Permit Application Status

PRCOM20141074


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20141074
Building Permit - Commercial
Certificate of Occupancy
RESIDENCES AT NEW LONGVIEW LLC
NEW MULTI-FAMILY
APARTMENT BUILDING #4 - TYPE C4/5
05/08/2014
01/08/2015
11/18/2014
03/18/2016
Locations
Contacts
NEIGHBORS CONSTRUCTION COMPANY INC, Address:1708 E 123RD ST, Phone:(913) 422-5555  
MINICK GAMBRELL CONTRACTORS LLC, Address:11528 W 90TH ST, Phone:(913) 538-5391  
LYNN ELECTRIC & COMMUNICATIONS INC, Address:725 N 2ND ST STE K, Phone:(785) 843-5709  
BLUE RIVER PLUMBING INC, Address:9125 BARTON ST, Phone:(913) 701-6410  
NSPJ ARCHITECTS, Address:3515 W 75TH ST, SUITE 201  
RESIDENCES AT NEW LONGVIEW LLC, Address:5015 NW CANAL ST  
OLSSON ASSOCIATES, Address:1251 NW BRIARCLIFF PKWY, STE. 50, Phone:(816) 361-1177  
CITY OF LEES SUMMIT, Address:220 S MAIN  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 11/12/2014
Brian Austerman
Misc
Corrective Action Required
11/12/2014

Riser diagram shows a check valve before the risers on the FDC line. A check valve at the base of the riser from the underground is also required. Corrected 12-18-14
Installation acceptance testing
Corrective Action Required
11/12/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hydrostatic and flow testing
Misc
Corrective Action Required
11/12/2014

Drain points shall be routed to the exterior or to an acceptable floor drain
Misc
Corrective Action Required
11/12/2014

Air compressor for dry system shall be listed for fire service. Verified at inspection
Misc
Corrective Action Required
11/12/2014

Expansion chamber for antifreeze system not shown, if used it shall be rated for fire service use
Alarm Plan Review Released for Construction 10/13/2014
Brian Austerman
Misc
Corrective Action Required
10/13/2014

Relabel CO2 to CO on all sets of plans RESOLVED 10/13/2014
Installation acceptance testing
Corrective Action Required
10/13/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm and flow testing
Misc
Corrective Action Required
10/13/2014

Outside horn/strobe to activate on a waterflow alarm only
Misc
Corrective Action Required
10/13/2014

Add an annunciator panel to the sprinkler room RESOLVED 10/13/2014
Misc
Corrective Action Required
10/13/2014

Add monitor modules to the garage CO detectors to relay a supervisory signal to the alarm panel. CO detectors in the garages are also to be interlocked to the garage door opener, activation of the CO detector shall automatically open the garage door RESOLVED 10/13/2014
Alarm Plan Review Rejected 08/25/2014
Brian Austerman
Misc
Corrective Action Required
08/25/2014

Relabel CO2 to CO on all sets of plans
Installation acceptance testing
Corrective Action Required
08/25/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm and flow testing
Misc
Corrective Action Required
08/25/2014

Outside horn/strobe to activate on a waterflow alarm only
Misc
Corrective Action Required
08/25/2014

Add an annunciator panel to the sprinkler room
Misc
Corrective Action Required
08/25/2014

Add monitor modules to the garage CO detectors to relay a supervisory signal to the alarm panel. CO detectors in the garages are also to be interlocked to the garage door opener, activation of the CO detector shall automatically open the garage door
Licensed Contractors Approved 06/11/2014 07/09/2014
Mike Weisenborn
Business License
Resolved
07/09/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Resolved
07/09/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Final Development Plan Review Approved 07/22/2014 07/09/2014
Mark Harding
Building Plan Review Approved with Conditions 06/11/2014 06/10/2014
Joe Frogge
Misc
Corrective Action Required
06/04/2014

2012 IBC Stairway identification signs. A sign shall be provided at each floor landing in an interior exit stairway and ram connecting more than three stories designating the floor level, the terminus of the top and bottom of the interior exit stairway and ramp and the identification of the stair or ramp. The signage shall also state the story of, and the direction to, the exit discharge and the availability of roof access from the interior exit stairway and ramp for the fire department. The sign shall be location 5 feet above the floor landing in a position that is readily visible when the doors are in the open and closed positions. In addition to the stairway identification sign, a floor-level sign in raised characters and Braille complying with ICC A117.1 shall be located at each floor-level landing adjacent to the door leading from the interior exit stairway and ramp into the corridor to identify the floor level. (see code section for specific requirements) Action required: Comment for informational purposes. May be verified at inspections.
Misc
Resolved
06/10/2014

2012 IBC 1107.6.2 Group R-2. Accessible units, Type A units and Type B units shall be provided in Group R-2 occupancies in accordance with Sections 1107.6.2.1 and 1107.6.2.2. Action required: Clarify which units will be Type A and demonstrate how they will meet ICC A117.1 requirements. Clarify how remaining (Type B) units will meet ICC A117.1 requirements. plans updated
Misc
Corrective Action Required
06/04/2014

2009 ANSI ICC A117.1 Section 307.4 Vertical Clearance. Vertical clearance shall be 80 inches minimum. Rails or other barriers shall be provided where the vertical clearance is less than 80 inches. The leading edge of such rails or barrier shall be located 27 inches maximum above the floor. Action required: Modify documents to demonstrate how this requirement will be met. 6/10/14 - acknowledged in letter. To be verified at inspection
Misc
Resolved
06/10/2014

2012 IPC 916.3 Vent installation below the fixture flood level rim. The vent located below the flood level rim of the fixture being vented shall be installed as required for drainage piping in accordance with Chapter 7, except for sizing. The vent shall be sized in accordance with Section 906.2. The lowest point of the island fixture vent shall connect full size to the drainage system. The connection shall be to a vertical drain pipe or to the top half of a horizontal drain pipe. Cleanouts shall be provided in the island fixture vent to permit rodding of all vent piping located below the flood level rim of the fixtures. Rodding in both directions shall be permitted through a cleanout. Action required: Modify island fixture vent venting detail. Cleanout on vent side to either be above flood rim level or be bi-directional. 6/10/14 - drawings updated
Misc
Resolved
06/10/2014

2011 NEC Article 230.2 (E) Identification. Where a building or structure is supplied by more than one service, or any combination of branch circuits, feeders, and services, a permanent plaque or directory shall be installed at each service disconnect location denoting all other services, feeders, and branch circuits supplying that building or structure and the area served by each. See 225.37. Action required: Modify documents to demonstrate how this requirement will be met. 6/10/14 - provided on drawings
Fire Plan Review Approved with Conditions 06/11/2014 06/09/2014
Brian Austerman
Misc
Corrective Action Required
06/04/2014

Elevator must be capable of accomodating a stretcher, NFPA 5000.54.3. Plans appear to show conformity, this comment is for information only
Misc
Corrective Action Required
06/04/2014

