Summary
PRCOM20132440
Building Permit - Commercial
Certificate of Occupancy
GRIDER PROPERTIES LLC
NEW COMMERCIAL
GRIDER ORTHODONTICS BUILDING
11/01/2013
08/12/2014
08/19/2014
04/08/2015
Locations
Contacts
GRIDER PROPERTIES LLC, Address:2725 NW THOREAU DR, Phone:(816) 260-0699  
KC CONSTRUCTORS INC, Address:14716 S BYNUM RD, Phone:(816) 246-2095  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
KC CONSTRUCTORS INC, Address:14716 S BYNUM RD, Phone:(816) 246-2095  
INTEGRITY PLUMBING SERVICES LLC, Address:405 SW Nelson Dr., Phone:(816) 803-9032  
CREAL, CLARK AND SEIFERT, Address:919 CORBY STREET, Phone:(816) 364-2435  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 08/19/2014 05/27/2014
Mike Weisenborn
Licensed Contractors Approved 04/23/2014 04/23/2014
Mike Weisenborn
Fire Plan Review Approved with Conditions 04/30/2014 04/23/2014
Mike Weisenborn
Misc
Corrective Action Required
04/23/2014

1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. THUMB LATCH OR PANIC HARDWARE ONLY ON THE EGRESS SIDE OF MARKED EXITS, FOR INFORMATION ONLY
Misc
Corrective Action Required
04/23/2014

RECCOMMEND AN ADDITIONAL EXIT SIGN/ COMBINATION LIGHT IN THE CORRIDOR
Portable fire extinguishers - general
Corrective Action Required
04/23/2014

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. MINIMUM SIZE IS 2A10B:C
Misc
Corrective Action Required
04/23/2014

WILL THERE BE ANY COMPRESSED GASSES AND IF SO INDICATE TYPE, SIZE AND STORAGE LOCATIONS
Building Plan Review Approved with Conditions 04/30/2014 04/23/2014
Mike Weisenborn
Final Development Plan
Corrective Action Required
04/23/2014

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required - This comment is for information purposes.
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
04/23/2014

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Engineered truss package
Corrective Action Required
04/23/2014

Copies of the engineered truss package were not provided at the time of permit application. Action required - Provide two (2) copies of the engineered truss package. The package shall be signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to framing inspection.
Bldg - Doors - Door hardware
Corrective Action Required
04/23/2014

2006 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate. Action required - Make needed corrections. Mike Weisenborn 02/18/2014 3:48 PM - To be verified on inspection.
NEC - Receptacles - Grounding
Corrective Action Required
04/23/2014

2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B). Action required - Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 3:52 PM - Note added to the plans. To be verified on inspection.
Bldg - Size of doors 1008.1.1
Corrective Action Required
04/23/2014

2012 IBC 1008.1.1 – Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in a Group i-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of door openings shall not be less than 80 inches. See Code for possible exceptions. Action required - Door 112 does not meet the minimum width requirement of 32 inches clear as the closet is larger than 10 square feet. The plans do not need to be revised but compliance will be verified on inspection.
Licensed Contractors Approved 02/21/2014 02/20/2014
Mike Weisenborn
License contractors
Resolved
02/20/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval.
Building Plan Review Rejected 02/21/2014 02/19/2014
Mike Weisenborn
Final Development Plan
Corrective Action Required
02/19/2014

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required - This comment is for information purposes.
Plumb - Separate facilities
Resolved
02/18/2014

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - Make needed corrections to the plans. Mike Weisenborn 02/18/2014 3:34 PM - Corrections have been made.
Bldg - Accessibility - Toilet and bathing facilities
Resolved
02/18/2014

2006 IBC 1109.2 - Toilet and bathing facilities. Toilet rooms and bathing facilities shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing facilities provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing facility shall be accessible. Action required - All restrooms are required to meet the requirements of this section. Restrooms located off of private offices can be adaptable as outlined in this section. Make needed corrections. Mike Weisenborn 02/18/2014 3:35 PM - The private restroom has been removed.
Accessibility - Water closet - Clearance around
Resolved
02/18/2014

ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided. Action required - Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 3:36 PM - Corrections have been made.
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Resolved
02/18/2014

