Review Type |
Outcome |
Est. Completion Date |
Completed |
Final Development Plan Review
|
Approved
|
08/19/2014
|
05/27/2014
|
|
Mike Weisenborn
|
|
|
Licensed Contractors
|
Approved
|
04/23/2014
|
04/23/2014
|
|
Mike Weisenborn
|
|
|
Fire Plan Review
|
Approved with Conditions
|
04/30/2014
|
04/23/2014
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
THUMB LATCH OR PANIC HARDWARE ONLY ON THE EGRESS SIDE OF MARKED EXITS, FOR INFORMATION ONLY
|
|
Misc
Corrective Action Required
RECCOMMEND AN ADDITIONAL EXIT SIGN/ COMBINATION LIGHT IN THE CORRIDOR
|
|
Portable fire extinguishers - general
Corrective Action Required
2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
MINIMUM SIZE IS 2A10B:C
|
|
Misc
Corrective Action Required
WILL THERE BE ANY COMPRESSED GASSES AND IF SO INDICATE TYPE, SIZE AND STORAGE LOCATIONS
|
|
|
Building Plan Review
|
Approved with Conditions
|
04/30/2014
|
04/23/2014
|
|
Mike Weisenborn
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required - This comment is for information purposes.
|
|
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Action required - This comment is for information purposes.
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required - Provide two (2) copies of the engineered truss package. The package shall be signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to framing inspection.
|
|
Bldg - Doors - Door hardware
Corrective Action Required
2006 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Action required - Make needed corrections.
Mike Weisenborn 02/18/2014 3:48 PM - To be verified on inspection.
|
|
NEC - Receptacles - Grounding
Corrective Action Required
2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B).
Action required - Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 3:52 PM - Note added to the plans. To be verified on inspection.
|
|
Bldg - Size of doors 1008.1.1
Corrective Action Required
2012 IBC 1008.1.1 – Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in a Group i-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of door openings shall not be less than 80 inches. See Code for possible exceptions.
Action required - Door 112 does not meet the minimum width requirement of 32 inches clear as the closet is larger than 10 square feet. The plans do not need to be revised but compliance will be verified on inspection.
|
|
|
Licensed Contractors
|
Approved
|
02/21/2014
|
02/20/2014
|
|
Mike Weisenborn
|
|
License contractors
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances.
Action required - Provide the names of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval.
|
|
|
Building Plan Review
|
Rejected
|
02/21/2014
|
02/19/2014
|
|
Mike Weisenborn
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required - This comment is for information purposes.
|
|
Plumb - Separate facilities
2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.)
Action required - Make needed corrections to the plans.
Mike Weisenborn 02/18/2014 3:34 PM - Corrections have been made.
|
|
Bldg - Accessibility - Toilet and bathing facilities
2006 IBC 1109.2 - Toilet and bathing facilities. Toilet rooms and bathing facilities shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing facilities provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing facility shall be accessible.
Action required - All restrooms are required to meet the requirements of this section. Restrooms located off of private offices can be adaptable as outlined in this section. Make needed corrections.
Mike Weisenborn 02/18/2014 3:35 PM - The private restroom has been removed.
|
|
Accessibility - Water closet - Clearance around
ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided.
Action required - Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 3:36 PM - Corrections have been made.
|
|
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1.
Action required - Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 3:38 PM - Corrections have been made.
|
|
Accessibility - Lavatories and sinks - Clear floor space
ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.)
Action required - Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 3:40 PM - Corrections have been made.
|
|
Bldg - Accessibility - Point of sale and service counters 1109.12.3
2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Action required - Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 3:41 PM - Corrections have been made.
|
|
Bldg - Toilet rooms - Floor surface and walls
2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Action required - The finish schedule indicates that wood is to be used in the restrooms. Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 3:43 PM - Corrections have been made.
|
|
Bldg - Toilet rooms - Walls
2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture.
Action required - This requirement includes walls next to the water closets. Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 3:43 PM - Corrections have been made.
|
|
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Action required - This comment is for information purposes.
|
|
Bldg - Accessibility - Drinking fountains minimum number
2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons.
Action required - If a drinking fountain is provided it shall meet both height requirements. Make corrections needed to comply with this section. Note - The City of Lee's Summit does not require a drinking fountain when a breakroom sink is provided.
Mike Weisenborn 02/18/2014 3:44 PM - Corrections have been made.
|
|
Accessibility - Water closet - Grab bars
ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Action required - I am unable to locate any reference to the required vertical grab bar. Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 3:44 PM - Corrections have been made.
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required - Provide two (2) copies of the engineered truss package. The package shall be signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to framing inspection.
|
|
Bldg - Glazing - Human impact loads
2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Action required - Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 3:45 PM - Corrections have been made.
|
|
Mech - Domestic clothes dryer ducts 504.6
2006 IBC 504.6 - Domestic clothes dryer ducts. Exhaust ducts for domestic clothes dryers shall be constructed of metal and shall have a smooth interior finish. The exhaust duct shall be a minimum nominal size of 4 inches in diameter. The entire exhaust system shall be supported and secured in place. The male end of the duct at overlapped duct joints shall extend in the direction of airflow. Clothes dryer transition ducts used to connect the appliance to the exhaust duct system shall be limited to single lengths not to exceed 8 feet and shall be listed and labeled for the application. Transition ducts shall not be concealed within construction.