Standpipes. IFC 905.3.1 has been ammended locally to read: Class 1 standpipe systems shall be installed throughout buildings where the floor of the highest story is located more than two stories above the lowest level of the fire department vehicle assess. Provide standpipes on each floor level in the stairwells
Construction documents - Fire protection systems
Corrective Action Required
06/04/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Submit sprinkler plans for approval
Alarms connected to automatic sprinkler system
Corrective Action Required
06/04/2014

2012 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Submit alarm plans for approval
Knox box required
Corrective Action Required
06/04/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application
Misc
Corrective Action Required
06/04/2014

[B] 1022.8 Discharge identification. An interior exit stairway and ramp shall not continue below its level of exit discharge unless an approved barrier is provided at the level of exit discharge to prevent persons from unintentionally continuing into levels below. Directional exit signs shall be provided as specified in Section 1011. Provide a gate on the stairway at the landing at ground level
Misc
Corrective Action Required
06/04/2014

908.7 Carbon monoxide alarms. Group I or R occupancies located in a building containing a fuel-burning appliance or in a building which has an attached garage shall be equipped with single-station carbon monoxide alarms. The carbon monoxide alarms shall be listed as complying with UL 2034 and be installed and maintained in accordance with NFPA 720 and the manufacturer’s instructions. An open parking garage, as defined in Chapter 2 of the International Building Code, or an enclosed parking garage ventilated in accordance with Section 404 of the International Mechanical Code shall not be considered an attached garage. Exception: Sleeping units or dwelling units which do not themselves contain a fuel-burning appliance or have an attached garage, but which are located in a building with a fuel-burning appliance or an attached garage, need not be equipped with single-station carbon monoxide alarms provided that: 1. The sleeping unit or dwelling unit is located more than one story above or below any story which contains a fuel-burning appliance or an attached garage; 2. The sleeping unit or dwelling unit is not connected by duct work or ventilation shafts to any room containing a fuel-burning appliance or to an attached garage; and 3. The building is equipped with a common area carbon monoxide alarm system. Provide carbon monoxide detection per the above code
Misc
Corrective Action Required
06/04/2014

[B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. Provide remote emergency lighting on the exterior of the exits
Portable fire extinguishers - general
Corrective Action Required
06/04/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. For information only
Misc
Corrective Action Required
06/04/2014

607.4 Elevator key location. Keys for the elevator car doors and fire-fighter service keys shall be kept in an approved location for immediate use by the fire department. To be placed in the knox box, for information only
Misc
Corrective Action Required
06/09/2014

6/9/14. Plan review for added CO monitoring of the garages and common areas. Approved as submitted
Special Inspections Review Approved 06/20/2014 05/30/2014
Mike Weisenborn
Licensed Contractors Rejected 06/20/2014 05/22/2014
Joe Frogge
Business License
Corrective Action Required
05/22/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Corrective Action Required
05/22/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Building Plan Review Rejected 05/22/2014 05/21/2014
Joe Frogge
Misc
Corrective Action Required
05/21/2014

2012 IBC Stairway identification signs. A sign shall be provided at each floor landing in an interior exit stairway and ram connecting more than three stories designating the floor level, the terminus of the top and bottom of the interior exit stairway and ramp and the identification of the stair or ramp. The signage shall also state the story of, and the direction to, the exit discharge and the availability of roof access from the interior exit stairway and ramp for the fire department. The sign shall be location 5 feet above the floor landing in a position that is readily visible when the doors are in the open and closed positions. In addition to the stairway identification sign, a floor-level sign in raised characters and Braille complying with ICC A117.1 shall be located at each floor-level landing adjacent to the door leading from the interior exit stairway and ramp into the corridor to identify the floor level. (see code section for specific requirements) Action required: Comment for informational purposes. May be verified at inspections.
Misc
Corrective Action Required
05/21/2014

2012 IBC 1107.6.2 Group R-2. Accessible units, Type A units and Type B units shall be provided in Group R-2 occupancies in accordance with Sections 1107.6.2.1 and 1107.6.2.2. Action required: Clarify which units will be Type A and demonstrate how they will meet ICC A117.1 requirements. Clarify how remaining (Type B) units will meet ICC A117.1 requirements.
Misc
Corrective Action Required
05/21/2014

2009 ANSI ICC A117.1 Section 307.4 Vertical Clearance. Vertical clearance shall be 80 inches minimum. Rails or other barriers shall be provided where the vertical clearance is less than 80 inches. The leading edge of such rails or barrier shall be located 27 inches maximum above the floor. Action required: Modify documents to demonstrate how this requirement will be met.
Misc
Corrective Action Required
05/21/2014

2012 IPC 916.3 Vent installation below the fixture flood level rim. The vent located below the flood level rim of the fixture being vented shall be installed as required for drainage piping in accordance with Chapter 7, except for sizing. The vent shall be sized in accordance with Section 906.2. The lowest point of the island fixture vent shall connect full size to the drainage system. The connection shall be to a vertical drain pipe or to the top half of a horizontal drain pipe. Cleanouts shall be provided in the island fixture vent to permit rodding of all vent piping located below the flood level rim of the fixtures. Rodding in both directions shall be permitted through a cleanout. Action required: Modify island fixture vent venting detail. Cleanout on vent side to either be above flood rim level or be bi-directional.
Misc
Corrective Action Required
05/21/2014

2011 NEC Article 230.2 (E) Identification. Where a building or structure is supplied by more than one service, or any combination of branch circuits, feeders, and services, a permanent plaque or directory shall be installed at each service disconnect location denoting all other services, feeders, and branch circuits supplying that building or structure and the area served by each. See 225.37. Action required: Modify documents to demonstrate how this requirement will be met.
Fire Plan Review Approved with Conditions 05/22/2014 05/13/2014
Brian Austerman
Misc
Corrective Action Required
05/13/2014

Elevator must be capable of accomodating a stretcher, NFPA 5000.54.3. Plans appear to show conformity, this comment is for information only
Misc
Corrective Action Required
05/13/2014

Standpipes. IFC 905.3.1 has been ammended locally to read: Class 1 standpipe systems shall be installed throughout buildings where the floor of the highest story is located more than two stories above the lowest level of the fire department vehicle assess. Provide standpipes on each floor level in the stairwells
Construction documents - Fire protection systems
Corrective Action Required
05/13/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Submit sprinkler plans for approval
Alarms connected to automatic sprinkler system
Corrective Action Required
05/13/2014

2012 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Submit alarm plans for approval
Knox box required
Corrective Action Required
05/13/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application
Misc
Corrective Action Required
05/13/2014

[B] 1022.8 Discharge identification. An interior exit stairway and ramp shall not continue below its level of exit discharge unless an approved barrier is provided at the level of exit discharge to prevent persons from unintentionally continuing into levels below. Directional exit signs shall be provided as specified in Section 1011. Provide a gate on the stairway at the landing at ground level
Misc
Corrective Action Required
05/13/2014