2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1. Action required - Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 3:38 PM - Corrections have been made.
Accessibility - Lavatories and sinks - Clear floor space
Resolved
02/18/2014

ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.) Action required - Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 3:40 PM - Corrections have been made.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Resolved
02/18/2014

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 3:41 PM - Corrections have been made.
Bldg - Toilet rooms - Floor surface and walls
Resolved
02/18/2014

2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches. Action required - The finish schedule indicates that wood is to be used in the restrooms. Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 3:43 PM - Corrections have been made.
Bldg - Toilet rooms - Walls
Resolved
02/18/2014

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - This requirement includes walls next to the water closets. Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 3:43 PM - Corrections have been made.
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
02/19/2014

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Bldg - Accessibility - Drinking fountains minimum number
Resolved
02/18/2014

2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. Action required - If a drinking fountain is provided it shall meet both height requirements. Make corrections needed to comply with this section. Note - The City of Lee's Summit does not require a drinking fountain when a breakroom sink is provided. Mike Weisenborn 02/18/2014 3:44 PM - Corrections have been made.
Accessibility - Water closet - Grab bars
Resolved
02/18/2014

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - I am unable to locate any reference to the required vertical grab bar. Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 3:44 PM - Corrections have been made.
Engineered truss package
Corrective Action Required
02/18/2014

Copies of the engineered truss package were not provided at the time of permit application. Action required - Provide two (2) copies of the engineered truss package. The package shall be signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to framing inspection.
Bldg - Glazing - Human impact loads
Resolved
02/18/2014

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 3:45 PM - Corrections have been made.
Mech - Domestic clothes dryer ducts 504.6
Resolved
02/18/2014

2006 IBC 504.6 - Domestic clothes dryer ducts. Exhaust ducts for domestic clothes dryers shall be constructed of metal and shall have a smooth interior finish. The exhaust duct shall be a minimum nominal size of 4 inches in diameter. The entire exhaust system shall be supported and secured in place. The male end of the duct at overlapped duct joints shall extend in the direction of airflow. Clothes dryer transition ducts used to connect the appliance to the exhaust duct system shall be limited to single lengths not to exceed 8 feet and shall be listed and labeled for the application. Transition ducts shall not be concealed within construction. Action required - Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 3:47 PM - Corrections have been made.
Mech - Access to elevated appliances
Resolved
02/18/2014

2006 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet, such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances level service space. Such access shall not require climbing over obstructions greater than 30 inches high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches. 2. Ladders shall have rung spacing not to exceed 14 inches on center. 3. Ladders shall have a toe spacing not less than 6 inches deep. 4. There shall be a minimum of 18 inches between rails. 5. Rungs shall have a minimum 0.75-inch diameter and be capable of withstanding a 300-pound load. 6. Ladders over 30 feet in height shall be provided with offset sections and landings capable of withstanding 100 pound per square foot. 7. Ladders shall be protected against corrosion by approved means. Catwalks installed to provide the required access shall be not less than 24 inches wide and shall have railing as required for service platforms. Action required - Details for the ladder have not been provided. Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 3:48 PM - Corrections have been made.
Bldg - Doors - Door hardware
Corrective Action Required
02/19/2014

2006 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate. Action required - Make needed corrections. Mike Weisenborn 02/18/2014 3:48 PM - To be verified on inspection.
NEC - Receptacles - Grounding
Corrective Action Required
02/19/2014

2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B). Action required - Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 3:52 PM - Note added to the plans. To be verified on inspection.
Misc
Resolved
02/18/2014

The site plan shows a north/south property line about 2 feet from the east wall of the building. Our records do not show a property line at this location. If there is a property line or is to be a property line at this location than the east wall of the building will be required to meet fire-resistant construction requirements as applicable. Action required - Make corrections needed to comply with the code. Mike Weisenborn 02/18/2014 3:53 PM - Corrections have been made.
Misc
Resolved
02/18/2014

I am unable to locate construction details which show compliance with the requirements of Section 2308 of the 2006 IBC. Action required - Make corrections needed to comply with this section. Mike Weisenborn 02/18/2014 4:06 PM - Information has been added.
Misc
Resolved
04/23/2014

