W; SAME @ A150 W, 152 W&S, ABOVE DOOR #A133b; A118 S WALL FOR 4' TOP-OUT AT BOTH FACES;
In-wall Inspection Partial 7/28/2015 7/28/2015 at 12:00 AM 07/28/2015
Misc
Partial Correction
07/22/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: A100 E, N, W; 102; 103; 105; 106; 107; 108; 111; 113; 116; 117; 120; PAIN PRE-OP A120 BAYS 1-4; 121; 123; A125 BAYS 2-5; A125 BAYS 6,7,8; 131; 132; A133 BAYS 7,8; 134; 135; 136; 137; 138; 139-142; 143 WEST; 143; 145; 147; 148; 154; 155; 156; [EXSTG CORR RECESS @ DOOR 133A; 110; 112; 114; 119; 124; 125; 127; 128; 129; 130; 133; 145; 146; 147; 148; 149;
Rated Assembly Inspection Partial 7/28/2015 at 12:00 AM 07/28/2015
Misc
Partial Correction
07/22/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Misc
Partial Correction
07/22/2015
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: A111 E & S; EXISTING LOBBY EAST WALL OPPOSITE A143; ELECT A117 W, S, E WALLS; WALL SEPARATING A139 & A140; RECESSES/INFILLS AT EX CORR 11 @ NEW D.F. & THREE LOCATIONS @ EX CORR 7 N END; A148 OPPOSITE D.F. @ CORRIDOR; A108 N WALL; A135 S, E, N(EXCEPT WF STEEL BEAM @ TOP); A124 N WALL; S WALL OF SPACES 120 BAYS 5 & 6, 123, 122; BEAM WRAP @ 108 N; 113 E & W; [116; 120 N WALL @ BAYS 1-4; 136; 143; 155;
Piers/Caissons Inspection - Commercial Partial 8/4/2015 (1:00) 8/4/2015 at 12:00 AM 08/04/2015
Misc
Partial Correction
08/04/2015
OK TO POUR WHEN READY TWO 42" DRILLED PIERS PER DRAWING SHEETS S001 & S002 + RFI -0035
Above Ceiling Inspection Partial 8/4/2015 at 12:00 AM 08/04/2015
Misc
Partial Correction
08/04/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS @ A100, 104, 126, 137;
Rated Assembly Inspection Partial 8/4/2015 at 12:00 AM 08/04/2015
Misc
Partial Correction
07/28/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Misc
Partial Correction
07/28/2015
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: A111 E & S; EXISTING LOBBY EAST WALL OPPOSITE A143; ELECT A117 W, S, E WALLS; WALL SEPARATING A139 & A140; RECESSES/INFILLS AT EX CORR 11 @ NEW D.F. & THREE LOCATIONS @ EX CORR 7 N END; A148 OPPOSITE D.F. @ CORRIDOR; A108 N WALL; A135 S, E, N(EXCEPT WF STEEL BEAM @ TOP); A124 N WALL; S WALL OF SPACES 120 BAYS 5 & 6, 123, 122; BEAM WRAP @ 108 N; 113 E & W; [116; 120 N WALL @ BAYS 1-4; 136; 143; 155; [FIRE WALLS W/ STAFF LOUNGE A143 @ N & W; HALLWAY SIDE OF SOILED UTILITY A135; A130 & A124 TO 9' AFF; A154 N & W; A116 W, N, E WALLS CORR FACE; 129 N; 130 N;
In-wall Inspection Partial 8/4/2015 8/5/2015 at 12:00 AM 08/05/2015
Misc
Partial Correction
07/28/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL & SOFFIT FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: A100 E, N, W; 102; 103; 105; 106; 107; 108; 110; 111; 112; 113; 114; 116; 117; 119; 120; PAIN PRE-OP A120 BAYS 1-4; 121; 123; A125 BAYS 2-5; 124; 125; 125 BAYS 6,7,8; 127; 128; 129; 130; 131; 132; 133; A133 BAYS 7,8; EXSTG CORR RECESS @ DOOR 133A; 134; 135; 136; 137; 138; 139-142; 143 WEST; 143; 145; 146; 147; 148; 149; 154; 155; 156; [117 N; 118 S EXCEPT W 8' & E 4';
In-wall Inspection Partial 8/6/2015 8/6/2015 at 12:00 AM 08/06/2015