908.7 Carbon monoxide alarms. Group I or R occupancies located in a building containing a fuel-burning appliance or in a building which has an attached garage shall be equipped with single-station carbon monoxide alarms. The carbon monoxide alarms shall be listed as complying with UL 2034 and be installed and maintained in accordance with NFPA 720 and the manufacturer’s instructions. An open parking garage, as defined in Chapter 2 of the International Building Code, or an enclosed parking garage ventilated in accordance with Section 404 of the International Mechanical Code shall not be considered an attached garage. Exception: Sleeping units or dwelling units which do not themselves contain a fuel-burning appliance or have an attached garage, but which are located in a building with a fuel-burning appliance or an attached garage, need not be equipped with single-station carbon monoxide alarms provided that: 1. The sleeping unit or dwelling unit is located more than one story above or below any story which contains a fuel-burning appliance or an attached garage; 2. The sleeping unit or dwelling unit is not connected by duct work or ventilation shafts to any room containing a fuel-burning appliance or to an attached garage; and 3. The building is equipped with a common area carbon monoxide alarm system. Provide carbon monoxide detection per the above code
Misc
Corrective Action Required
05/13/2014

[B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. Provide remote emergency lighting on the exterior of the exits
Portable fire extinguishers - general
Corrective Action Required
05/13/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. For information only
Misc
Corrective Action Required
05/13/2014