Details/specifications for the exray equipment has not been provided. Action required - Provide specifications and installation requirements for the x-ray equipment. Mike Weisenborn 02/19/2014 2:07 PM - I am unable to locate information regarding protection of the x-ray area. Please provide additional information. Mike Weisenborn 04/23/2014 2:42 PM - Information has been provided. A copy of the sheilding requirements have been attached to the plans.
Misc
Resolved
02/18/2014

I am unable to locate the electrical panel on the plans. Action - Provide additional information. Mike Weisenborn 02/18/2014 3:54 PM - Added to the plans.
Misc
Resolved
02/18/2014

I am unable to locate the disconnect for the electrical system. Action required - Provide additional information. Mike Weisenborn 02/18/2014 3:55 PM - Information has been added.
Misc
Resolved
02/18/2014

The plans do not show where the stormwater is going once it leaves the downspouts. Action required - Provide additional information. Mike Weisenborn 02/18/2014 4:01 PM - Information has been added.
Bldg - Size of doors 1008.1.1
Corrective Action Required
02/19/2014

2012 IBC 1008.1.1 – Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in a Group i-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of door openings shall not be less than 80 inches. See Code for possible exceptions. Action required - Door 112 does not meet the minimum width requirement of 32 inches clear as the closet is larger than 10 square feet. The plans do not need to be revised but compliance will be verified on inspection.
Fire Plan Review Approved with Conditions 02/21/2014 02/18/2014
Mike Weisenborn
Misc
Corrective Action Required
02/18/2014

1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. THUMB LATCH OR PANIC HARDWARE ONLY ON THE EGRESS SIDE OF MARKED EXITS, FOR INFORMATION ONLY
Misc
Corrective Action Required
02/18/2014

RECCOMMEND AN ADDITIONAL EXIT SIGN/ COMBINATION LIGHT IN THE CORRIDOR
Portable fire extinguishers - general
Corrective Action Required
02/18/2014

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. MINIMUM SIZE IS 2A10B:C
Misc
Corrective Action Required
02/18/2014

WILL THERE BE ANY COMPRESSED GASSES AND IF SO INDICATE TYPE, SIZE AND STORAGE LOCATIONS
Building Plan Review Rejected 11/15/2013 11/15/2013
Mike Weisenborn
Final Development Plan
Informational
11/15/2013

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required - This comment is for information purposes.
Plumb - Separate facilities
Corrective Action Required
11/15/2013

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - Make needed corrections to the plans.
Bldg - Accessibility - Toilet and bathing facilities
Corrective Action Required
11/15/2013

2006 IBC 1109.2 - Toilet and bathing facilities. Toilet rooms and bathing facilities shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing facilities provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing facility shall be accessible. Action required - All restrooms are required to meet the requirements of this section. Restrooms located off of private offices can be adaptable as outlined in this section. Make needed corrections.
Accessibility - Water closet - Clearance around
Corrective Action Required
11/15/2013

ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided. Action required - Make corrections needed to comply with this section.
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Corrective Action Required
11/15/2013

2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1. Action required - Make corrections needed to comply with this section.
Accessibility - Lavatories and sinks - Clear floor space
Corrective Action Required
11/15/2013

ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.) Action required - Make corrections needed to comply with this section.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
11/15/2013

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Make corrections needed to comply with this section.
Bldg - Toilet rooms - Floor surface and walls
Corrective Action Required
11/15/2013

2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches. Action required - The finish schedule indicates that wood is to be used in the restrooms. Make corrections needed to comply with this section.
Bldg - Toilet rooms - Walls
Corrective Action Required
11/15/2013

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - This requirement includes walls next to the water closets. Make corrections needed to comply with this section.
Accessibility - Refrigerator/Freezer - General requirements
Informational
11/15/2013

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Bldg - Accessibility - Drinking fountains minimum number
Corrective Action Required
11/15/2013

2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. Action required - If a drinking fountain is provided it shall meet both height requirements. Make corrections needed to comply with this section. Note - The City of Lee's Summit does not require a drinking fountain when a breakroom sink is provided.
Accessibility - Water closet - Grab bars
Corrective Action Required
11/15/2013

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - I am unable to locate any reference to the required vertical grab bar. Make corrections needed to comply with this section.
Engineered truss package
Corrective Action Required
11/15/2013

Copies of the engineered truss package were not provided at the time of permit application. Action required - Provide two (2) copies of the engineered truss package. The package shall be signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to framing inspection.
Bldg - Glazing - Human impact loads
Corrective Action Required
11/15/2013