Misc
Partial Correction
08/05/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL & SOFFIT FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: A100 E, N, W; 102; 103; 105; 106; 107; 108; 110; 111; 112; 113; 114; 116; 117; 119; 120; PAIN PRE-OP A120 BAYS 1-4; 121; 123; A125 BAYS 2-5; 124; 125; 125 BAYS 6,7,8; 127; 128; 129; 130; 131; 132; 133; A133 BAYS 7,8; EXSTG CORR RECESS @ DOOR 133A; 134; 135; 136; 137; 138; 139-142; 143 WEST; 143; 145; 146; 147; 148; 149; 154; 155; 156; 117 N; [118 S; 150; 151; 152; 126 NW;
Above Ceiling Inspection Partial 8/6/2015 at 12:00 AM 08/06/2015
Misc
Partial Correction
08/06/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS @ A100, 104, 126, 137, 120 @ SINK, 148;
Above Ceiling Inspection Partial 8/7/2015 at 12:00 AM 08/07/2015
Misc
Partial Correction
08/06/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS @ A100, 104, 126, 137, 120 @ SINK, 148; SOFFITS @ A127 & A145;
Above Ceiling Inspection Partial 8/4/2015 at 12:00 AM 08/07/2015
Corrective Action Required
08/06/2015
Rated Assembly Inspection Partial 8/7/2015 at 12:00 AM 08/07/2015
Misc
Partial Correction
08/07/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Misc
Partial Correction
08/07/2015
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: A111 E & S; EXISTING LOBBY EAST WALL OPPOSITE A143; ELECT A117 W, S, E WALLS; WALL SEPARATING A139 & A140; RECESSES/INFILLS AT EX CORR 11 @ NEW D.F. & THREE LOCATIONS @ EX CORR 7 N END; A148 OPPOSITE D.F. @ CORRIDOR; A108 N WALL; A135 S, E, N(EXCEPT WF STEEL BEAM @ TOP); A124 N WALL; S WALL OF SPACES 120 BAYS 5 & 6, 123, 122; BEAM WRAP @ 108 N; 113 E & W; [116; 120 N WALL @ BAYS 1-4; 136; 143; 155; [FIRE WALLS W/ STAFF LOUNGE A143 @ N & W; HALLWAY SIDE OF SOILED UTILITY A135; A130 & A124 TO 9' AFF; A154 N & W; A116 W, N, E WALLS CORR FACE; 129 N; 130 N; A117 N WALL; A126 NW TO 10' AFF;
Underground Electrical Inspection - Commercial Passed 8/10/2015 at 12:00 AM 08/10/2015
Rated Assembly Inspection Partial 8/10/2015 8/10/2015 at 12:00 AM 08/10/2015
Misc
Partial Correction
08/07/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Misc
Partial Correction
08/10/2015
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: A111 E & S; EXISTING LOBBY EAST WALL OPPOSITE A143; ELECT A117 W, S, E WALLS; WALL SEPARATING A139 & A140; RECESSES/INFILLS AT EX CORR 11 @ NEW D.F. & THREE LOCATIONS @ EX CORR 7 N END; A148 OPPOSITE D.F. @ CORRIDOR; A108 N WALL; A135 S, E, N(EXCEPT WF STEEL BEAM @ TOP); A124 N WALL; S WALL OF SPACES 120 BAYS 5 & 6, 123, 122; BEAM WRAP @ 108 N; 113 E & W; 116; 120 N WALL @ BAYS 1-4; 136; 143; 155; FIRE WALLS W/ STAFF LOUNGE A143 @ N & W; HALLWAY SIDE OF SOILED UTILITY A135; A130 & A124 TO 9' AFF; A154 N & W; A116 W, N, E WALLS CORR FACE; 129 N; 130 N; A117 N WALL; A126 NW TO 10' AFF; [A118 S; A150 N, W TO 10' AFF; A152 W, S;
Sewer Service Inspection Passed 8/13/2015 (8:00) 8/12/2015 at 12:00 AM 08/12/2015
Rated Assembly Inspection Partial 8/13/2015 8/13/2015 at 12:00 AM 08/13/2015
Misc
Partial Correction
08/10/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Misc