607.4 Elevator key location. Keys for the elevator car doors and fire-fighter service keys shall be kept in an approved location for immediate use by the fire department. To be placed in the knox box, for information only
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Multi-Family $17,314.37 $17,314.37 Paid 01/08/2015
8331507-Sewer Connection Fee $3,000.00 $3,000.00 Paid 01/08/2015
$3,000.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Failed 1/14/2015 1/14/2015 at 12:00 AM 01/14/2015
Misc
Corrective Action Required
01/14/2015
clearance to rebar from ground 3" Olson failed because of frost
Footing Inspection - Commercial Passed 1/20/2015 1/20/2015 at 12:00 AM 01/20/2015
Misc
Resolved
01/20/2015
clearance to rebar from ground 3" Olson failed because of frost
Electrical Service Inspection Partial 4/27/2015 4/27/2015 at 12:00 AM 04/27/2015
Misc
Corrective Action Required
04/27/2015
TEMP POWER FOR TRASH COMPACTOR ONLY WILL BE 80 AMP BREAKER, PALNEL WILL BE LOCKED . SERVICE FOR TRASH UNIT WILL BE OUT OF BUILDING 4 WHEN 4 IS READY FOR SERIVCE. TEMP RELEASE ONLY
Rough Framing Inspection - Commercial Partial 5/7/2015 5/7/2015 at 12:00 AM 05/07/2015
Misc
Corrective Action Required
05/07/2015
EXTERIOR WALL SHEAR 1-3 OK
Rated Assembly Inspection Failed 5/19/2015 at 12:00 AM 05/19/2015
Misc
Corrective Action Required
05/19/2015
ELEVATOR - 1-3RD 1ST LAYER-SCREW PATTERN 16" ADD STUD, COMPLETE SCREWS SOUTH TOWER
Rated Assembly Inspection Partial 5/20/2015 5/20/2015 at 12:00 AM 05/20/2015
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
05/20/2015
STAIR TOWERS 1-2 LAYER 1-3 FLOORS
Rough Framing Inspection - Commercial Partial 5/20/2015 5/20/2015 at 12:00 AM 05/20/2015
Misc
Corrective Action Required
05/07/2015
EXTERIOR WALL SHEAR 1-3 OK
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
05/20/2015
ROUGH FRAMING- OK TO ROCK ELEVATOR INTERIOR 1-3
Rough Framing Inspection - Commercial Failed 5/22/2015 5/22/2015 at 12:00 AM 05/22/2015
Misc
Corrective Action Required
05/20/2015
EXTERIOR WALL SHEAR 1-3 OK ELEVATOR -STRAP WALLS 1-4 FAILED
Rated Assembly Inspection Partial 6/23/2015 at 12:00 AM 06/23/2015
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
06/23/2015
ELEVATOR 1-3 OK INSIDE STAIR TOWERS- SCREWS16"O.C. STUDS RECALL
Sprinkler - Hydrostatic Test Passed 6/24/2015 at 12:00 AM 06/24/2015
Rated Assembly Inspection Failed 6/24/2015 6/24/2015 at 12:00 AM 06/24/2015
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
06/23/2015
ELEVATOR- SCREW PATTERN STAIR TOWERS- SCREWS16"O.C. STUDS RECALLfailed
Rated Assembly Inspection Failed 6/26/2015 6/26/2015 at 12:00 AM 06/26/2015
Misc
Corrective Action Required
06/26/2015
1st layer elevator walls failed needs screw rear of wall at corners
In-wall Inspection Failed 7/7/2015 7/7/2015 at 12:00 AM 07/07/2015
LOWER LEVEL
Corrective Action Required
07/07/2015
PREROCK-FAILED
FIRST FLOOR
Corrective Action Required
07/07/2015
PRE-ROCK FAILED
SECOND FLOOR
Corrective Action Required
07/07/2015
THIRD FLOOR
Corrective Action Required
07/07/2015
FOURTH FLOOR
Corrective Action Required
07/07/2015
In-wall Inspection Failed 7/8/2015 7/8/2015 at 12:00 AM 07/08/2015
LOWER LEVEL
Corrective Action Required
07/07/2015
PREROCK-FAILED,1ST, 2ND TIME
FIRST FLOOR
Corrective Action Required
07/07/2015
PRE-ROCK FAILED
SECOND FLOOR
Corrective Action Required
07/07/2015
THIRD FLOOR
Corrective Action Required
07/07/2015
In-wall Inspection Partial 7/9/2015 7/9/2015 at 12:00 AM 07/09/2015
LOWER LEVEL
Corrective Action Required
07/08/2015
PREROCK-LOWER LEVEL
FIRST FLOOR
Corrective Action Required
07/08/2015
PRE-ROCK SHOWERWALL
SECOND FLOOR
Corrective Action Required
07/08/2015
PRE ROCK SHOWER WALLS
THIRD FLOOR
Corrective Action Required
07/08/2015
PRE ROCK SHOWER WALLS
FOURTH FLOOR
Corrective Action Required
07/09/2015
PRE ROCK SHOWER WALLS
All Rough Inspection - Commercial Not Ready 7/14/2015 7/14/2015 at 12:00 AM 07/14/2015
In-wall Inspection Failed 7/14/2015 7/14/2015 at 12:00 AM 07/14/2015
LOWER LEVEL
Corrective Action Required
07/09/2015
PREROCK-LOWER LEVEL
FIRST FLOOR
Corrective Action Required
07/09/2015
PRE-ROCK SHOWERWALL
SECOND FLOOR
Corrective Action Required
07/09/2015
PRE ROCK SHOWER WALLS
THIRD FLOOR
Corrective Action Required
07/09/2015
PRE ROCK SHOWER WALLS -failed
FOURTH FLOOR
Corrective Action Required
07/09/2015
PRE ROCK SHOWER WALLS-failed
Rated Assembly Inspection Failed 7/15/2015 7/15/2015 at 12:00 AM 07/15/2015
Misc
Corrective Action Required
06/26/2015
1st layer elevator walls failed needs screw rear of wall at corners dryer vent boxes- -TUB WALLS - 4101 CAULK 2ND-FAILED-4213,4205, 3RD-FAILED-4309, 4TH FAILED-12,08,09,00,07,01
FIRST FLOOR
Corrective Action Required
07/15/2015
SECOND FLOOR
Corrective Action Required
07/15/2015
THIRD FLOOR
Corrective Action Required
07/15/2015
FOURTH FLOOR
Corrective Action Required
07/15/2015
Rated Assembly Inspection Partial 7/16/2015 at 12:00 AM 07/16/2015
Misc
Corrective Action Required
07/15/2015
1st layer elevator walls failed needs screw rear of wall at corners dryer vent boxes- -TUB WALLS - 4101 CAULK 2ND-FAILED-4213,4205, 3RD-FAILED-4309, 4TH FAILED-12,08,09,00,07,01 TUBS 4211-4412 TUBS DIDNT PASS
FIRST FLOOR
Corrective Action Required
07/15/2015
SECOND FLOOR
Corrective Action Required
07/15/2015
THIRD FLOOR
Corrective Action Required
07/15/2015
Rated Assembly Inspection Partial 7/17/2015 at 12:00 AM 07/17/2015
Misc
Corrective Action Required
07/16/2015
1st layer elevator walls failed needs screw rear of wall at corners dryer vent boxes- -TUB WALLS - 4101 CAULK 2ND-FAILED-4213,4205, 3RD-FAILED-4309, 4TH FAILED-12,08,09,00,07,01 TUBS 4211-4412 TUBS DIDNT PASS 2ND LAYER TUBWALL 2HRS- 4,3,2
FIRST FLOOR
Corrective Action Required
07/16/2015
SECOND FLOOR
Corrective Action Required
07/16/2015
THIRD FLOOR
Corrective Action Required
07/16/2015
All Rough Inspection - Commercial Failed 7/15/2015 7/17/2015 at 12:00 AM 07/17/2015
