Permit Application Status

PRCOM20141075


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20141075
Building Permit - Commercial
Certificate of Occupancy
RESIDENCES AT NEW LONGVIEW LLC
NEW MULTI-FAMILY
APARTMENT BUILDING #7 - TYPE B4/5
05/08/2014
01/08/2015
11/18/2014
03/18/2016
Locations
Contacts
NEIGHBORS CONSTRUCTION COMPANY INC, Address:1708 E 123RD ST, Phone:(913) 422-5555  
MINICK GAMBRELL CONTRACTORS LLC, Address:11528 W 90TH ST, Phone:(913) 538-5391  
LYNN ELECTRIC & COMMUNICATIONS INC, Address:725 N 2ND ST STE K, Phone:(785) 843-5709  
BLUE RIVER PLUMBING INC, Address:9125 BARTON ST, Phone:(913) 701-6410  
NSPJ ARCHITECTS, Address:3515 W 75TH ST, SUITE 201  
RESIDENCES AT NEW LONGVIEW LLC, Address:5015 NW CANAL ST  
OLSSON ASSOCIATES, Address:1251 NW BRIARCLIFF PKWY, STE. 50, Phone:(816) 361-1177  
CITY OF LEES SUMMIT, Address:220 S MAIN  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 11/12/2014
Brian Austerman
Misc
Corrective Action Required
11/12/2014

Riser diagram shows a check valve before the risers on the FDC line. A check valve at the base of the riser from the underground is also required.
Installation acceptance testing
Corrective Action Required
11/12/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816)969-1300 to schedule hydrostatic and flow testing
Misc
Corrective Action Required
11/12/2014

Drain points shall be routed to the exterior or to an acceptable floor drain
Misc
Corrective Action Required
11/12/2014

The air compressor for the dry system shall be listed for fire service use
Misc
Corrective Action Required
11/12/2014

Expansion chamber for antifreeze system not shown, if used it shall be rated for fire service use
Alarm Plan Review Released for Construction 10/13/2014
Brian Austerman
Misc
Corrective Action Required
10/13/2014

Relabel CO2 to CO on all sets of plans RESOLVED 10/13/2014
Installation acceptance testing
Corrective Action Required
10/13/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm and flow testing
Misc
Corrective Action Required
10/13/2014

Outside horn/strobe to activate on a waterflow alarm only
Misc
Corrective Action Required
10/13/2014

Add an annunciator panel to the sprinkler room RESOLVED 10/13/2014
Misc
Corrective Action Required
10/13/2014

Add monitor modules to the garage CO detectors to relay a supervisory signal to the alarm panel. CO detectors in the garages are also to be interlocked to the garage door opener, activation of the CO detector shall automatically open the garage door RESOLVED 10/13/2014
Alarm Plan Review Rejected 08/25/2014
Brian Austerman
Misc
Corrective Action Required
08/25/2014

Relabel CO2 to CO on all sets of plans
Installation acceptance testing
Corrective Action Required
08/25/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm and flow testing
Misc
Corrective Action Required
08/25/2014

Outside horn/strobe to activate on a waterflow alarm only
Misc
Corrective Action Required
08/25/2014

Add an annunciator panel to the sprinkler room
Misc
Corrective Action Required
08/25/2014

Add monitor modules to the garage CO detectors to relay a supervisory signal to the alarm panel. CO detectors in the garages are also to be interlocked to the garage door opener, activation of the CO detector shall automatically open the garage door
Licensed Contractors Approved 06/11/2014 07/09/2014
Mike Weisenborn
Business License
Resolved
07/09/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Resolved
07/09/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Final Development Plan Review Approved 07/22/2014 07/09/2014
Mike Weisenborn
Building Plan Review Approved with Conditions 06/11/2014 06/10/2014
Joe Frogge
Misc
Corrective Action Required
06/04/2014

2012 IBC Stairway identification signs. A sign shall be provided at each floor landing in an interior exit stairway and ram connecting more than three stories designating the floor level, the terminus of the top and bottom of the interior exit stairway and ramp and the identification of the stair or ramp. The signage shall also state the story of, and the direction to, the exit discharge and the availability of roof access from the interior exit stairway and ramp for the fire department. The sign shall be location 5 feet above the floor landing in a position that is readily visible when the doors are in the open and closed positions. In addition to the stairway identification sign, a floor-level sign in raised characters and Braille complying with ICC A117.1 shall be located at each floor-level landing adjacent to the door leading from the interior exit stairway and ramp into the corridor to identify the floor level. (see code section for specific requirements) Action required: Comment for informational purposes. May be verified at inspections.
Misc
Resolved
06/10/2014