Partial Correction
08/10/2015
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: A111 E & S; EXISTING LOBBY EAST WALL OPPOSITE A143; ELECT A117 W, S, E WALLS; WALL SEPARATING A139 & A140; RECESSES/INFILLS AT EX CORR 11 @ NEW D.F. & THREE LOCATIONS @ EX CORR 7 N END; A148 OPPOSITE D.F. @ CORRIDOR; A108 N WALL; A135 S, E, N(EXCEPT WF STEEL BEAM @ TOP); A124 N WALL; S WALL OF SPACES 120 BAYS 5 & 6, 123, 122; BEAM WRAP @ 108 N; 113 E & W; 116; 120 N WALL @ BAYS 1-4; 136; 143; 155; FIRE WALLS W/ STAFF LOUNGE A143 @ N & W; HALLWAY SIDE OF SOILED UTILITY A135; A130 & A124 TO 9' AFF; A154 N & W; A116 W, N, E WALLS CORR FACE; 129 N; 130 N; A117 N WALL; A126 NW TO 10' AFF; A118 S; A150 N, W TO 10' AFF; A152 W, S; A150 N & W ABOVE 10' AFF; CORRIDOR FACE OUTSIDE A150 & 152;
In-wall Inspection Partial 8/13/2015 at 12:00 AM 08/13/2015
Misc
Partial Correction
08/06/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL & SOFFIT FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: A100 E, N, W; 102; 103; 105; 106; 107; 108; 110; 111; 112; 113; 114; 116; 117; 119; 120; PAIN PRE-OP A120 BAYS 1-4; 121; 123; A125 BAYS 2-5; 124; 125; 125 BAYS 6,7,8; 127; 128; 129; 130; 131; 132; 133; A133 BAYS 7,8; EXSTG CORR RECESS @ DOOR 133A; 134; 135; 136; 137; 138; 139-142; 143 WEST; 143; 145; 146; 147; 148; 149; 154; 155; 156; 117 N; [118 S; 150; 151; 152; 126 NW; A150 SE @ DOOR; A101 NORTH WALL; A109;
Above Ceiling Inspection Partial 8/13/2015 at 12:00 AM 08/13/2015
Misc
Partial Correction
08/13/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS @ A100, 104, 126, 137, 120 @ SINK, 148; SOFFITS @ A127 & A145; SOFFITS @ A125 N & S;
Rated Assembly Inspection Partial 8/18/2015 at 12:00 AM 08/18/2015
Misc
Partial Correction
08/18/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
In-wall Inspection Partial 8/18/2015 at 12:00 AM 08/18/2015
Rated Assembly Inspection Partial 8/21/2015 at 12:00 AM 08/21/2015
Misc
Partial Correction
08/13/2015
OK TO COVER WHEN READY COMPONENTS OF 2-HR FIRE-RATED WALLS AT LOCATIONS: TWO LAYERS 5/8" TYPE X GWB TOP-OUT AT CORR A112 OUTSIDE A114 SOUTH;
Rated Assembly Inspection Passed 8/21/2015 at 12:00 AM 08/21/2015
Gas Piping Inspection - Commercial Passed 8/21/2015 at 12:00 AM 08/21/2015
Gas Service Inspection - Commercial Failed 8/21/2015 at 12:00 AM 08/21/2015
Misc
Corrective Action Required
08/21/2015
LSCO 7-608: GAS PIPING TEST PRESSURE DECREASED DURING MONITORING PERIOD. CORRECT AND PRESSURIZE PIPING SYSTEM TO HOLD STEADY AT MINIMUM 10 PSI
Rated Assembly Inspection Passed 8/25/2015 8/25/2015 at 12:00 AM 08/25/2015
Gas Service Inspection - Commercial Passed 8/25/2015 at 12:00 AM 08/25/2015
Misc
Resolved
08/25/2015
LSCO 7-608: GAS PIPING TEST PRESSURE DECREASED DURING MONITORING PERIOD. CORRECT AND PRESSURIZE PIPING SYSTEM TO HOLD STEADY AT MINIMUM 10 PSI
Underground Plumbing Inspection - Commercial Passed 8/27/2015 at 12:00 AM 08/27/2015
Rated Assembly Inspection Failed 8/28/2015 8/28/2015 at 12:00 AM 08/28/2015
Misc
Corrective Action Required
08/28/2015
RATED WALL AT 153 N NOT APPROVED.