Action required - Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 3:47 PM - Corrections have been made.
|
|
Mech - Access to elevated appliances
2006 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet, such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances level service space. Such access shall not require climbing over obstructions greater than 30 inches high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches. 2. Ladders shall have rung spacing not to exceed 14 inches on center. 3. Ladders shall have a toe spacing not less than 6 inches deep. 4. There shall be a minimum of 18 inches between rails. 5. Rungs shall have a minimum 0.75-inch diameter and be capable of withstanding a 300-pound load. 6. Ladders over 30 feet in height shall be provided with offset sections and landings capable of withstanding 100 pound per square foot. 7. Ladders shall be protected against corrosion by approved means. Catwalks installed to provide the required access shall be not less than 24 inches wide and shall have railing as required for service platforms.
Action required - Details for the ladder have not been provided. Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 3:48 PM - Corrections have been made.
|
|
Bldg - Doors - Door hardware
Corrective Action Required
2006 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Action required - Make needed corrections.
Mike Weisenborn 02/18/2014 3:48 PM - To be verified on inspection.
|
|
NEC - Receptacles - Grounding
Corrective Action Required
2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B).
Action required - Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 3:52 PM - Note added to the plans. To be verified on inspection.
|
|
Misc
The site plan shows a north/south property line about 2 feet from the east wall of the building. Our records do not show a property line at this location. If there is a property line or is to be a property line at this location than the east wall of the building will be required to meet fire-resistant construction requirements as applicable.
Action required - Make corrections needed to comply with the code.
Mike Weisenborn 02/18/2014 3:53 PM - Corrections have been made.
|
|
Misc
I am unable to locate construction details which show compliance with the requirements of Section 2308 of the 2006 IBC.
Action required - Make corrections needed to comply with this section.
Mike Weisenborn 02/18/2014 4:06 PM - Information has been added.
|
|
Misc
Details/specifications for the exray equipment has not been provided.
Action required - Provide specifications and installation requirements for the x-ray equipment.
Mike Weisenborn 02/19/2014 2:07 PM - I am unable to locate information regarding protection of the x-ray area. Please provide additional information.
Mike Weisenborn 04/23/2014 2:42 PM - Information has been provided. A copy of the sheilding requirements have been attached to the plans.
|
|
Misc
I am unable to locate the electrical panel on the plans.
Action - Provide additional information.
Mike Weisenborn 02/18/2014 3:54 PM - Added to the plans.
|
|
Misc
I am unable to locate the disconnect for the electrical system.
Action required - Provide additional information.
Mike Weisenborn 02/18/2014 3:55 PM - Information has been added.
|
|
Misc
The plans do not show where the stormwater is going once it leaves the downspouts.
Action required - Provide additional information.
Mike Weisenborn 02/18/2014 4:01 PM - Information has been added.
|
|
Bldg - Size of doors 1008.1.1
Corrective Action Required
2012 IBC 1008.1.1 – Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in a Group i-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of door openings shall not be less than 80 inches. See Code for possible exceptions.
Action required - Door 112 does not meet the minimum width requirement of 32 inches clear as the closet is larger than 10 square feet. The plans do not need to be revised but compliance will be verified on inspection.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
02/21/2014
|
02/18/2014
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
THUMB LATCH OR PANIC HARDWARE ONLY ON THE EGRESS SIDE OF MARKED EXITS, FOR INFORMATION ONLY
|
|
Misc
Corrective Action Required
RECCOMMEND AN ADDITIONAL EXIT SIGN/ COMBINATION LIGHT IN THE CORRIDOR
|
|
Portable fire extinguishers - general
Corrective Action Required
2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
MINIMUM SIZE IS 2A10B:C
|
|
Misc
Corrective Action Required
WILL THERE BE ANY COMPRESSED GASSES AND IF SO INDICATE TYPE, SIZE AND STORAGE LOCATIONS
|
|
|
Building Plan Review
|
Rejected
|
11/15/2013
|
11/15/2013
|
|
Mike Weisenborn
|
|
Final Development Plan
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required - This comment is for information purposes.
|
|
Plumb - Separate facilities
Corrective Action Required
2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.)
Action required - Make needed corrections to the plans.
|
|
Bldg - Accessibility - Toilet and bathing facilities
Corrective Action Required
2006 IBC 1109.2 - Toilet and bathing facilities. Toilet rooms and bathing facilities shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing facilities provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing facility shall be accessible.
Action required - All restrooms are required to meet the requirements of this section. Restrooms located off of private offices can be adaptable as outlined in this section. Make needed corrections.
|
|
Accessibility - Water closet - Clearance around
Corrective Action Required
ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided.