LOWER LEVEL
Corrective Action Required
07/17/2015
4000 LINE SETS CAULK TRUCK LINE INCOMPLETE -
FIRST FLOOR
Corrective Action Required
07/17/2015
4100,4112
SECOND FLOOR
Corrective Action Required
07/17/2015
NOT READY HVAC INCOMPLETE
All Rough Inspection - Commercial Failed 7/22/2015 7/22/2015 at 12:00 AM 07/22/2015
LOWER LEVEL
Corrective Action Required
07/17/2015
4000 LINE SETS CAULK TRUCK LINE INCOMPLETE -
FIRST FLOOR
Corrective Action Required
07/17/2015
4100,4112 not complete
SECOND FLOOR
Corrective Action Required
07/17/2015
NOT READY HVAC INCOMPLETE not ready
All Rough Inspection - Commercial Failed 7/23/2015 7/24/2015 at 12:00 AM 07/24/2015
LOWER LEVEL
Corrective Action Required
07/22/2015
4000 LINE SETS CAULK TRUCK LINE INCOMPLETE -
FIRST FLOOR
Corrective Action Required
07/22/2015
4100,4112 not complete
SECOND FLOOR
Corrective Action Required
07/22/2015
NOT READY HVAC INCOMPLETE not ready
All Rough Inspection - Commercial Failed 7/27/2015 7/27/2015 at 12:00 AM 07/27/2015
LOWER LEVEL
Corrective Action Required
07/24/2015
4000 ok
FIRST FLOOR
Corrective Action Required
07/24/2015
SECOND FLOOR
Corrective Action Required
07/24/2015
NOT READY HVAC INCOMPLETE not ready, not ready
All Rough Inspection - Commercial Failed 7/28/2015 7/28/2015 at 12:00 AM 07/28/2015
LOWER LEVEL
Corrective Action Required
07/27/2015
TUB TRAPS FOR 1ST FLOOR INCOMPLETE (BSMT LEVELINPSECT)
FIRST FLOOR
Corrective Action Required
07/27/2015
SECOND FLOOR
Corrective Action Required
07/27/2015
NOT READY HVAC INCOMPLETE not ready, not ready, NOT READY3RD
All Rough Inspection - Commercial Failed 7/29/2015 7/29/2015 at 12:00 AM 07/29/2015
LOWER LEVEL
Corrective Action Required
07/28/2015
TUB TRAPS FOR 1ST FLOOR INCOMPLETE (BSMT LEVELINPSECT) 1/2 done
FIRST FLOOR
Corrective Action Required
07/28/2015
SECOND FLOOR
Corrective Action Required
07/28/2015
NOT READY HVAC INCOMPLETE not ready, not ready, NOT READY3RD, not ready
All Rough Inspection - Commercial Failed 7/30/2015 7/30/2015 at 12:00 AM 07/30/2015
LOWER LEVEL
Corrective Action Required
07/29/2015
TUB TRAPS FOR 1ST FLOOR INCOMPLETE (BSMT LEVELINPSECT) 1/2 done
FIRST FLOOR
Corrective Action Required
07/29/2015
SECOND FLOOR
Corrective Action Required
07/29/2015
NOT READY HVAC INCOMPLETE not ready, not ready, NOT READY3RD, not ready
All Rough Inspection - Commercial Partial 7/31/2015 7/31/2015 at 12:00 AM 07/31/2015
LOWER LEVEL
Corrective Action Required
07/30/2015
TUB TRAPS FOR 1ST FLOOR INCOMPLETE (BSMT LEVELINPSECT) 1/2 done
FIRST FLOOR
Corrective Action Required
07/30/2015
Misc
Partial Correction
07/31/2015
2ND FLOOR AND 3RD FLOOR RE-INSPECT-OK
All Rough Inspection - Commercial Not Ready 8/3/2015 8/3/2015 at 12:00 AM 08/03/2015
LOWER LEVEL
Corrective Action Required
07/31/2015
TUB TRAPS FOR 1ST FLOOR INCOMPLETE (BSMT LEVELINPSECT) 1/2 done
FIRST FLOOR
Corrective Action Required
07/31/2015
Misc
Partial Correction
07/31/2015
2ND FLOOR AND 3RD FLOOR RE-INSPECT-OK
All Rough Inspection - Commercial Partial 8/4/2015 8/4/2015 at 12:00 AM 08/04/2015
LOWER LEVEL
Corrective Action Required
08/03/2015
TUB TRAPS FOR 1ST FLOOR INCOMPLETE (BSMT LEVELINPSECT) 1/2 done
FIRST FLOOR
Corrective Action Required
08/03/2015
Misc
Partial Correction
08/03/2015
2ND FLOOR AND 3RD FLOOR RE-INSPECT-OK
FOURTH FLOOR
Partial Correction
08/04/2015
APPROVED TO COVER
Rated Assembly Inspection Partial 8/5/2015 8/5/2015 at 12:00 AM 08/05/2015
Misc
Resolved
08/05/2015
1st layer elevator walls failed needs screw rear of wall at corners dryer vent boxes-
FIRST FLOOR
Partial Correction
08/05/2015
1ST LAYER CORRIDOR LID APPROVED
SECOND FLOOR
Partial Correction
08/05/2015
1ST LAYER CORRIDOR LID APPROVED
THIRD FLOOR
Partial Correction
08/05/2015
1ST LAYER CORRIDOR LID APPROVED
All Rough Inspection - Commercial Partial 8/5/2015 8/5/2015 at 12:00 AM 08/05/2015
LOWER LEVEL
Resolved
08/05/2015
FIRST FLOOR
Corrective Action Required
08/04/2015
Misc
Partial Correction
08/04/2015
2ND FLOOR AND 3RD FLOOR RE-INSPECT-OK
FOURTH FLOOR
Partial Correction
08/04/2015
APPROVED TO COVER
Rated Assembly Inspection Not Ready 8/6/2015 8/6/2015 at 12:00 AM 08/06/2015
FIRST FLOOR
Partial Correction
08/05/2015
1ST LAYER CORRIDOR LID APPROVED
SECOND FLOOR
Partial Correction
08/05/2015
1ST LAYER CORRIDOR LID APPROVED
THIRD FLOOR
Partial Correction
08/05/2015
1ST LAYER CORRIDOR LID APPROVED
All Rough Inspection - Commercial Partial 8/6/2015 8/6/2015 at 12:00 AM 08/06/2015
FIRST FLOOR
Partial Correction
08/06/2015
ATTACHED GARAGES APPROVED TO COVER ONLY
Misc
Partial Correction
08/05/2015
2ND FLOOR AND 3RD FLOOR RE-INSPECT-OK
FOURTH FLOOR
Partial Correction
08/05/2015
APPROVED TO COVER
Rated Assembly Inspection Partial 8/7/2015 8/7/2015 at 12:00 AM 08/07/2015
FIRST FLOOR
Partial Correction
08/06/2015
2ND LAYER CORRIDOR LID APPROVED UNITS 1ST LAYER APPROVED
SECOND FLOOR
Partial Correction
08/06/2015
2ND LAYER CORRIDOR LID APPROVED
THIRD FLOOR
Partial Correction
08/06/2015
2ND LAYER CORRIDOR LID APPROVED
LOWER LEVEL
Partial Correction
08/07/2015
UNITS FIRST LAYER APPROVED
All Rough Inspection - Commercial Partial 8/10/2015 8/10/2015 at 12:00 AM 08/10/2015
FIRST FLOOR
Partial Correction
08/06/2015
ATTACHED GARAGES APPROVED TO COVER ONLY
Misc
Partial Correction
08/06/2015
2ND FLOOR AND 3RD FLOOR RE-INSPECT-OK
FOURTH FLOOR
Partial Correction
08/06/2015
APPROVED TO COVER
Rated Assembly Inspection Partial 8/11/2015 8/11/2015 at 12:00 AM 08/11/2015
FIRST FLOOR
Partial Correction
08/07/2015
2ND LAYER CORRIDOR LID APPROVED UNITS 1ST LAYER APPROVED
SECOND FLOOR
Partial Correction
08/07/2015
2ND LAYER CORRIDOR LID APPROVED 2 HOUR CONDIDTIONS APPROVED
THIRD FLOOR
Partial Correction
08/07/2015
2ND LAYER CORRIDOR LID APPROVED
LOWER LEVEL
Partial Correction
08/07/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED
FOURTH FLOOR
Partial Correction
08/11/2015
CORRIDOR LID APPROVED
Above Ceiling Inspection Failed 8/11/2015 8/11/2015 at 12:00 AM 08/11/2015