Rated Assembly Inspection Passed 9/1/2015 9/1/2015 at 12:00 AM 09/01/2015
Misc
Resolved
09/01/2015
OK TO TAPE, MUD, AND FIRE-STOP RATED WALL AT 153 NORTH
Above Ceiling Inspection Partial 9/4/2015 9/4/2015 at 12:00 AM 09/04/2015
Misc
Partial Correction
09/04/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS @ A100, 104, 126, 137, 120 @ SINK, 148; SOFFITS @ A127 & A145; SOFFITS @ A125 N & S;
Misc
Partial Correction
09/04/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 120 BAYS 5&6; 122; 123; 125; 127; 128; 131; 132; 133; 137; 138 EXCEPT BOTH FACES OF BULKHEAD AT DOOR 133B; 139; 140; 141; 142; 143;
Rough Framing Inspection - Commercial Passed 9/4/2015 at 12:00 AM 09/04/2015
Above Ceiling Inspection Not Ready 9/10/2015 at 12:00 AM 09/10/2015
Misc
Partial Correction
09/10/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS @ A100, 104, 126, 137, 120 @ SINK, 148; SOFFITS @ A127 & A145; SOFFITS @ A125 N & S;
Misc
Partial Correction
09/10/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 120 BAYS 5&6; 122; 123; 125; 127; 128; 131; 132; 133; 137; 138 EXCEPT BOTH FACES OF BULKHEAD AT DOOR 133B; 139; 140; 141; 142; 143;
Misc
Corrective Action Required
09/10/2015
CEILING FRAMING & ABOVE-CEILING SYSTEMS AT ENTRANCE CANOPY: NOTHING ON DRAWINGS TO INDICATE INTERMEDIATE SUPPORT OF JOISTS
Above Ceiling Inspection Partial 9/11/2015 9/11/2015 at 12:00 AM 09/11/2015
Misc
Partial Correction
09/10/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS @ A100, 104, 126, 137, 120 @ SINK, 148; SOFFITS @ A127 & A145; SOFFITS @ A125 N & S;
Misc
Partial Correction
09/10/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 120 BAYS 5&6; 122; 123; 125; 127; 128; 131; 132; 133; 137; 138 EXCEPT BOTH FACES OF BULKHEAD AT DOOR 133B; 139; 140; 141; 142; 143; [100-110; 113; 120-123; 126-129; 134-136; 143 EXCEPT W 3'; 145-147; 148 EXCEPT W 3'; BULKHEAD AT DOOR 133B;
Misc
Corrective Action Required
09/10/2015
CEILING FRAMING & ABOVE-CEILING SYSTEMS AT ENTRANCE CANOPY: NOTHING ON DRAWINGS TO INDICATE INTERMEDIATE SUPPORT OF JOISTS
Above Ceiling Inspection Partial 9/15/2015 9/15/2015 at 12:00 AM 09/15/2015
Misc
Partial Correction
09/11/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS @ A100, 104, 126, 137, 120 @ SINK, 148; SOFFITS @ A127 & A145; SOFFITS @ A125 N & S; A150; 152 EXCEPT AT J.B. @ W TO BE MADE UP & CLOSED;
Misc
Partial Correction
09/11/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 120 BAYS 5&6; 122; 123; 125; 127; 128; 131; 132; 133; 137; 138 EXCEPT BOTH FACES OF BULKHEAD AT DOOR 133B; 139; 140; 141; 142; 143; [100-110; 113; 120-123; 126-129; 134-136; 143 EXCEPT W 3'; 145-147; 148 EXCEPT W 3'; BULKHEAD AT DOOR 133B;
Misc
Corrective Action Required