2012 IBC 1107.6.2 Group R-2. Accessible units, Type A units and Type B units shall be provided in Group R-2 occupancies in accordance with Sections 1107.6.2.1 and 1107.6.2.2. Action required: Clarify which units will be Type A and demonstrate how they will meet ICC A117.1 requirements. Clarify how remaining (Type B) units will meet ICC A117.1 requirements. 6/10/14 - drawings updated
Misc
Corrective Action Required
06/04/2014

2009 ANSI ICC A117.1 Section 307.4 Vertical Clearance. Vertical clearance shall be 80 inches minimum. Rails or other barriers shall be provided where the vertical clearance is less than 80 inches. The leading edge of such rails or barrier shall be located 27 inches maximum above the floor. Action required: Modify documents to demonstrate how this requirement will be met 6/10/14 - acknowledged in letter - to be verified in field.
Misc
Resolved
06/10/2014

2012 IPC 916.3 Vent installation below the fixture flood level rim. The vent located below the flood level rim of the fixture being vented shall be installed as required for drainage piping in accordance with Chapter 7, except for sizing. The vent shall be sized in accordance with Section 906.2. The lowest point of the island fixture vent shall connect full size to the drainage system. The connection shall be to a vertical drain pipe or to the top half of a horizontal drain pipe. Cleanouts shall be provided in the island fixture vent to permit rodding of all vent piping located below the flood level rim of the fixtures. Rodding in both directions shall be permitted through a cleanout. Action required: Modify island fixture vent venting detail. Cleanout on vent side to either be above flood rim level or be bi-directional. 6/10/14 - provided on drawing
Misc
Resolved
06/10/2014

2011 NEC Article 230.2 (E) Identification. Where a building or structure is supplied by more than one service, or any combination of branch circuits, feeders, and services, a permanent plaque or directory shall be installed at each service disconnect location denoting all other services, feeders, and branch circuits supplying that building or structure and the area served by each. See 225.37. Action required: Modify documents to demonstrate how this requirement will be met. 6/10/14 - provided on drawing
Fire Plan Review Approved with Conditions 06/11/2014 06/09/2014
Brian Austerman
Misc
Corrective Action Required
06/04/2014

Elevator must be capable of accomodating a stretcher, NFPA 5000.54.3. Plans appear to show this, comment is for information only
Misc
Corrective Action Required
06/04/2014

Standpipes. IFC 905.3.1 has been ammended locally to read: Class 1 standpipe systems shall be installed throughout buildings where the floor of the highest story is located more than two stories above the lowest level of fire department vehicle access. Provide standpipes on each floor level in the stairwells
Construction documents - Fire protection systems
Corrective Action Required
06/04/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
06/04/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Knox box required
Corrective Action Required
06/04/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application
Misc
Corrective Action Required
06/04/2014

[B] 1022.8 Discharge identification. An interior exit stairway and ramp shall not continue below its level of exit discharge unless an approved barrier is provided at the level of exit discharge to prevent persons from unintentionally continuing into levels below. Directional exit signs shall be provided as specified in Section 1011. Provide a gate on the stairway at the landing at ground level RESOLVED 6/9/14 IDENTIFICATION OF FLOOR LEVEL TO BE PLACED IN STAIRWAY
Misc
Corrective Action Required
06/04/2014

908.7 Carbon monoxide alarms. Group I or R occupancies located in a building containing a fuel-burning appliance or in a building which has an attached garage shall be equipped with single-station carbon monoxide alarms. The carbon monoxide alarms shall be listed as complying with UL 2034 and be installed and maintained in accordance with NFPA 720 and the manufacturer’s instructions. An open parking garage, as defined in Chapter 2 of the International Building Code, or an enclosed parking garage ventilated in accordance with Section 404 of the International Mechanical Code shall not be considered an attached garage. Exception: Sleeping units or dwelling units which do not themselves contain a fuel-burning appliance or have an attached garage, but which are located in a building with a fuel-burning appliance or an attached garage, need not be equipped with single-station carbon monoxide alarms provided that: 1. The sleeping unit or dwelling unit is located more than one story above or below any story which contains a fuel-burning appliance or an attached garage; 2. The sleeping unit or dwelling unit is not connected by duct work or ventilation shafts to any room containing a fuel-burning appliance or to an attached garage; and 3. The building is equipped with a common area carbon monoxide alarm system. Provide carbon monoxide alarms per the above code 6/9/14. Plan review for added CO monitoring of the garages and common areas. Approved as submitted
Misc
Corrective Action Required
06/04/2014

[B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. Provide remote emergency egress illumination on the exterior of the exits
Portable fire extinguishers - general
Corrective Action Required
06/04/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. For information only
Misc
Corrective Action Required
06/04/2014

607.4 Elevator key location. Keys for the elevator car doors and fire-fighter service keys shall be kept in an approved location for immediate use by the fire department. To be placed in the knox box
Special Inspections Review Approved 06/20/2014 05/30/2014
Mike Weisenborn
Building Plan Review Rejected 05/22/2014 05/22/2014
Joe Frogge
Misc
Corrective Action Required
05/22/2014