Misc
Corrective Action Required
08/11/2015
LANDINGS FOR STAIRS, ADD JOIST HANGER AND TOE NAIL JOISTS
Above Ceiling Inspection Passed 8/12/2015 8/12/2015 at 12:00 AM 08/12/2015
Misc
Resolved
08/12/2015
LANDINGS FOR STAIRS, ADD JOIST HANGER AND TOE NAIL JOISTS
Rated Assembly Inspection Partial 8/12/2015 8/12/2015 at 12:00 AM 08/12/2015
FIRST FLOOR
Partial Correction
08/11/2015
2ND LAYER CORRIDOR LID APPROVED UNITS 1ST LAYER APPROVED
SECOND FLOOR
Partial Correction
08/11/2015
2ND LAYER CORRIDOR LID APPROVED 2 HOUR CONDIDTIONS APPROVED
THIRD FLOOR
Partial Correction
08/11/2015
2ND LAYER CORRIDOR LID APPROVED
LOWER LEVEL
Partial Correction
08/11/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED
FOURTH FLOOR
Partial Correction
08/11/2015
CORRIDOR LID APPROVED
Rated Assembly Inspection Partial 8/14/2015 8/14/2015 at 12:00 AM 08/14/2015
FIRST FLOOR
Partial Correction
08/12/2015
2ND LAYER CORRIDOR LID APPROVED UNITS 1ST LAYER APPROVED
SECOND FLOOR
Partial Correction
08/12/2015
2ND LAYER CORRIDOR LID APPROVED 2 HOUR CONDIDTIONS APPROVED
THIRD FLOOR
Partial Correction
08/12/2015
2ND LAYER CORRIDOR LID APPROVED
LOWER LEVEL
Partial Correction
08/12/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED
FOURTH FLOOR
Partial Correction
08/14/2015
ELEVATOR LID APPROVED 1ST LAYER CORRIDOOR APPROVED
Rated Assembly Inspection Partial 8/17/2015 8/17/2015 at 12:00 AM 08/17/2015
FIRST FLOOR
Partial Correction
08/14/2015
2ND LAYER CORRIDOR LID APPROVED UNITS 1ST LAYER APPROVED
SECOND FLOOR
Partial Correction
08/14/2015
2ND LAYER CORRIDOR LID APPROVED 2 HOUR CONDIDTIONS APPROVED
THIRD FLOOR
Partial Correction
08/14/2015
2ND LAYER CORRIDOR LID APPROVED
LOWER LEVEL
Partial Correction
08/14/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.
FOURTH FLOOR
Partial Correction
08/14/2015
ELEVATOR LID 3RD LAYER APPROVED. 1ST LAYER CORRIDOOR APPROVED 1ST LAYER ROOM LIDS APPROVED EXCEPT 4404 AND 4408.
Rated Assembly Inspection Partial 8/18/2015 8/18/2015 at 12:00 AM 08/18/2015
FIRST FLOOR
Partial Correction
08/17/2015
2ND LAYER CORRIDOR LID APPROVED UNITS 1ST LAYER APPROVED
SECOND FLOOR
Partial Correction
08/17/2015
2ND LAYER CORRIDOR LID APPROVED 2 HOUR CONDIDTIONS APPROVED
THIRD FLOOR
Partial Correction
08/17/2015
2ND LAYER CORRIDOR LID APPROVED
LOWER LEVEL
Partial Correction
08/17/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED.
FOURTH FLOOR
Partial Correction
08/17/2015
ELEVATOR LID 4TH LAYER APPROVED. 1ST LAYER CORRIDOOR APPROVED 1ST LAYER ROOM LIDS APPROVED EXCEPT 4404 AND 4408.
Misc
Partial Correction
08/18/2015
STAIR TOWERS: 1ST LAYER APPROVED THROUGHOUT WALLS AND LIDS
Rated Assembly Inspection Partial 8/19/2015 8/19/2015 at 12:00 AM 08/19/2015
FIRST FLOOR
Partial Correction
08/18/2015
2ND LAYER CORRIDOR LID APPROVED UNITS 1ST LAYER APPROVED
SECOND FLOOR
Partial Correction
08/18/2015
2ND LAYER CORRIDOR LID APPROVED 2 HOUR CONDIDTIONS APPROVED
THIRD FLOOR
Partial Correction
08/18/2015
2ND LAYER CORRIDOR LID APPROVED
LOWER LEVEL
Partial Correction
08/18/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED.
FOURTH FLOOR
Partial Correction
08/18/2015
ELEVATOR LID 4TH LAYER APPROVED. 1ST AND 2ND LAYER CORRIDOOR APPROVED 1ST AND 2ND LAYER ROOM LIDS APPROVED 1ST LAYER WALLS APPROVED. INSTALL BATH FANS NORTH UNITS
Misc
Partial Correction
08/18/2015
STAIR TOWERS: 1ST LAYER APPROVED THROUGHOUT WALLS AND LIDS
Rated Assembly Inspection Partial 8/20/2015 8/20/2015 at 12:00 AM 08/20/2015
FIRST FLOOR
Partial Correction
08/19/2015
2ND LAYER CORRIDOR LID APPROVED UNITS 1ST LAYER APPROVED
SECOND FLOOR
Partial Correction
08/19/2015
2ND LAYER CORRIDOR LID APPROVED 2 HOUR CONDIDTIONS APPROVED
THIRD FLOOR
Partial Correction
08/19/2015
2ND LAYER CORRIDOR LID APPROVED
LOWER LEVEL
Partial Correction
08/19/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED. 2 hour conditions approved
FOURTH FLOOR
Partial Correction
08/19/2015
ELEVATOR LID 4TH LAYER APPROVED. 1ST AND 2ND LAYER CORRIDOOR APPROVED 1ST AND 2ND LAYER ROOM LIDS APPROVED 1ST LAYER WALLS APPROVED. INSTALL BATH FANS NORTH UNITS
Misc
Partial Correction
08/19/2015
STAIR TOWERS: 1ST LAYER APPROVED THROUGHOUT WALLS AND LIDS
Electrical Service Inspection Failed 8/21/2015 at 12:00 AM 08/21/2015
Misc
Corrective Action Required
04/27/2015
PULL SECONDARY CONDUCTORS AND GROUNDED CONDUCTORS AND LAND THEM. GOUNDING APPROVED.
Rated Assembly Inspection Partial 8/24/2015 8/24/2015 at 12:00 AM 08/24/2015
FIRST FLOOR
Partial Correction
08/20/2015
2ND LAYER CORRIDOR LID APPROVED UNITS 1ST LAYER APPROVED
SECOND FLOOR
Partial Correction
08/20/2015
2ND LAYER CORRIDOR LID APPROVED 2 HOUR CONDIDTIONS APPROVED
THIRD FLOOR
Partial Correction
08/20/2015
2ND LAYER CORRIDOR LID APPROVED units 1st layer
LOWER LEVEL
Partial Correction
08/20/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED. 2 hour conditions approved
FOURTH FLOOR
Partial Correction
08/20/2015
ELEVATOR LID 4TH LAYER APPROVED. 1ST AND 2ND LAYER CORRIDOOR APPROVED 1ST AND 2ND LAYER ROOM LIDS APPROVED 1ST LAYER WALLS APPROVED. INSTALL BATH FANS NORTH UNITS 2ND LAYER, 4TH FLOOR @ 2HR CONDITIONS; 1ST LAYER WALLS & CEILINGS, 3RD FLOOR; 2ND LAYER CEILING STAIR TOWERS & SECONDARY LANDINGS
Above Ceiling Inspection Failed 8/24/2015 8/24/2015 at 12:00 AM 08/24/2015
Above Ceiling Inspection Failed 8/25/2015 8/25/2015 at 12:00 AM 08/25/2015
LOWER LEVEL
Corrective Action Required
08/25/2015
CAULK HOLE IN CEILING SOUTH END
FIRST FLOOR
Corrective Action Required
08/25/2015
CAULK ALL HOLES D1 UNITS INCOMPLETE
SECOND FLOOR
Corrective Action Required
08/25/2015
ELECTRCIAL INCOMPLETE
THIRD FLOOR
Corrective Action Required
08/25/2015
INCOMPLETE
FOURTH FLOOR
Corrective Action Required
08/25/2015
Rated Assembly Inspection Partial 8/25/2015 8/25/2015 at 12:00 AM 08/25/2015
FIRST FLOOR
Partial Correction
08/24/2015
2ND LAYER CORRIDOR LID APPROVED UNITS 1ST LAYER APPROVED
SECOND FLOOR
Partial Correction
