Permit Application Status

PRCOM20141554


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20141554
Building Permit - Commercial
Final Completion
NEWTON MARILYN S-TRUSTEE
ALTERATION COMMERCIAL
INSTALLATION OF NEW FIRE SUPPRESSION SPRINKLER AND ALARM SYSTEMS Mike Weisenborn 03/02/2015 2:49 PM - PER EMAIL FROM BRIAN AUSTERMAN
06/12/2014
03/02/2015
Locations
Contacts
AEGIS FIRE PROTECTION LLC, Address:11936 W 119TH ST #262, Phone:(913) 825-0343  
NEWTON MARILYN S-TRUSTEE, Address:2013 NW N ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 06/24/2014 10/24/2014
Brian Austerman
Alarm Plan Review Released for Construction 06/24/2014 06/24/2014
Brian Austerman
Misc
Corrective Action Required
06/24/2014

Replace heat detector over FACP with a smoke detector
Misc
Corrective Action Required
06/24/2014

Show outside horn strobe on plans. Place over FDC, and shall activate on waterflow only
Sprinkler Plan Review Released for Construction 06/24/2014 06/18/2014
Brian Austerman
Misc
Corrective Action Required
06/18/2014

Show location of FDC 6/18/14 Resolved
Misc
Corrective Action Required
06/18/2014

Show closest hydrant to FDC, hydrant will need to be within 100' from FDC Hydrant at tie-in location, 30' from building
Knox box required
Corrective Action Required
06/18/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application
Sprinkler Plan Review Rejected 06/24/2014 06/16/2014
Brian Austerman
Misc
Corrective Action Required
06/16/2014

Show location of FDC
Misc
Corrective Action Required
06/16/2014

Show closest hydrant to FDC, hydrant will need to be within 100' from FDC
Knox box required
Corrective Action Required
06/16/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application
Alarm Plan Review Rejected 06/24/2014 06/16/2014
Brian Austerman
Misc
Corrective Action Required
06/16/2014

Replace heat detector over FACP with a smoke detector
Misc
Corrective Action Required
06/16/2014

Show outside horn strobe on plans. Place over FDC, and shall activate on waterflow only
Licensed Contractors Approved 06/24/2014 06/12/2014
Joe Frogge
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sprinkler - Hydrostatic Test Passed 9/19/2014 at 12:00 AM 09/22/2014
Sprinkler - Flow Test Failed 10/2/2014 at 12:00 AM 10/02/2014
Alarm Test Passed 10/2/2014 at 12:00 AM 10/02/2014
Occupancy Inspection - Fire Temporary C of O 10/2/2014 at 12:00 AM 10/02/2014
Misc
Corrective Action Required
10/02/2014
-install elec outlet cover on elec outlet in sprinkler room - provide a heat source for the sprinkler room - frpovide frie extingusihers throughout warehouse - secure/remove dead elec panel on north wall of warehouse - install vehicle impact guards around the yard hydrants - paint the yard hydrants yelow with silver tops - obtain knox box/ locks and mount the knox box on wareahouse above / close to fire department connection approx. 5'-6' off ground provide access keys to warehouse - label the sprinkler roomdoor "sprinkler room' - obtain a 60 second flow time at the inspectors test
Sprinkler - Flow Test Passed 10/3/2014 at 12:00 AM 10/03/2014
Occupancy Inspection - Fire Passed 4/8/2015 at 12:00 AM 04/08/2015
Documents & Images
Date Uploaded File Type Document Name
06/16/2014 Letter Fire (Alarm) Plan Review Notice
06/16/2014 Letter Fire (Sprinkler) Plan Review
06/18/2014 Letter Fire (Sprinkler) Plan Review
06/18/2014 Letter Fire (Sprinkler) Plan Review
06/24/2014 Letter Fire (Alarm) Plan Review Notice
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.