09/11/2015
CEILING FRAMING & ABOVE-CEILING SYSTEMS AT ENTRANCE CANOPY: NOTHING ON DRAWINGS TO INDICATE INTERMEDIATE SUPPORT OF JOISTS
Above Ceiling Inspection Partial 9/21/2015 at 12:00 AM 09/21/2015
Misc
Partial Correction
09/15/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS @ A100, 104, 126, 137, 120 @ SINK, 148; SOFFITS @ A127 & A145; SOFFITS @ A125 N & S; A150; 152 EXCEPT AT J.B. @ W TO BE MADE UP & CLOSED;
Misc
Partial Correction
09/15/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 120 BAYS 5&6; 122; 123; 125; 127; 128; 131; 132; 133; 137; 138 EXCEPT BOTH FACES OF BULKHEAD AT DOOR 133B; 139; 140; 141; 142; 143; [100-110; 113; 120-123; 126-129; 134-136; 143 EXCEPT W 3'; 145-147; 148 EXCEPT W 3'; BULKHEAD AT DOOR 133B;
Misc
Resolved
09/21/2015
CEILING FRAMING & ABOVE-CEILING SYSTEMS AT ENTRANCE CANOPY: NOTHING ON DRAWINGS TO INDICATE INTERMEDIATE SUPPORT OF JOISTS
Above Ceiling Inspection Partial 9/23/2015 9/23/2015 at 12:00 AM 09/23/2015
Misc
Partial Correction
09/21/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS @ A100, 104, 126, 137, 120 @ SINK, 148; SOFFITS @ A127 & A145; SOFFITS @ A125 N & S; A150; 152; A153 O.R.
Misc
Partial Correction
09/21/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 120 BAYS 5&6; 122; 123; 125; 127; 128; 131; 132; 133; 137; 138 EXCEPT BOTH FACES OF BULKHEAD AT DOOR 133B; 139; 140; 141; 142; 143; 100-110; 113; 120-123; 126-129; 134-136; 143; 145-147; 148; BULKHEAD AT DOOR 133B; CORRIDOR A149;
Above Ceiling Inspection Partial 9/25/2015 9/25/2015 at 12:00 AM 09/25/2015
Misc
Resolved
09/25/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFITS @ A100, 104, 126, 137, 120 @ SINK, 148; SOFFITS @ A127 & A145; SOFFITS @ A125 N & S; A150; 152; A153 O.R.;
Misc
Resolved
09/25/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 120 BAYS 5&6; 122; 123; 125; 127; 128; 131; 132; 133; 137; 138 EXCEPT BOTH FACES OF BULKHEAD AT DOOR 133B; 139; 140; 141; 142; 143; 100-110; 113; 120-123; 126-129; 134-136; 143; 145-147; 148; BULKHEAD AT DOOR 133B; CORRIDOR A149;
Misc
Partial Correction
09/25/2015
ALL ACT AND GWB CEILINGS OK TO COVER WHEN READY EXCEPT A153 O.R. TO BE REINSPECTED AFTER ALL SYSTEMS COMPLETED
In-wall Inspection Passed 9/4/2015 8/18/2015 at 12:00 AM 10/12/2015
Misc
Resolved
09/04/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL & SOFFIT FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: A100 E, N, W; 102; 103; 105; 106; 107; 108; 110; 111; 112; 113; 114; 116; 117; 119; 120; PAIN PRE-OP A120 BAYS 1-4; 121; 123; A125 BAYS 2-5; 124; 125; 125 BAYS 6,7,8; 127; 128; 129; 130; 131; 132; 133; A133 BAYS 7,8; EXSTG CORR RECESS @ DOOR 133A; 134; 135; 136; 137; 138; 139-142; 143 WEST; 143; 145; 146; 147; 148; 149; 154; 155; 156; 117 N; 118 S; 150; 151; 152; 126 NW; A150 SE @ DOOR; A101 NORTH WALL; A109;