08/24/2015
2ND LAYER CORRIDOR LID APPROVED 2 HOUR CONDIDTIONS APPROVED
THIRD FLOOR
Partial Correction
08/24/2015
2ND LAYER CORRIDOR LID APPROVED units 1st layer 2ND LAYER 2HR WALLS
LOWER LEVEL
Partial Correction
08/24/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED. 2 hour conditions approved
FOURTH FLOOR
Partial Correction
08/24/2015
ELEVATOR LID 4TH LAYER APPROVED. 1ST AND 2ND LAYER CORRIDOOR APPROVED 1ST AND 2ND LAYER ROOM LIDS APPROVED 1ST LAYER WALLS APPROVED. INSTALL BATH FANS NORTH UNITS 2ND LAYER, 4TH FLOOR @ 2HR CONDITIONS; 1ST LAYER WALLS & CEILINGS, 3RD FLOOR; 2ND LAYER CEILING STAIR TOWERS & SECONDARY LANDINGS
Electrical Service Inspection Passed 8/26/2015 8/26/2015 at 12:00 AM 08/26/2015
Rated Assembly Inspection Partial 8/26/2015 8/26/2015 at 12:00 AM 08/26/2015
FIRST FLOOR
Resolved
08/26/2015
2ND LAYER CORRIDOR LID APPROVED UNITS 1ST LAYER APPROVED
SECOND FLOOR
Resolved
08/26/2015
2ND LAYER CORRIDOR LID APPROVED 2 HOUR CONDIDTIONS APPROVED
THIRD FLOOR
Resolved
08/26/2015
2ND LAYER CORRIDOR LID APPROVED units 1st layer 2ND LAYER 2HR WALLS
LOWER LEVEL
Partial Correction
08/25/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED. 2 hour conditions approved
FOURTH FLOOR
Corrective Action Required
08/26/2015
4th ok towers
Above Ceiling Inspection Partial 8/26/2015 8/26/2015 at 12:00 AM 08/26/2015
LOWER LEVEL
Resolved
08/26/2015
CAULK HOLE IN CEILING SOUTH ENDok
FIRST FLOOR
Corrective Action Required
08/25/2015
CAULK ALL HOLES D1 UNITS INCOMPLETE corridor partial
SECOND FLOOR
Corrective Action Required
08/25/2015
ELECTRCIAL INCOMPLETE 2nd time
THIRD FLOOR
Corrective Action Required
08/25/2015
INCOMPLETE 3rd time
FOURTH FLOOR
Corrective Action Required
08/26/2015
Water Service Inspection Passed 08/26/2015
Underslab Plumbing Inspection - Commercial Passed 08/26/2015
Underground Plumbing Inspection - Commercial Passed 08/26/2015
Sewer Service Inspection Passed 08/26/2015
Underslab Electrical Inspection - Commercial Passed 08/26/2015
All Rough Inspection - Commercial Passed 08/26/2015
FIRST FLOOR
Resolved
08/26/2015
ATTACHED GARAGES APPROVED TO COVER ONLY
Misc
Resolved
08/26/2015
2ND FLOOR AND 3RD FLOOR RE-INSPECT-OK
Above Ceiling Inspection Partial 8/27/2015 8/27/2015 at 12:00 AM 08/27/2015
FIRST FLOOR
Corrective Action Required
08/26/2015
CORRIODR
SECOND FLOOR
Corrective Action Required
08/26/2015
CORRIDOR
THIRD FLOOR
Corrective Action Required
08/26/2015
CORRIODR
Above Ceiling Inspection Partial 8/28/2015 8/28/2015 at 12:00 AM 08/28/2015
FIRST FLOOR
Corrective Action Required
08/27/2015
CORRIODR, D1
SECOND FLOOR
Corrective Action Required
08/27/2015
CORRIDOR, D1
THIRD FLOOR
Corrective Action Required
08/27/2015
CORRIODR,D1
Rated Assembly Inspection Partial 8/31/2015 8/31/2015 at 12:00 AM 08/31/2015
LOWER LEVEL
Partial Correction
08/26/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED. 2 hour conditions approved
FOURTH FLOOR
Corrective Action Required
08/26/2015
4th ok towers 4th layer
Rated Assembly Inspection Partial 9/1/2015 9/1/2015 at 12:00 AM 09/01/2015
LOWER LEVEL
Partial Correction
08/31/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED. 2 hour conditions approved
Above Ceiling Inspection Failed 9/1/2015 9/1/2015 at 12:00 AM 09/01/2015
FIRST FLOOR
Corrective Action Required
08/28/2015
CORRIODR, D1
SECOND FLOOR
Corrective Action Required
08/28/2015
CORRIDOR, D1
THIRD FLOOR
Corrective Action Required
08/28/2015
CORRIODR,D1
FOURTH FLOOR
Corrective Action Required
09/01/2015
ELECTRICAL INCOMPLETE
Above Ceiling Inspection Partial 9/2/2015 9/2/2015 at 12:00 AM 09/02/2015
FIRST FLOOR
Corrective Action Required
09/01/2015
CORRIODR, D1
SECOND FLOOR
Corrective Action Required
09/01/2015
CORRIDOR, D1
THIRD FLOOR
Corrective Action Required
09/01/2015
CORRIODR,D1
FOURTH FLOOR
Corrective Action Required
09/01/2015
INSTALL DAMPERS 4405-6 4412-4413 SECURE NM WITHIN 12" OF BOX
Above Ceiling Inspection Passed 9/3/2015 9/3/2015 at 12:00 AM 09/03/2015
FIRST FLOOR
Resolved
09/03/2015
CORRIODR, D1
SECOND FLOOR
Resolved
09/03/2015
CORRIDOR, D1
THIRD FLOOR
Resolved
09/03/2015
CORRIODR,D1
FOURTH FLOOR
Resolved
09/03/2015
Rated Assembly Inspection Partial 9/11/2015 9/11/2015 at 12:00 AM 09/11/2015
LOWER LEVEL
Partial Correction
09/01/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED. 2 hour conditions approved PLUMBING PENETRATIONS 1-4
Rated Assembly Inspection Failed 9/15/2015 9/15/2015 at 12:00 AM 09/15/2015
LOWER LEVEL
Partial Correction
09/11/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED. 2 hour conditions approved PLUMBING PENETRATIONS 1-4 MICRO VENT - FAILED 1-4
Rated Assembly Inspection Partial 9/16/2015 9/16/2015 at 12:00 AM 09/16/2015
LOWER LEVEL
Partial Correction
09/15/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED. HVAC PENETRATIONS 1-4 2 hour conditions approved PLUMBING PENETRATIONS 1-4 MICRO VENT - FAILED 1-4
Rated Assembly Inspection Partial 10/12/2015 10/12/2015 at 12:00 AM 10/12/2015
LOWER LEVEL
Partial Correction
09/16/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED. HVAC PENETRATIONS 1-4 2 hour conditions approved PLUMBING PENETRATIONS 1-4 MICRO VENT - FAILED 1-4 elevator wall-outside ok , inside 1,2
All Rough Inspection - Commercial Failed 10/13/2015 10/13/2015 at 12:00 AM 10/13/2015
LOWER LEVEL
Corrective Action Required
10/13/2015
FIRST FLOOR
Corrective Action Required
10/13/2015
Rated Assembly Inspection Partial 10/14/2015 10/14/2015 at 12:00 AM 10/14/2015
LOWER LEVEL
Partial Correction
10/12/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED. HVAC PENETRATIONS 1-4 2 hour conditions approved PLUMBING PENETRATIONS 1-4 MICRO VENT - FAILED 1-4 elevator wall-outside ok , inside 1,2
Misc
Partial Correction
10/14/2015
FIRST FLOOR SECOND LAYER ELEVATOR FRONTS APPROVED
All Rough Inspection - Commercial Passed 10/15/2015
LOWER LEVEL
Resolved
10/15/2015
FIRST FLOOR
Resolved
10/15/2015
In-wall Inspection Passed 10/5/2015 10/15/2015
