Permit Application Status

PRCOM20140543


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20140543
Building Permit - Commercial
Certificate of Occupancy
RED LEES SUMMIT EAST LLC
NEW TENANT FINISH
TENANT FINISH
04/07/2014
05/15/2014
10/11/2014
07/02/2014
Locations
Contacts
SOUTHERN RETAIL CONSTRUCTION, INC, Address:11722 ALLISONVILLE RD, SUITE #103-438, Phone:(317) 863-5643  
S & D MECHANICAL LLC, Address:301 NW 73RD ST, Phone:(816) 616-4921  
TMF ELECTRIC, Address:2716 S VERMONT AVE  
NORTHSIDE PLUMBING, Address:975 SWIFT, Phone:(816) 842-7900  
CORTLAND MORGAN, Address:711 NORTH FIELDER ROAD, Phone:(817) 635-5696  
RED LEES SUMMIT EAST LLC, Address:1 E WASHINGTON ST STE 300  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 05/29/2014
Brian Austerman
Misc
Corrective Action Required
05/29/2014

Waterflow and tampers to be labeled and addressed for the Rue 21 space, verified at testing
Licensed Contractors Approved 04/17/2014 05/15/2014
Development Center
Business License
Corrective Action Required
04/14/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Corrective Action Required
04/14/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 04/15/2014
Joe Frogge
Address numbers required
Corrective Action Required
04/15/2014

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on doors leading into space, front door and corridor door. Verified at inspection
Misc
Corrective Action Required
04/15/2014

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Duct detection required for units over 2,000 cfm. Show on alarm plans
Construction documents - Fire protection systems
Corrective Action Required
04/15/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
04/15/2014

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Building Plan Review Approved with Conditions 04/15/2014
Joe Frogge
Misc
Corrective Action Required
04/15/2014

2012 IPC Location of shutoff valves. Shutoff valves shall be installed in the following locations: 1. On the fixture supply to each plumbing fixture other than bathtubs and showers in one- and two-family residential occupancies, and other than in individual sleeping units that are provided with unit shutoff valves in hotels, motels, boarding houses and similar occupancies. 2. On the water supply pipe to each sillcock. 3. On the water supply pipe to each appliance or mechanical equipment. Action required: Comment for informational purposes. Provide shutoff valves at required locations. To be verified at inspection.
Misc
Corrective Action Required
04/15/2014

Planning & Development sign requirements as concerns the proposed vinyl signage in storefront windows. •Summit Fair Shopping Center has a Tenant Sign Criteria Handbook that was approved by City Council. •The handbook states the following for window signs: Decals and lettering or other signing indicating product lines or credit card acceptability shall not be permitted on the storefront glazing other than store operating hours. •If signs are applied internally, the City doesn’t regulate this type of sign application. •If the window sign is applied to the exterior, than the City would have to review (which the handbook would dictate that it’s not allowed). Authorization from RED Development would be required for this type of sign application. If RED is okay with it and if the sign is applied internally than the City would be okay with the application. Required actions: Coordinate signage with RED Development. If signage is proposed to be applied to exterior of windows, contact Jennifer Thompson with our Planning Department at 969-1606.
Zoning Review Approved 04/17/2014 04/14/2014
Joe Frogge
Building Plan Review Approved with Conditions 04/17/2014 04/14/2014
Joe Frogge
Misc
Corrective Action Required
04/14/2014

2012 IPC Location of shutoff valves. Shutoff valves shall be installed in the following locations: 1. On the fixture supply to each plumbing fixture other than bathtubs and showers in one- and two-family residential occupancies, and other than in individual sleeping units that are provided with unit shutoff valves in hotels, motels, boarding houses and similar occupancies. 2. On the water supply pipe to each sillcock. 3. On the water supply pipe to each appliance or mechanical equipment. Action required: Comment for informational purposes. Provide shutoff valves at required locations. To be verified at inspection.
Misc
Corrective Action Required
04/14/2014

Planning & Development sign requirements as concerns the proposed vinyl signage in storefront windows. •Summit Fair Shopping Center has a Tenant Sign Criteria Handbook that was approved by City Council. •The handbook states the following for window signs: Decals and lettering or other signing indicating product lines or credit card acceptability shall not be permitted on the storefront glazing other than store operating hours. •If signs are applied internally, the City doesn’t regulate this type of sign application. •If the window sign is applied to the exterior, than the City would have to review (which the handbook would dictate that it’s not allowed). Authorization from RED Development would be required for this type of sign application. If RED is okay with it and if the sign is applied internally than the City would be okay with the application. Required actions: Coordinate signage with RED Development. If signage is proposed to be applied to exterior of windows, contact Jennifer Thompson with our Planning Department at 969-1606.
Fire Plan Review Approved with Conditions 04/17/2014 04/10/2014
Brian Austerman
Address numbers required
Corrective Action Required
04/10/2014