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - Make corrections needed to comply with this section.
Mech - Domestic clothes dryer ducts 504.6
Corrective Action Required
11/15/2013

2006 IBC 504.6 - Domestic clothes dryer ducts. Exhaust ducts for domestic clothes dryers shall be constructed of metal and shall have a smooth interior finish. The exhaust duct shall be a minimum nominal size of 4 inches in diameter. The entire exhaust system shall be supported and secured in place. The male end of the duct at overlapped duct joints shall extend in the direction of airflow. Clothes dryer transition ducts used to connect the appliance to the exhaust duct system shall be limited to single lengths not to exceed 8 feet and shall be listed and labeled for the application. Transition ducts shall not be concealed within construction. Action required - Make corrections needed to comply with this section.
Mech - Access to elevated appliances
Corrective Action Required
11/15/2013

2006 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet, such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances level service space. Such access shall not require climbing over obstructions greater than 30 inches high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches. 2. Ladders shall have rung spacing not to exceed 14 inches on center. 3. Ladders shall have a toe spacing not less than 6 inches deep. 4. There shall be a minimum of 18 inches between rails. 5. Rungs shall have a minimum 0.75-inch diameter and be capable of withstanding a 300-pound load. 6. Ladders over 30 feet in height shall be provided with offset sections and landings capable of withstanding 100 pound per square foot. 7. Ladders shall be protected against corrosion by approved means. Catwalks installed to provide the required access shall be not less than 24 inches wide and shall have railing as required for service platforms. Action required - Details for the ladder have not been provided. Make corrections needed to comply with this section.
Bldg - Doors - Door hardware
Corrective Action Required
11/15/2013

2006 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate. Action required - Make corrections needed to comply with this section.
NEC - Receptacles - Grounding
Corrective Action Required
11/15/2013

2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B). Action required - Make corrections needed to comply with this section.
Misc
Corrective Action Required
11/15/2013

The site plan shows a north/south property line about 2 feet from the east wall of the building. Our records do not show a property line at this location. If there is a property line or is to be a property line at this location than the east wall of the building will be required to meet fire-resistant construction requirements as applicable. Action required - Make corrections needed to comply with the code.
Misc
Corrective Action Required
11/15/2013

I am unable to locate construction details which show compliance with the requirements of Section 2308 of the 2006 IBC. Action required - Make corrections needed to comply with this section.
Misc
Corrective Action Required
11/15/2013

Details/specifications for the exray equipment has not been provided. Action required - Provide specifications and installation requirements for the x-ray equipment.
Misc
Corrective Action Required
11/15/2013

I am unable to locate the electrical panel on the plans. Action - Provide additional information.
Misc
Corrective Action Required
11/15/2013

I am unable to locate the disconnect for the electrical system. Action required - Provide additional information.
Misc
Corrective Action Required
11/15/2013

The plans do not show where the stormwater is going once it leaves the downspouts. Action required - Provide additional information.
Fire Plan Review Approved with Conditions 11/15/2013 11/14/2013
Mike Weisenborn
Misc
Corrective Action Required
11/05/2013

1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. THUMB LATCH OR PANIC HARDWARE ONLY ON THE EGRESS SIDE OF MARKED EXITS, FOR INFORMATION ONLY
Misc
Corrective Action Required
11/05/2013

RECCOMMEND AN ADDITIONAL EXIT SIGN/ COMBINATION LIGHT IN THE CORRIDOR
Portable fire extinguishers - general
Corrective Action Required
11/05/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. MINIMUM SIZE IS 2A10B:C
Misc
Corrective Action Required
11/05/2013