2012 IBC Stairway identification signs. A sign shall be provided at each floor landing in an interior exit stairway and ram connecting more than three stories designating the floor level, the terminus of the top and bottom of the interior exit stairway and ramp and the identification of the stair or ramp. The signage shall also state the story of, and the direction to, the exit discharge and the availability of roof access from the interior exit stairway and ramp for the fire department. The sign shall be location 5 feet above the floor landing in a position that is readily visible when the doors are in the open and closed positions. In addition to the stairway identification sign, a floor-level sign in raised characters and Braille complying with ICC A117.1 shall be located at each floor-level landing adjacent to the door leading from the interior exit stairway and ramp into the corridor to identify the floor level. (see code section for specific requirements) Action required: Comment for informational purposes. May be verified at inspections.
Misc
Corrective Action Required
05/22/2014

2012 IBC 1107.6.2 Group R-2. Accessible units, Type A units and Type B units shall be provided in Group R-2 occupancies in accordance with Sections 1107.6.2.1 and 1107.6.2.2. Action required: Clarify which units will be Type A and demonstrate how they will meet ICC A117.1 requirements. Clarify how remaining (Type B) units will meet ICC A117.1 requirements.
Misc
Corrective Action Required
05/22/2014

2009 ANSI ICC A117.1 Section 307.4 Vertical Clearance. Vertical clearance shall be 80 inches minimum. Rails or other barriers shall be provided where the vertical clearance is less than 80 inches. The leading edge of such rails or barrier shall be located 27 inches maximum above the floor. Action required: Modify documents to demonstrate how this requirement will be met
Misc
Corrective Action Required
05/22/2014

2012 IPC 916.3 Vent installation below the fixture flood level rim. The vent located below the flood level rim of the fixture being vented shall be installed as required for drainage piping in accordance with Chapter 7, except for sizing. The vent shall be sized in accordance with Section 906.2. The lowest point of the island fixture vent shall connect full size to the drainage system. The connection shall be to a vertical drain pipe or to the top half of a horizontal drain pipe. Cleanouts shall be provided in the island fixture vent to permit rodding of all vent piping located below the flood level rim of the fixtures. Rodding in both directions shall be permitted through a cleanout. Action required: Modify island fixture vent venting detail. Cleanout on vent side to either be above flood rim level or be bi-directional.
Misc
Corrective Action Required
05/22/2014

2011 NEC Article 230.2 (E) Identification. Where a building or structure is supplied by more than one service, or any combination of branch circuits, feeders, and services, a permanent plaque or directory shall be installed at each service disconnect location denoting all other services, feeders, and branch circuits supplying that building or structure and the area served by each. See 225.37. Action required: Modify documents to demonstrate how this requirement will be met.
Licensed Contractors Rejected 05/22/2014 05/22/2014
Joe Frogge
Business License
Corrective Action Required
05/22/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Corrective Action Required
05/22/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 05/22/2014 05/13/2014
Brian Austerman
Misc
Corrective Action Required
05/13/2014

Elevator must be capable of accomodating a stretcher, NFPA 5000.54.3. Plans appear to show this, comment is for information only
Misc
Corrective Action Required
05/13/2014

Standpipes. IFC 905.3.1 has been ammended locally to read: Class 1 standpipe systems shall be installed throughout buildings where the floor of the highest story is located more than two stories above the lowest level of fire department vehicle access. Provide standpipes on each floor level in the stairwells
Construction documents - Fire protection systems
Corrective Action Required
05/13/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
05/13/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Knox box required
Corrective Action Required
05/13/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application
Misc
Corrective Action Required
05/13/2014

[B] 1022.8 Discharge identification. An interior exit stairway and ramp shall not continue below its level of exit discharge unless an approved barrier is provided at the level of exit discharge to prevent persons from unintentionally continuing into levels below. Directional exit signs shall be provided as specified in Section 1011. Provide a gate on the stairway at the landing at ground level
Misc
Corrective Action Required
05/13/2014

908.7 Carbon monoxide alarms. Group I or R occupancies located in a building containing a fuel-burning appliance or in a building which has an attached garage shall be equipped with single-station carbon monoxide alarms. The carbon monoxide alarms shall be listed as complying with UL 2034 and be installed and maintained in accordance with NFPA 720 and the manufacturer’s instructions. An open parking garage, as defined in Chapter 2 of the International Building Code, or an enclosed parking garage ventilated in accordance with Section 404 of the International Mechanical Code shall not be considered an attached garage. Exception: Sleeping units or dwelling units which do not themselves contain a fuel-burning appliance or have an attached garage, but which are located in a building with a fuel-burning appliance or an attached garage, need not be equipped with single-station carbon monoxide alarms provided that: 1. The sleeping unit or dwelling unit is located more than one story above or below any story which contains a fuel-burning appliance or an attached garage; 2. The sleeping unit or dwelling unit is not connected by duct work or ventilation shafts to any room containing a fuel-burning appliance or to an attached garage; and 3. The building is equipped with a common area carbon monoxide alarm system. Provide carbon monoxide alarms per the above code
Misc
Corrective Action Required
05/13/2014