Above Ceiling Inspection Passed 9/25/2015 at 12:00 AM 10/12/2015
Misc
Resolved
10/12/2015
ALL ACT AND GWB CEILINGS OK TO COVER WHEN READY EXCEPT A153 O.R. TO BE REINSPECTED AFTER ALL SYSTEMS COMPLETED
Foundation Inspection - Commercial Passed 6/29/2015 at 12:00 AM 10/12/2015
Misc
Resolved
10/12/2015
OK TO POUR WHEN READY 5" THICK EQUIPMENT SLAB AT 1.2/A.5 PREPED WITH MAT OF #4 REBAR AT MID-DEPTH @ 16" O/C E/W
Piers/Caissons Inspection - Commercial Passed 8/4/2015 at 12:00 AM 10/12/2015
Miscellaneous Inspection Passed 10/13/2015 at 12:00 AM 10/13/2015
Occupancy Inspection - Codes Commercial Failed 10/14/2015 10/14/2015 at 12:00 AM 10/14/2015
Misc
Corrective Action Required
10/14/2015
ELECTRICAL RECEPTALCES AT FOUR EXAM ROOMS: TWO LESS THAN 6' FROM EDGE OF SINK AT EACH ROOM NOT GFCI-PROTECTED.
Misc
Corrective Action Required
10/14/2015
SAFETY GLASS TO BE VERIFIED WHEN GLAZING IS COMPLETED.
Misc
Corrective Action Required
10/14/2015
"NO SMOKING" SIGNS REQUIRED AT PUBLIC ENTRANCE DOORS.
Misc
Corrective Action Required
10/14/2015
LABELED DOORS A143b, A151 AND A155 SUBJECT TO APPROVAL WHEN INSTALLED PERMANENT.
Misc
Corrective Action Required
10/14/2015
REQUIREMENT FOR OPENING DEVICE AT WEST MAIN ENTRANCE TO BE DETERMINED.
Misc
Corrective Action Required
10/14/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES.
Misc
Corrective Action Required
10/14/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC OR PATIENTS PRIOR TO APPROVAL.
Alarm Test Passed 10/14/2015 at 8:00 AM 10/14/2015
Occupancy Inspection - Fire Failed 10/14/2015 at 12:00 AM 10/14/2015
Occupancy Inspection - Codes Commercial Temporary C of O 10/28/2015 10/28/2015 at 12:00 AM 10/28/2015
Misc
Corrective Action Required
10/14/2015
ELECTRICAL RECEPTALCES IN CABINETS ABOVE SINKS AT THE TWO SOUTH EXAM ROOMS NOT GFCI-PROTECTED.
Misc
Resolved
10/28/2015
SAFETY GLASS TO BE VERIFIED WHEN GLAZING IS COMPLETED.
Misc
Corrective Action Required
10/14/2015
"NO SMOKING" SIGNS REQUIRED AT PUBLIC ENTRANCE DOORS.
Misc
Corrective Action Required
10/14/2015
LABELED DOORS A143b, A151 AND A155 SUBJECT TO APPROVAL WHEN INSTALLED PERMANENT.
Misc
Resolved
10/28/2015
REQUIREMENT FOR OPENING DEVICE AT WEST MAIN ENTRANCE TO BE DETERMINED.
Misc
Corrective Action Required
10/14/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES.
Misc
Resolved
10/28/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC OR PATIENTS PRIOR TO APPROVAL.
Occupancy Inspection - Planning Temporary C of O 10/28/2015
Corrective Action Required
10/28/2015
The new islands on the north and south sides of the covered pick-up/drop-off shall be landscaped.