WILL THERE BE ANY COMPRESSED GASSES AND IF SO INDICATE TYPE, SIZE AND STORAGE LOCATIONS
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $1,714.75 $1,714.75 Paid 08/12/2014
$1,714.75
8331507-Sewer Connection Fee $390.00 $390.00 Paid 08/12/2014
$390.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Water Service Inspection Partial 8/19/2014 (1:00) 8/19/2014 at 12:00 AM 08/19/2014
Misc
Partial Correction
08/19/2014
1" COPPER WATER SERIVCE LINE IN TRENCH 42"+ DEEP. IF COVER, AT RISK SINCE PERMIT PRINTS NOT ON JOBSITE.
Sewer Service Inspection Passed 8/20/2014 (2:00) 8/20/2014 at 12:00 AM 08/20/2014
Water Service Inspection Passed 8/20/2014 at 12:00 AM 08/20/2014
Misc
Resolved
08/20/2014
1" COPPER WATER SERIVCE LINE IN TRENCH 42"+ DEEP. IF COVER, AT RISK SINCE PERMIT PRINTS NOT ON JOBSITE.
Footing Inspection - Commercial Partial 8/22/2014 (10:00) 8/22/2014 at 12:00 AM 08/22/2014
Misc
Partial Correction
08/22/2014
OK TO POUR WHEN READY FOOTING FOR NORTH WALL + WEST WALL + WEST 52' OF S WALL + N 30' OF EAST WALL;
Footing Inspection - Commercial Partial 8/22/2014 (2:00) 8/22/2014 at 12:00 AM 08/22/2014
Misc
Partial Correction
08/22/2014
OK TO POUR WHEN READY FOOTING FOR NORTH WALL + WEST WALL + WEST 52' OF S WALL + N 30' OF EAST WALL; ENGINEER OF RECORD DIRECTING G.C. RE WET/SOFT CONDITIONS AT SE CORNER
Underground Electrical Inspection - Commercial Partial 8/26/2014 8/26/2014 at 12:00 AM 08/26/2014
Misc
Partial Correction
08/26/2014
OK TO COVER WHEN READY ONE 3" AND ONE 4" SCH 40 PVC CONDUITS FROM BULDING ENTRY TO POWER POLE AT SW CORNER OF SITE
Underground Electrical Inspection - Commercial Partial 8/27/2014 8/27/2014 at 12:00 AM 08/27/2014
Misc
Partial Correction
08/27/2014
OK TO COVER WHEN READY: ONE 3" AND ONE 4" SCH 40 PVC CONDUITS FROM BULDING ENTRY TO POWER POLE AT SW CORNER OF SITE; 1" PVC CONDUIT TO LOCATIONS OF FIVE LIGHT POLES
Underground Plumbing Inspection - Commercial Passed 9/3/2014 9/3/2014 at 12:00 AM 09/03/2014
Footing Inspection - Commercial Passed 9/3/2014 (11:30) 9/3/2014 at 12:00 AM 09/03/2014
Underslab Plumbing Inspection - Commercial Passed 9/5/2014 at 12:00 AM 09/05/2014
Underslab Electrical Inspection - Commercial Passed 9/5/2014 9/5/2014 at 12:00 AM 09/05/2014
Underslab Plumbing Inspection - Commercial Passed 9/5/2014 at 12:00 AM 09/05/2014
In-wall Inspection Not Ready 9/26/2014 9/26/2014 at 12:00 AM 09/26/2014
Misc
Corrective Action Required
09/26/2014
IN-WALL PLUMBING NOT APPROVED. STUD SHOES, NAIL GUARDS AND BOCA PLATES NOT COMPLETED.
Rough Framing Inspection - Commercial Partial 9/26/2014 at 12:00 AM 09/26/2014
Misc
Partial Correction
09/26/2014
ROOF DECK AND PARAPET OK TO COVER WHEN READY.
Rough Plumbing Inspection - Commercial Partial 9/29/2014 at 12:00 AM 09/29/2014
Rough Framing Inspection - Commercial Passed 9/29/2014 9/29/2014 at 12:00 AM 09/29/2014
Misc
Resolved
09/29/2014
ROOF DECK AND PARAPET OK TO COVER WHEN READY.
Above Ceiling Inspection Partial 10/3/2014 at 12:00 AM 10/03/2014
Misc
Partial Correction
10/03/2014
TRUSS ROOF STRUCTURE OK TO COVER WHEN READY.