[B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. Provide remote emergency egress illumination on the exterior of the exits
Portable fire extinguishers - general
Corrective Action Required
05/13/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. For information only
Misc
Corrective Action Required
05/13/2014

607.4 Elevator key location. Keys for the elevator car doors and fire-fighter service keys shall be kept in an approved location for immediate use by the fire department. To be placed in the knox box
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Multi-Family $16,678.16 $16,678.16 Paid 01/08/2015
8331507-Sewer Connection Fee $3,000.00 $3,000.00 Paid 01/08/2015
$3,000.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Failed 1/15/2015 (10:00) 1/15/2015 at 12:00 AM 01/15/2015
Misc
Corrective Action Required
01/15/2015
UPPER PORTION EAST SIDE- Failed- see clearance between foam board and rebar. clearance between rebar and ground. spacing blocks are not 3" . missing section of rebar on south side back of elevator location. recall when ready do not pour.
Footing Inspection - Commercial Passed 1/20/2015 (10:00) 1/20/2015 at 12:00 AM 01/20/2015
Misc
Resolved
01/20/2015
UPPER PORTION EAST SIDE- Failed- see clearance between foam board and rebar. clearance between rebar and ground. spacing blocks are not 3" . missing section of rebar on south side back of elevator location. recall when ready do not pour.
Underslab Electrical Inspection - Commercial Passed 1/28/2015 at 12:00 AM 01/28/2015
Underslab Plumbing Inspection - Commercial Passed 2/3/2015 2/3/2015 at 12:00 AM 02/03/2015
All Rough Inspection - Commercial Not Ready 8/11/2015 8/11/2015 at 12:00 AM 08/11/2015
Rough Framing Inspection - Commercial Partial 8/28/2015 8/28/2015 at 12:00 AM 08/28/2015
Misc
Corrective Action Required
08/28/2015
ELEVATOR SHAFT OK TO ROCK
Rated Assembly Inspection Partial 9/2/2015 9/2/2015 at 12:00 AM 09/02/2015
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
09/02/2015
ELEVATOR-INSIDE 1ST LAYER 1ST LAYER CEILING
Rated Assembly Inspection Failed 9/9/2015 9/9/2015 at 12:00 AM 09/09/2015
Misc
Corrective Action Required
09/09/2015
2ND LAYER ELEVATOR CEILING CALLED IN BY NICK @ 913-653-4490 SALLY SARVADI 09/09/2015 2:21 PM 1ST LAYER ELEVATOR, WALL CEILING- 2ND LAYER WALLS, 2ND LAYER CEILING COVERED BY 3RD LAYER
Rated Assembly Inspection Failed 9/11/2015 at 12:00 AM 09/11/2015
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
09/09/2015
2ND LAYER ELEVATOR CEILING CALLED IN BY NICK @ 913-653-4490 SALLY SARVADI 09/09/2015 2:21 PM 1ST LAYER ELEVATOR, WALL CEILING- 2ND LAYER WALLS, 2ND LAYER CEILING COVERED BY 3RD LAYER9/9, 3RD COVERED BY 4TH 9/10
In-wall Inspection Not Ready 9/25/2015 at 12:00 AM 09/25/2015
In-wall Inspection Failed 9/30/2015 9/30/2015 at 12:00 AM 09/30/2015
Misc
Corrective Action Required
09/30/2015
-install protectioin plates and plates straps on plates bored at 50%
In-wall Inspection Failed 10/5/2015 at 12:00 AM 10/05/2015
Misc
Corrective Action Required
09/30/2015
-install protectioin plates and plates straps on plates bored at 50% 3rd failed, b,1,2,3 ok for prerock tub walls 4th no
In-wall Inspection Failed 10/6/2015 10/6/2015 at 12:00 AM 10/06/2015
Misc
Corrective Action Required
10/06/2015
-install protectioin plates and plates straps on plates bored at 50% 3rd failed, b,1,2,3 ok for prerock tub walls 4th no bsmt failed for prerock-1,2,3,4 ok
Rated Assembly Inspection Partial 10/7/2015 10/7/2015 at 12:00 AM 10/07/2015