Occupancy Inspection - Fire Passed 10/28/2015 11/3/2015 at 12:00 AM 11/03/2015
Occupancy Inspection - Codes Commercial Full C of O 11/3/2015 at 12:00 AM 11/03/2015
Misc
Resolved
11/03/2015
ELECTRICAL RECEPTALCES IN CABINETS ABOVE SINKS AT THE TWO SOUTH EXAM ROOMS NOT GFCI-PROTECTED.
Misc
Resolved
11/03/2015
"NO SMOKING" SIGNS REQUIRED AT PUBLIC ENTRANCE DOORS.
Misc
Resolved
11/03/2015
LABELED DOORS A143b, A151 AND A155 SUBJECT TO APPROVAL WHEN INSTALLED PERMANENT.
Misc
Resolved
11/03/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES.
Occupancy Inspection - Planning Passed 12/15/2015
Occupancy Inspection - Water Utilities Passed 03/02/2016
Documents & Images
Date Uploaded File Type Document Name
12/11/2014 Letter Codes P/R Corrections Document
03/05/2015 Letter Codes Plan Review Conditions
04/21/2015 Letter Inspection Summary
04/30/2015 Letter Fire (Sprinkler) Plan Review
05/01/2015 Letter Inspection Summary
05/05/2015 Letter Inspection Summary
06/09/2015 Letter Inspection Summary
07/09/2015 Letter Inspection Summary
07/09/2015 Letter Fire Building Plan Review
07/17/2015 Letter Inspection Summary
07/08/2015 Letter Inspection Summary
08/05/2015 Letter Inspection Summary
06/30/2015 Letter Inspection Summary
06/29/2015 Letter Inspection Summary
08/10/2015 Letter Inspection Summary
06/23/2015 Letter Inspection Summary
06/19/2015 Letter Inspection Summary
06/18/2015 Letter Inspection Summary
08/21/2015 Letter Inspection Summary
08/25/2015 Letter Inspection Summary
08/27/2015 Letter Inspection Summary
06/05/2015 Letter Inspection Summary
06/05/2015 Letter Inspection Summary
05/19/2015 Letter Inspection Summary
05/15/2015 Letter Inspection Summary
05/14/2015 Letter Inspection Summary
04/28/2015 Letter Inspection Summary
04/16/2015 Letter Inspection Summary
03/05/2015 Letter Codes Building Permit
03/05/2015 Receipt Receipt for transaction: 2015-000295
02/20/2015 Letter Fire (Sprinkler) Plan Review
10/14/2015 Letter Inspection Summary
12/24/2014 Letter Codes P/R Corrections Document
12/08/2014 Letter Fire Building Plan Review
07/28/2015 Letter Inspection Summary
07/22/2015 Letter Inspection Summary
07/21/2015 Letter Inspection Summary
07/17/2015 Letter Inspection Summary
07/16/2015 Letter Inspection Summary
08/06/2015 Letter Inspection Summary
07/07/2015 Letter Inspection Summary
08/07/2015 Letter Inspection Summary
08/04/2015 Letter Inspection Summary
08/12/2015 Letter Inspection Summary
08/13/2015 Letter Inspection Summary
08/18/2015 Letter Inspection Summary
09/01/2015 Letter Inspection Summary
11/04/2015 Letter Planning Inspection Summary
11/04/2015 Letter Planning Inspection Summary
09/04/2015 Letter Inspection Summary
09/04/2015 Letter Inspection Summary
09/11/2015 Letter Inspection Summary
09/15/2015 Letter Inspection Summary
09/21/2015 Letter Inspection Summary
09/23/2015 Letter Inspection Summary
09/25/2015 Letter Inspection Summary
10/02/2015 Letter Fire Building Plan Review
10/02/2015 Letter Codes P/R Corrections Document
10/28/2015 Letter Codes Temporary Certificate of Occupancy
11/03/2015 Letter Field Certificate of Occupancy
11/04/2015 Letter Codes Final Certificate of Occupancy
12/15/2015 Letter Planning Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home