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on doors leading into space, front door and corridor door. Verified at inspection
Misc
Corrective Action Required
04/10/2014

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Duct detection required for units over 2,000 cfm. Show on alarm plans
Construction documents - Fire protection systems
Corrective Action Required
04/10/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
04/10/2014

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $659.40 $659.40 Paid 05/15/2014
$659.40
8331507-Sewer Connection Fee $180.00 $180.00 Paid 05/15/2014
$180.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 5/20/2014 5/20/2014 at 12:00 AM 05/20/2014
In-wall Inspection Partial 5/23/2014 at 12:00 AM 05/23/2014
Misc
Partial Correction
05/23/2014
OK TO COVER WHEN READY LIGHT-GUAGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: PERIMETER WALLS EXCEPT AT IN-WALL ELECTRICAL;
In-wall Inspection Partial 5/23/2014 at 12:00 AM 05/23/2014
Misc
Partial Correction
05/23/2014
OK TO COVER WHEN READY LIGHT-GUAGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: PERIMETER WALLS INCLUDING AT IN-WALL ELECTRICAL;
In-wall Inspection Partial 5/28/2014 5/28/2014 at 12:00 AM 05/28/2014
Misc
Partial Correction
05/23/2014
OK TO COVER WHEN READY LIGHT-GUAGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: PERIMETER WALLS INCLUDING AT IN-WALL ELECTRICAL;
Partial Correction
05/28/2014
OKAY TO COVER INTERIOR WALLS. TWO STORM DRAIN CLEANOUTS ARE TO REMAIN ACCESSABLE. MAKE UP GROUNDING PIG TAILS IN BOXES AND CALL FOR INSPECTION BEFORE INSTALLING DEVICES.
Rated Assembly Inspection Partial 5/30/2014 at 12:00 AM 05/28/2014
Misc
Partial Correction
05/28/2014
SCREW PATTERN APPROVED PER UL 465. FIRE CAULK PENETATIONS IN 1 HOUR WALL PER DETAIL FOR THE "A" AND "A1" WALLS AND CALL FOR RE-INSPECTION.
Above Ceiling Inspection Partial 5/30/2014 5/30/2014 at 12:00 AM 05/30/2014
Misc
Partial Correction
05/30/2014
BATHROOM LIDS APPROVED
In-wall Inspection Partial 6/9/2014 at 12:00 AM 06/09/2014
Misc
Corrective Action Required
06/09/2014
TWO ROOF DRAIN RISERS AT NORTH WALL: LOCATE TO ACCOMODATE REMOVAL OF THREADED PLUGS
Rated Assembly Inspection Passed 6/9/2014 at 12:00 AM 06/09/2014
Misc
Resolved
06/09/2014
SCREW PATTERN APPROVED PER UL 465. FIRE CAULK PENETATIONS IN 1 HOUR WALL PER DETAIL FOR THE "A" AND "A1" WALLS AND CALL FOR RE-INSPECTION.
In-wall Inspection Passed 6/10/2014 at 12:00 AM 06/10/2014
Misc
Resolved
06/10/2014
TWO ROOF DRAIN RISERS AT NORTH WALL: LOCATE TO ACCOMODATE REMOVAL OF THREADED PLUGS
In-wall Inspection Passed 6/18/2014 6/18/2014 at 12:00 AM 06/18/2014
Electrical Service Inspection Partial 6/20/2014 6/20/2014 at 12:00 AM 06/20/2014
Misc
Partial Correction
06/20/2014
SERVICE EQUIPMENT AND WIRING COMPLETE TO LOAD SIDE DISCONNECT. #6 SERVICE GROUND TO BUILDING GROUND GRID TO BE REPLACED WITH #4. SERVICE RELEASED TO KCP&L FOR SCHEDULING. JB TO RE-INSPECT EQUIPMENT AND WIRING PRIOR TO ACTIVATION.
Electrical Service Inspection Passed 6/23/2014 at 12:00 AM 06/23/2014
Misc
Resolved
06/23/2014
SERVICE EQUIPMENT AND WIRING COMPLETE TO LOAD SIDE DISCONNECT. #6 SERVICE GROUND TO BUILDING GROUND GRID TO BE REPLACED WITH #4. SERVICE RELEASED TO KCP&L FOR SCHEDULING. JB TO RE-INSPECT EQUIPMENT AND WIRING PRIOR TO ACTIVATION.
Above Ceiling Inspection Passed 5/30/2014 at 12:00 AM 06/23/2014
Misc
Resolved
06/23/2014
BATHROOM LIDS APPROVED
Alarm Test Passed 6/23/2014 at 12:00 AM 06/23/2014