LOWER LEVEL
Resolved
10/15/2015
PREROCK-LOWER LEVEL
FIRST FLOOR
Resolved
10/15/2015
PRE-ROCK SHOWERWALL
SECOND FLOOR
Resolved
10/15/2015
PRE ROCK SHOWER WALLS
THIRD FLOOR
Resolved
10/15/2015
PRE ROCK SHOWER WALLS -failed
FOURTH FLOOR
Resolved
10/15/2015
PRE ROCK SHOWER WALLS-failed
Rough Framing Inspection - Commercial Passed 10/15/2015
Misc
Resolved
10/15/2015
EXTERIOR WALL SHEAR 1-3 OK ELEVATOR -STRAP WALLS 1-4 FAILED
Rated Assembly Inspection Passed 10/15/2015 10/15/2015 at 12:00 AM 10/15/2015
LOWER LEVEL
Resolved
10/15/2015
UNITS FIRST LAYER APPROVED 2 HOUR CONDIDTIONS APPROVED 2ND LAYER ELEVATOR ROOM APPROVED 3RD AND FOURTH LAYER ELEVATOR ROOM FAILED DUE TO DUCT ELEVATION. STRUCTURAL BEAM STILL NEEDS PROTECTED.>>>1ST LAYER APPROVED. HVAC PENETRATIONS 1-4 2 hour conditions approved PLUMBING PENETRATIONS 1-4 MICRO VENT - FAILED 1-4 elevator wall-outside ok , inside 1,2
Misc
Resolved
10/15/2015
FIRST FLOOR SECOND LAYER ELEVATOR FRONTS APPROVED
Miscellaneous Inspection Failed 10/21/2015 10/21/2015 at 12:00 AM 10/21/2015
Misc
Corrective Action Required
10/21/2015
#4 4100-sink Carl outside 4102 4104 sink 4106 sink vent 4108 sink 4112 sink 4012 GFI patio door 4008 gfi sink dbl 4006 Gfci dbl sink 4004 gfi dbl 4002 ok 4000 ok
Miscellaneous Inspection Failed 10/22/2015 10/22/2015 at 12:00 AM 10/22/2015
Misc
Corrective Action Required
10/21/2015
#4 3rd,4th notready 2nd floor - sink blow off drain , units painting 4100-sink Carl outside 4102 4104 sink 4106 sink vent 4108 sink 4112 sink 4012 GFI patio door 4008 gfi sink dbl 4006 Gfci dbl sink 4004 gfi dbl 4002 ok 4000 ok
Occupancy Inspection - Planning Failed 10/27/2015
Corrective Action Required
10/27/2015
Installation of balcony railing on the east side of the building is not complete.
Sprinkler - Flow Test Passed 10/27/2015 at 9:30 AM 10/27/2015
Alarm Test Passed 10/27/2015 at 9:30 AM 10/27/2015
Occupancy Inspection - Fire Temporary C of O 10/27/2015 10/27/2015 at 12:00 AM 10/27/2015
Occupancy Inspection - Codes Commercial Failed 10/27/2015 10/27/2015 at 12:00 AM 10/27/2015
Misc
Corrective Action Required
10/27/2015
BASEMENT-OK 1ST FLOOR-UNITS OK 2ND FLOOR-01,02,04,05,06 BLOW OFF 3RD FLOOR NOT INSPECTED 4TH FLOOR- PLUMBING BLOW OFF PIPING HVAC CUT IN CEILING FOR HOOD 4400,12,13,11,08,09,07,06, 05 CUT CABINET OUTLET FOR HOOD. INSTALL 3M PILLOWS IN CONDUIT THROUGH FLOORS INSPECT ROOF NORTH WALL HEATER 1ST FLOOR INCOMPLETE STORAGE 8 PVC, S12 PVC IT ROOM , JANITOR CLOSET, OPEN BOX SOUTH EXTERIOR OF BUILDING.
Corrective Action Required
10/27/2015
Occupancy Inspection - Codes Commercial Temporary C of O 10/28/2015 10/29/2015 at 12:00 AM 10/29/2015
Misc
Resolved
02/04/2016
OK FOR TCO ALL FLOORS
Occupancy Inspection - Codes Commercial Partial 3/18/2016 12/15/2015
Misc
Resolved
03/18/2016
PENDING APPROVAL FROM ALL OTHER DEPARTMENTS
Occupancy Inspection - Planning Passed 01/28/2016
Occupancy Inspection - Fire Passed 3/17/2016 03/17/2016
Occupancy Inspection - Codes Commercial Failed 3/18/2016 03/18/2016
Resolved
02/04/2016
Resolved
02/04/2016
Occupancy Inspection - Codes Commercial Partial 03/18/2016
Occupancy Inspection - Codes Commercial Full C of O 03/18/2016
Documents & Images
Date Uploaded File Type Document Name
05/13/2014 Letter Fire Building Plan Review
05/22/2014 Letter Codes P/R Corrections Document
05/30/2014 Letter Statement of Special Inspections
06/09/2014 Letter Fire Building Plan Review
08/25/2014 Letter Fire (Alarm) Plan Review Notice
10/13/2014 Letter Fire (Alarm) Plan Review Notice
12/19/2014 Letter Fire (Sprinkler) Plan Review
01/08/2015 Receipt Receipt for transaction: 2015-000024
01/08/2015 Letter Codes Building Permit
01/14/2015 Letter Inspection Summary
01/20/2015 Letter Inspection Summary
04/27/2015 Letter Inspection Summary
05/07/2015 Letter Inspection Summary
05/19/2015 Letter Inspection Summary
05/20/2015 Letter Inspection Summary
05/22/2015 Letter Inspection Summary
06/23/2015 Letter Inspection Summary
06/24/2015 Letter Inspection Summary
06/25/2015 Letter Inspection Summary
06/26/2015 Letter Inspection Summary
07/08/2015 Letter Inspection Summary
07/09/2015 Letter Inspection Summary
07/14/2015 Letter Inspection Summary
07/15/2015 Letter Inspection Summary
07/16/2015 Letter Inspection Summary
07/17/2015 Letter Inspection Summary
07/22/2015 Letter Inspection Summary
07/27/2015 Letter Inspection Summary
07/28/2015 Letter Inspection Summary
07/29/2015 Letter Inspection Summary
07/31/2015 Letter Inspection Summary
08/03/2015 Letter Inspection Summary
08/04/2015 Letter Inspection Summary
08/05/2015 Letter Inspection Summary
08/06/2015 Letter Inspection Summary
08/07/2015 Letter Inspection Summary
08/10/2015 Letter Inspection Summary
08/11/2015 Letter Inspection Summary
08/12/2015 Letter Inspection Summary
08/14/2015 Letter Inspection Summary
08/17/2015 Letter Inspection Summary
08/18/2015 Letter Inspection Summary
08/19/2015 Letter Inspection Summary
08/20/2015 Letter Inspection Summary
08/21/2015 Letter Inspection Summary
08/24/2015 Letter Inspection Summary
08/25/2015 Letter Inspection Summary
08/26/2015 Letter Inspection Summary
08/26/2015 Letter Inspection Summary
08/27/2015 Letter Inspection Summary
08/28/2015 Letter Inspection Summary
08/31/2015 Letter Inspection Summary
09/01/2015 Letter Inspection Summary
09/02/2015 Letter Inspection Summary
09/03/2015 Letter Inspection Summary
09/11/2015 Letter Inspection Summary
09/15/2015 Letter Inspection Summary
09/16/2015 Letter Inspection Summary
10/12/2015 Letter Inspection Summary
10/13/2015 Letter Inspection Summary
10/14/2015 Letter Inspection Summary
10/15/2015 Letter Inspection Summary
10/21/2015 Letter Inspection Summary
10/22/2015 Letter Inspection Summary
10/27/2015 Letter Inspection Summary
10/29/2015 Letter Codes Temporary Certificate of Occupancy
03/18/2016 Letter Field Certificate of Occupancy
03/21/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home