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
09/11/2015
2ND LAYER ELEVATOR CEILING CALLED IN BY NICK @ 913-653-4490 SALLY SARVADI 09/09/2015 2:21 PM 1ST LAYER ELEVATOR, WALL CEILING- 2ND LAYER WALLS, 2ND LAYER CEILING COVERED BY 3RD LAYER9/9, 3RD COVERED BY 4TH 9/10 DRYER BOXES B-4-OK
In-wall Inspection Failed 10/7/2015 10/7/2015 at 12:00 AM 10/07/2015
Misc
Corrective Action Required
10/06/2015
-install protectioin plates and plates straps on plates bored at 50% 3rd failed, b,1,2,3 ok for prerock tub walls 4th no bsmt failed for prerock-1,2,3,4 ok,BSMT FAILED
In-wall Inspection Failed 10/8/2015 10/8/2015 at 12:00 AM 10/08/2015
Misc
Corrective Action Required
10/07/2015
-install protectioin plates and plates straps on plates bored at 50% 3rd failed, b,1,2,3 ok for prerock tub walls 4th no bsmt failed for prerock-1,2,3,4 ok,BSMT FAILED bsmt failed again
All Rough Inspection - Commercial Not Ready 10/8/2015 10/8/2015 at 12:00 AM 10/08/2015
Misc
Corrective Action Required
10/08/2015
not ready bsmt , 1st floor, hvac sprinkler , firecaulking, plumbing plates, electrical panels.
In-wall Inspection Failed 10/9/2015 10/9/2015 at 12:00 AM 10/09/2015
Misc
Corrective Action Required
10/08/2015
-install protectioin plates and plates straps on plates bored at 50% 3rd failed, b,1,2,3 ok for prerock tub walls 4th no bsmt failed for prerock-1,2,3,4 ok,BSMT FAILED bsmt failed again pre-rock failed 9/25,9/30,10/5,10/6,10/7,10/8,10/9. fees due after 2nd inspection.
In-wall Inspection Partial 10/12/2015 10/12/2015 at 12:00 AM 10/12/2015
Misc
Corrective Action Required
10/09/2015
prerock inspection-- inwall bsmt level complete10/12/15 1,2,3,4
All Rough Inspection - Commercial Failed 10/15/2015 10/16/2015 at 12:00 AM 10/16/2015
Misc
Corrective Action Required
10/08/2015
BSMT NORTH END UNIT NEEDS JOIST HANGER.
FIRST FLOOR
Corrective Action Required
10/16/2015
Sprinkler - Hydrostatic Test Passed 10/21/2015 at 10:00 AM 10/21/2015
All Rough Inspection - Commercial Partial 10/21/2015 10/21/2015 at 12:00 AM 10/21/2015
Misc
Corrective Action Required
10/16/2015
BSMT COMPLETE
FIRST FLOOR
Corrective Action Required
10/16/2015
PVC 4" DRAIN COLLARS
SECOND FLOOR
Corrective Action Required
10/21/2015
FULL LIST SEE NIC- PROTECTIONI PLATES ELECTRICAL PANELS INCOMPLETE CAULK PVC 4" ROOF DRAINS FIRESTOP BETWEEN UNITS
Rated Assembly Inspection Partial 10/22/2015 10/22/2015 at 12:00 AM 10/22/2015
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/07/2015
2ND LAYER ELEVATOR CEILING CALLED IN BY NICK @ 913-653-4490 SALLY SARVADI 09/09/2015 2:21 PM 1ST LAYER ELEVATOR, WALL CEILING- 2ND LAYER WALLS, 2ND LAYER CEILING COVERED BY 3RD LAYER9/9, 3RD COVERED BY 4TH 9/10 caulking of tub traps DRYER BOXES B-4-OK
All Rough Inspection - Commercial Failed 10/22/2015 10/22/2015 at 12:00 AM 10/22/2015
Misc
Corrective Action Required
10/21/2015
BSMT COMPLETE
FIRST FLOOR
Corrective Action Required
10/21/2015
PVC 4" DRAIN COLLARS
SECOND FLOOR
Corrective Action Required
10/21/2015
FULL LIST SEE NIC- PROTECTIONI PLATES ELECTRICAL PANELS INCOMPLETE CAULK PVC 4" ROOF DRAINS FIRESTOP BETWEEN UNITS
THIRD FLOOR
Corrective Action Required
10/22/2015
elect, google , puddy pads, carl bath vents 4" drainetc
Rated Assembly Inspection Partial 10/23/2015 10/23/2015 at 12:00 AM 10/23/2015
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/22/2015