Sprinkler - Flow Test Passed 6/23/2014 at 12:00 AM 06/25/2014
Occupancy Inspection - Codes Commercial Not Ready 6/26/2014 6/26/2014 at 12:00 AM 06/26/2014
Misc
Corrective Action Required
06/26/2014
ELECTRICAL SERVICE NOT YET ACTIVATED
Occupancy Inspection - Fire Temporary C of O 6/25/2014 6/25/2014 at 12:00 AM 06/26/2014
Misc
Corrective Action Required
06/26/2014
- j-boxes need covers -deck level by HVAC - exit and emergency lights need to illuminate on AC and DC power - test duct detection devices - exit sign over rear exit door
Occupancy Inspection - Codes Commercial Not Ready 6/27/2014 at 12:00 AM 06/27/2014
Misc
Resolved
06/27/2014
ELECTRICAL SERVICE NOT YET ACTIVATED
Misc
Partial Correction
06/27/2014
OK TO SET UP FOR BUSINESS AT SALES AREA ONLY. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Misc
Corrective Action Required
06/27/2014
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
06/27/2014
NEC 380-10 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: CHECK ALL AND ENSURE NONE ARE "SOFT" OR LOOSE SIDE-TO-SIDE.
Misc
Corrective Action Required
06/27/2014
AREAS OTHER THAN SALES AREA NOT READY FOR INSPECTION.
Misc
Corrective Action Required
06/27/2014
ROOFTOP INSPECTION YET TO BE PERFORMED.
Occupancy Inspection - Codes Commercial Not Ready 6/30/2014 6/30/2014 at 12:00 AM 06/30/2014
Misc
Partial Correction
06/27/2014
OK TO SET UP FOR BUSINESS AT SALES AREA ONLY. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Misc
Corrective Action Required
06/27/2014
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
06/27/2014
NEC 380-10 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: CHECK ALL AND ENSURE NONE ARE "SOFT" OR LOOSE SIDE-TO-SIDE.
Misc
Corrective Action Required
06/27/2014
AREAS OTHER THAN SALES AREA NOT READY FOR INSPECTION.
Misc
Corrective Action Required
06/27/2014
ROOFTOP INSPECTION YET TO BE PERFORMED.
Occupancy Inspection - Fire Passed 7/2/2014 7/2/2014 at 12:00 AM 07/02/2014
Occupancy Inspection - Codes Commercial Full C of O 7/2/2014 7/2/2014 at 12:00 AM 07/02/2014
Misc
Resolved
07/02/2014
OK TO SET UP FOR BUSINESS AT SALES AREA ONLY. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Misc
Resolved
07/02/2014
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Resolved
07/02/2014
NEC 380-10 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: CHECK ALL AND ENSURE NONE ARE "SOFT" OR LOOSE SIDE-TO-SIDE.
Misc
Resolved
07/02/2014
AREAS OTHER THAN SALES AREA NOT READY FOR INSPECTION.
Misc
Resolved
07/02/2014
ROOFTOP INSPECTION YET TO BE PERFORMED.
Miscellaneous Inspection Passed 7/2/2014 at 12:00 AM 07/02/2014
Documents & Images
Date Uploaded File Type Document Name
04/10/2014 Letter Fire Building Plan Review
04/14/2014 Letter Codes P/R Corrections Document
05/15/2014 Letter Codes Building Permit
05/15/2014 Letter Codes Plan Review Conditions
05/20/2014 Letter Inspection Summary
05/23/2014 Letter Inspection Summary
05/23/2014 Letter Inspection Summary
05/28/2014 Letter Inspection Summary
05/29/2014 Letter Fire (Alarm) Plan Review Notice
05/30/2014 Letter Inspection Summary
06/09/2014 Letter Inspection Summary
06/18/2014 Letter Inspection Summary
06/20/2014 Letter Inspection Summary
06/23/2014 Letter Inspection Summary
06/27/2014 Letter Inspection Summary
07/02/2014 Letter Field Certificate of Occupancy
09/12/2014 Letter Codes Final Certificate of Occupancy
09/12/2014 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home