Action required - Make corrections needed to comply with this section.
|
|
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Corrective Action Required
2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1.
Action required - Make corrections needed to comply with this section.
|
|
Accessibility - Lavatories and sinks - Clear floor space
Corrective Action Required
ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.)
Action required - Make corrections needed to comply with this section.
|
|
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Action required - Make corrections needed to comply with this section.
|
|
Bldg - Toilet rooms - Floor surface and walls
Corrective Action Required
2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Action required - The finish schedule indicates that wood is to be used in the restrooms. Make corrections needed to comply with this section.
|
|
Bldg - Toilet rooms - Walls
Corrective Action Required
2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture.
Action required - This requirement includes walls next to the water closets. Make corrections needed to comply with this section.
|
|
Accessibility - Refrigerator/Freezer - General requirements
ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Action required - This comment is for information purposes.
|
|
Bldg - Accessibility - Drinking fountains minimum number
Corrective Action Required
2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons.
Action required - If a drinking fountain is provided it shall meet both height requirements. Make corrections needed to comply with this section. Note - The City of Lee's Summit does not require a drinking fountain when a breakroom sink is provided.
|
|
Accessibility - Water closet - Grab bars
Corrective Action Required
ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Action required - I am unable to locate any reference to the required vertical grab bar. Make corrections needed to comply with this section.
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required - Provide two (2) copies of the engineered truss package. The package shall be signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to framing inspection.
|
|
Bldg - Glazing - Human impact loads
Corrective Action Required
2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Action required - Make corrections needed to comply with this section.
|
|
Mech - Domestic clothes dryer ducts 504.6
Corrective Action Required
2006 IBC 504.6 - Domestic clothes dryer ducts. Exhaust ducts for domestic clothes dryers shall be constructed of metal and shall have a smooth interior finish. The exhaust duct shall be a minimum nominal size of 4 inches in diameter. The entire exhaust system shall be supported and secured in place. The male end of the duct at overlapped duct joints shall extend in the direction of airflow. Clothes dryer transition ducts used to connect the appliance to the exhaust duct system shall be limited to single lengths not to exceed 8 feet and shall be listed and labeled for the application. Transition ducts shall not be concealed within construction.
Action required - Make corrections needed to comply with this section.
|
|
Mech - Access to elevated appliances
Corrective Action Required
2006 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet, such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances level service space. Such access shall not require climbing over obstructions greater than 30 inches high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches. 2. Ladders shall have rung spacing not to exceed 14 inches on center. 3. Ladders shall have a toe spacing not less than 6 inches deep. 4. There shall be a minimum of 18 inches between rails. 5. Rungs shall have a minimum 0.75-inch diameter and be capable of withstanding a 300-pound load. 6. Ladders over 30 feet in height shall be provided with offset sections and landings capable of withstanding 100 pound per square foot. 7. Ladders shall be protected against corrosion by approved means. Catwalks installed to provide the required access shall be not less than 24 inches wide and shall have railing as required for service platforms.
Action required - Details for the ladder have not been provided. Make corrections needed to comply with this section.
|
|
Bldg - Doors - Door hardware
Corrective Action Required
2006 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Action required - Make corrections needed to comply with this section.
|
|
NEC - Receptacles - Grounding
Corrective Action Required
2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B).
Action required - Make corrections needed to comply with this section.
|
|
Misc
Corrective Action Required
The site plan shows a north/south property line about 2 feet from the east wall of the building. Our records do not show a property line at this location. If there is a property line or is to be a property line at this location than the east wall of the building will be required to meet fire-resistant construction requirements as applicable.
Action required - Make corrections needed to comply with the code.
|
|
Misc
Corrective Action Required
I am unable to locate construction details which show compliance with the requirements of Section 2308 of the 2006 IBC.
Action required - Make corrections needed to comply with this section.
|
|
Misc
Corrective Action Required
Details/specifications for the exray equipment has not been provided.
Action required - Provide specifications and installation requirements for the x-ray equipment.
|
|
Misc
Corrective Action Required
I am unable to locate the electrical panel on the plans.
Action - Provide additional information.
|
|
Misc
Corrective Action Required
I am unable to locate the disconnect for the electrical system.
Action required - Provide additional information.
|
|
Misc
Corrective Action Required
The plans do not show where the stormwater is going once it leaves the downspouts.
Action required - Provide additional information.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
11/15/2013
|
11/14/2013
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
THUMB LATCH OR PANIC HARDWARE ONLY ON THE EGRESS SIDE OF MARKED EXITS, FOR INFORMATION ONLY
|
|
Misc
Corrective Action Required
RECCOMMEND AN ADDITIONAL EXIT SIGN/ COMBINATION LIGHT IN THE CORRIDOR
|
|
Portable fire extinguishers - general
Corrective Action Required
2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
MINIMUM SIZE IS 2A10B:C
|
|
Misc
Corrective Action Required
WILL THERE BE ANY COMPRESSED GASSES AND IF SO INDICATE TYPE, SIZE AND STORAGE LOCATIONS
|
|
|