2ND LAYER ELEVATOR CEILING CALLED IN BY NICK @ 913-653-4490 SALLY SARVADI 09/09/2015 2:21 PM 1ST LAYER ELEVATOR, WALL CEILING- 2ND LAYER WALLS, 2ND LAYER CEILING COVERED BY 3RD LAYER9/9, 3RD COVERED BY 4TH 9/10 caulking of tub traps DRYER BOXES B-4-OK corridor ceiling b,1,2,3
All Rough Inspection - Commercial Partial 10/23/2015 at 12:00 AM 10/23/2015
Misc
Corrective Action Required
10/22/2015
BSMT COMPLETE
FIRST FLOOR
Corrective Action Required
10/22/2015
PVC 4" DRAIN COLLARS
SECOND FLOOR
Corrective Action Required
10/22/2015
FULL LIST SEE NIC- PROTECTIONI PLATES ELECTRICAL PANELS INCOMPLETE CAULK PVC 4" ROOF DRAINS FIRESTOP BETWEEN UNITS
THIRD FLOOR
Corrective Action Required
10/22/2015
elect, google , puddy pads, carl bath vents 4" drainetc bath fans truss failed
FOURTH FLOOR
Corrective Action Required
10/23/2015
walked not ready
All Rough Inspection - Commercial Failed 10/26/2015 10/26/2015 at 12:00 AM 10/26/2015
Misc
Corrective Action Required
10/23/2015
BSMT COMPLETE
FIRST FLOOR
Corrective Action Required
10/23/2015
PVC 4" DRAIN COLLARS
SECOND FLOOR
Corrective Action Required
10/23/2015
THIRD FLOOR
Corrective Action Required
10/23/2015
, puddy pads,
FOURTH FLOOR
Corrective Action Required
10/23/2015
walked not ready
All Rough Inspection - Commercial Partial 10/28/2015 10/30/2015 at 12:00 AM 10/30/2015
Misc
Corrective Action Required
10/26/2015
BSMT COMPLETE
FIRST FLOOR
Corrective Action Required
10/26/2015
complete
SECOND FLOOR
Corrective Action Required
10/26/2015
THIRD FLOOR
Corrective Action Required
10/26/2015
FOURTH FLOOR
Corrective Action Required
10/26/2015
plumbing , rock angle walls, stand pipe, dead space.
Rated Assembly Inspection Partial 11/4/2015 11/4/2015 at 12:00 AM 11/04/2015
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/23/2015
2ND LAYER ELEVATOR CEILING CALLED IN BY NICK @ 913-653-4490 SALLY SARVADI 09/09/2015 2:21 PM 1ST LAYER ELEVATOR, WALL CEILING- 2ND LAYER WALLS, 2ND LAYER CEILING COVERED BY 3RD LAYER9/9, 3RD COVERED BY 4TH 9/10 caulking of tub traps DRYER BOXES B-4-OK corridor ceiling b,1,2,3
LOWER LEVEL
Corrective Action Required
11/04/2015
ROCK 1ST LAYER
FIRST FLOOR
Corrective Action Required
11/04/2015
SECOND FLOOR
Corrective Action Required
11/04/2015
THIRD FLOOR
Corrective Action Required
11/04/2015
FOURTH FLOOR
Corrective Action Required
11/04/2015
Rated Assembly Inspection Partial 11/5/2015 11/5/2015 at 12:00 AM 11/05/2015
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
11/04/2015
corridor ceiling b,1,2,3 1ST LAYER STAIR SIDE B,1,2,3,
LOWER LEVEL
Corrective Action Required
11/04/2015
ROCK 1ST LAYER 1,2 LAYER 2HR WALLS
FIRST FLOOR
Corrective Action Required
11/04/2015
1ST LAYER UNITS
SECOND FLOOR
Corrective Action Required
11/04/2015
1ST LAYER
THIRD FLOOR
Corrective Action Required
11/04/2015
FOURTH FLOOR
Corrective Action Required
11/04/2015
Rated Assembly Inspection Partial 11/6/2015 11/6/2015 at 12:00 AM 11/06/2015
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
11/05/2015
corridor ceiling b,1,2,3 1ST LAYER STAIR SIDE B,1,2,3, STAIR AND CORRIDOR SIDE 1ST LAYER COMPLETE STAIR TOWRS B,1,2,3
LOWER LEVEL
Corrective Action Required
11/05/2015
ROCK 1ST LAYER 1,2 LAYER 2HR WALLS
FIRST FLOOR
Corrective Action Required
11/05/2015
1ST LAYER UNITS 1ST LAYER 2HR WALLS
SECOND FLOOR
Corrective Action Required
11/05/2015
1ST LAYER 1ST LAYER CEILING INCOMPLETE 1ST LAYER 2HR WALLS NOT SCREWED OFF
THIRD FLOOR
Corrective Action Required
11/05/2015
INCOMPLETE
FOURTH FLOOR
Corrective Action Required
11/05/2015
Electrical Service Inspection Failed 11/10/2015 11/11/2015 at 12:00 AM 11/11/2015
Misc
Corrective Action Required
11/11/2015
incomplete 11-11-15
In-wall Inspection Passed 11/2/2015 11/12/2015 at 12:00 AM 11/11/2015
Misc
Resolved
11/11/2015
prerock inspection-- inwall bsmt level complete10/12/15 1,2,3,4
Rough Framing Inspection - Commercial Passed 11/12/2015 at 12:00 AM 11/11/2015
Misc
Resolved
11/11/2015
ELEVATOR SHAFT OK TO ROCK
Rough Plumbing Inspection - Commercial Passed 11/11/2015
Rated Assembly Inspection Failed 11/11/2015 11/11/2015 at 12:00 AM 11/11/2015
THE FOLLOWING AREAS ARE APPROVED
Resolved
11/11/2015
corridor ceiling b,1,2,3 1ST LAYER STAIR SIDE B,1,2,3, STAIR AND CORRIDOR SIDE 1ST LAYER COMPLETE STAIR TOWRS B,1,2,3
LOWER LEVEL
Resolved
11/11/2015
ROCK 1ST LAYER 1,2 LAYER 2HR WALLS
FIRST FLOOR
Resolved
11/11/2015
1ST LAYER UNITS 1ST LAYER 2HR WALLS
SECOND FLOOR
Resolved
11/11/2015
1ST LAYER 1ST LAYER CEILING INCOMPLETE 1ST LAYER 2HR WALLS NOT SCREWED OFF
THIRD FLOOR
Corrective Action Required
11/06/2015
CEILING INCOMPLETE 2ND LAYER OF 2HR WALLS INCOMPLETE
FOURTH FLOOR
Corrective Action Required
11/06/2015
Above Ceiling Inspection Failed 11/11/2015 11/11/2015 at 12:00 AM 11/11/2015
Misc
Corrective Action Required
11/11/2015
ABOVE CEILING CORRIDORS- B-1-2 OK 3-INCOMPLETE 4-
Electrical Service Inspection Passed 11/12/2015 11/12/2015 at 12:00 AM 11/12/2015
Misc
Corrective Action Required
11/11/2015
incomplete 11-11-15
Rated Assembly Inspection Partial 11/12/2015 11/12/2015 at 12:00 AM 11/12/2015
THIRD FLOOR
Resolved
11/12/2015
CEILING INCOMPLETE 2ND LAYER OF 2HR WALLS INCOMPLETE
FOURTH FLOOR
Corrective Action Required
11/11/2015
Above Ceiling Inspection Failed 11/12/2015 11/12/2015 at 12:00 AM 11/12/2015
Misc
Corrective Action Required
11/12/2015
ABOVE CEILING CORRIDORS- B-1-2 OK 3-INCOMPLETE carl 4-
Rated Assembly Inspection Partial 11/13/2015 11/13/2015 at 12:00 AM 11/13/2015
FOURTH FLOOR
Corrective Action Required
11/12/2015
FIRST LAYER LID APPROVED
Rated Assembly Inspection Not Ready 11/16/2015 11/16/2015 at 12:00 AM 11/16/2015
FOURTH FLOOR
Corrective Action Required
11/13/2015
FIRST LAYER LID APPROVED
Rated Assembly Inspection Partial 11/17/2015 11/17/2015 at 12:00 AM 11/17/2015
FOURTH FLOOR
Corrective Action Required
11/16/2015
FIRST LAYER LID APPROVED 1st layer south tower ok walls and ceiling 1st layer north tower ceiling ok walls not screwed off 2nd layers corridor and ceiling not complete
Rated Assembly Inspection Partial 11/18/2015 11/18/2015 at 12:00 AM 11/18/2015
FOURTH FLOOR
Corrective Action Required
11/17/2015
1st layer ceiling walls stairs towers-ok units/ corridors complete
Rated Assembly Inspection Partial 11/19/2015 at 12:00 AM 11/19/2015
FOURTH FLOOR
Corrective Action Required
11/18/2015
1,2 layer ceiling walls stairs towers-ok 2nd of 2hr locations
Rated Assembly Inspection Partial 11/20/2015 11/20/2015 at 12:00 AM 11/20/2015
FOURTH FLOOR
Corrective Action Required
11/19/2015
1,2 layer ceiling walls stairs towers-ok 2nd of 2hr locations
Rated Assembly Inspection Partial 11/24/2015 at 12:00 AM 11/24/2015
FOURTH FLOOR
Corrective Action Required
11/20/2015
1,2,3rd layer ceiling stairs towers-ok
Above Ceiling Inspection Partial 11/24/2015 at 12:00 AM 11/24/2015
Misc
Corrective Action Required
11/24/2015
ABOVE CEILING CORRIDORS- B-1-2-3-4 ok units 4thbok d-1 units b 3,4
Rated Assembly Inspection Passed 11/25/2015 at 12:00 AM 11/25/2015
FOURTH FLOOR
Resolved
11/25/2015
1,2,3rd layer ceiling stairs towers-ok
Rated Assembly Inspection Partial 12/4/2015 12/7/2015 at 12:00 AM 12/07/2015
Rated Assembly Inspection Partial 1/11/2016 1/11/2016 at 12:00 AM 01/11/2016
Rated Assembly Inspection Passed 1/12/2016 1/12/2016 01/11/2016
Rated Assembly Inspection Passed 1/13/2016 1/13/2016 01/13/2016
Rated Assembly Inspection Passed 2/4/2016 02/04/2016
Alarm Test Passed 3/3/2016 03/03/2016
Sprinkler - Flow Test Passed 3/3/2016 03/03/2016
Occupancy Inspection - Fire Not Ready 3/7/2016 03/07/2016
Occupancy Inspection - Codes Commercial Not Ready 3/7/2016 3/7/2016 03/07/2016
Misc
Corrective Action Required
03/07/2016
FOURTH FLOOR, FOUR NORTH UNITS INSTALL ARRESTORS FOR LAUNDRY THIRD FLOOR, SOUTH EAST UNIT CHECK MECH CLOSET PENETRATION 2ND FLOOR, INSTALL MISSING GFCI KITCHEN, FIX GFCI, INSTALL GUARD LOWER LEVEL, COMPLETE PLUMBING, CHECK ARRESTORS FOR DISHWASHER MAKE SURE ALL MONOXIDE DETECTORS, SMOKE ALARMS, EMERGENCY LIGHTS, SPRINKLER HEADS ARE USABLE.
Occupancy Inspection - Fire Temporary C of O 3/9/2016 03/09/2016
Occupancy Inspection - Fire Passed 3/17/2016 03/17/2016
Occupancy Inspection - Codes Commercial Full C of O 3/9/2016 3/18/2016 03/18/2016
Misc
Resolved
03/18/2016
FOURTH FLOOR, FOUR NORTH UNITS INSTALL ARRESTORS FOR LAUNDRY THIRD FLOOR, SOUTH EAST UNIT CHECK MECH CLOSET PENETRATION 2ND FLOOR, INSTALL MISSING GFCI KITCHEN, FIX GFCI, INSTALL GUARD LOWER LEVEL, COMPLETE PLUMBING, CHECK ARRESTORS FOR DISHWASHER MAKE SURE ALL MONOXIDE DETECTORS, SMOKE ALARMS, EMERGENCY LIGHTS, SPRINKLER HEADS ARE USABLE.
Occupancy Inspection - Planning Passed 04/01/2016
Documents & Images
Date Uploaded File Type Document Name
05/13/2014 Letter Fire Building Plan Review
05/22/2014 Letter Codes P/R Corrections Document
05/30/2014 Letter Statment of Special Inspections.
06/09/2014 Letter Fire Building Plan Review
08/25/2014 Letter Fire (Alarm) Plan Review Notice
10/13/2014 Letter Fire (Alarm) Plan Review Notice
12/19/2014 Letter Fire (Sprinkler) Plan Review
01/08/2015 Receipt Receipt for transaction: 2015-000024
01/08/2015 Letter Codes Building Permit
01/15/2015 Letter Inspection Summary
01/20/2015 Letter Inspection Summary
01/28/2015 Letter Inspection Summary
02/03/2015 Letter Inspection Summary
08/11/2015 Letter Inspection Summary
08/28/2015 Letter Inspection Summary
09/02/2015 Letter Inspection Summary
09/09/2015 Letter Inspection Summary
09/11/2015 Letter Inspection Summary
09/30/2015 Letter Inspection Summary
10/05/2015 Letter Inspection Summary
10/06/2015 Letter Inspection Summary
10/07/2015 Letter Inspection Summary
10/08/2015 Letter Inspection Summary
10/09/2015 Letter Inspection Summary
10/09/2015 Letter Re-Inspection Fee
10/09/2015 Letter Re-Inspection Fee
10/09/2015 Letter Re-Inspection Fee
10/09/2015 Letter Re-Inspection Fee
10/09/2015 Letter Re-Inspection Fee
10/12/2015 Letter Inspection Summary
10/16/2015 Letter Inspection Summary
10/21/2015 Letter Inspection Summary
10/22/2015 Letter Inspection Summary
10/23/2015 Letter Inspection Summary
10/26/2015 Letter Inspection Summary
10/30/2015 Letter Inspection Summary
11/04/2015 Letter Inspection Summary
11/05/2015 Letter Inspection Summary
11/11/2015 Letter Inspection Summary
11/12/2015 Letter Inspection Summary
11/13/2015 Letter Inspection Summary
11/17/2015 Letter Inspection Summary
11/18/2015 Letter Inspection Summary
11/19/2015 Letter Inspection Summary
11/24/2015 Letter Inspection Summary
11/25/2015 Letter Inspection Summary
01/13/2016 Letter Inspection Summary
01/20/2016 6buildingelevator
03/07/2016 Letter Inspection Summary
03/21/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home