In-wall Inspection Passed 10/31/2014 10/31/2014 at 12:00 AM 10/31/2014
Misc
Resolved
10/31/2014
IN-WALL PLUMBING NOT APPROVED. STUD SHOES, NAIL GUARDS AND BOCA PLATES NOT COMPLETED.
Gas Piping Inspection - Commercial Passed 11/20/2014 at 12:00 AM 11/20/2014
Gas Service Inspection - Commercial Passed 11/20/2014 11/20/2014 at 12:00 AM 11/20/2014
Underground Electrical Inspection - Commercial Not Ready 12/3/2014 12/3/2014 at 12:00 AM 12/03/2014
Misc
Partial Correction
08/27/2014
OK TO COVER WHEN READY: ONE 3" AND ONE 4" SCH 40 PVC CONDUITS FROM BULDING ENTRY TO POWER POLE AT SW CORNER OF SITE; 1" PVC CONDUIT TO LOCATIONS OF FIVE LIGHT POLES
Misc
Corrective Action Required
12/03/2014
POLE BASE TUBE FORMS NOT BRACED PLUMB. RE-BAR CAGES NOT HUNG WITH MINIMUM 3" CLEARANCE AT BOTTOM. NEED PERMIT PRINTS FOR INSPECTION. GROUNDING SUBJECT TO APPROVAL PER DRAWING WHEN READY.
Above Ceiling Inspection Passed 1/21/2015 at 12:00 AM 01/21/2015
Misc
Resolved
01/21/2015
TRUSS ROOF STRUCTURE OK TO COVER WHEN READY.
Electrical Service Inspection Passed 1/21/2015 at 12:00 AM 01/21/2015
Underground Electrical Inspection - Commercial Passed 12/3/2014 at 12:00 AM 01/27/2015
Misc
Resolved
01/27/2015
OK TO COVER WHEN READY: ONE 3" AND ONE 4" SCH 40 PVC CONDUITS FROM BULDING ENTRY TO POWER POLE AT SW CORNER OF SITE; 1" PVC CONDUIT TO LOCATIONS OF FIVE LIGHT POLES
Misc
Resolved
01/27/2015
POLE BASE TUBE FORMS NOT BRACED PLUMB. RE-BAR CAGES NOT HUNG WITH MINIMUM 3" CLEARANCE AT BOTTOM. NEED PERMIT PRINTS FOR INSPECTION. GROUNDING SUBJECT TO APPROVAL PER DRAWING WHEN READY.
Occupancy Inspection - Codes Commercial Not Ready 3/3/2015 at 12:00 AM 03/03/2015
Misc
Corrective Action Required
02/26/2015
FINISH SITEWORK NOT READY FOR INSPECTION
Misc
Corrective Action Required
02/26/2015
BUILDING EXTERIOR: - WALL PENETRATIONS TO BE SEALED
Misc
Corrective Action Required
02/26/2015
ROOFTOP: - GFI RECEPTACLE REQ'D W/I 10M OF MECH UNITS - PITCH POCKET NOT SEALED
Misc
Corrective Action Required
02/26/2015
EXPANSION TANK REQUIRED AT WATER HEATER
Misc
Corrective Action Required
02/26/2015
EXCESSIVE SET-BACK OF ELECT BOX @ 102 EAST WALL IN BASE CABINET BACKSPLASH
Misc
Corrective Action Required
02/26/2015
LOOSE/SOFT ELECT RECEPT @ 109 NORTH WALL
Misc
Corrective Action Required
02/26/2015
ELECT RECEPT NOT HOT FOR TEST @ PROCEDURE 107 NW WEST WALL
Misc
Corrective Action Required
02/27/2015
"NO SMOKING" SIGN REQ'D @ PUBLIC ENTRANCES
Misc
Corrective Action Required
02/27/2015
ADDRESS # REQ'D @ 3RD STREET ELEVATION AND AT REAR.
Misc
Corrective Action Required
02/27/2015
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600.3, IF INTERNALLY LIGHTED MUST BE SHOP-LABELED. INSTALL NO NON-LABELED SIGN.
Occupancy Inspection - Codes Commercial Not Ready 3/6/2015 3/6/2015 at 12:00 AM 03/06/2015
Misc
Resolved
03/06/2015
"NO SMOKING" SIGN REQ'D @ PUBLIC ENTRANCES
Misc
Resolved
03/06/2015
ADDRESS # REQ'D @ 3RD STREET ELEVATION AND AT REAR.
Misc
Resolved
03/06/2015
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600.3, IF INTERNALLY LIGHTED MUST BE SHOP-LABELED. INSTALL NO NON-LABELED SIGN.
Misc
Corrective Action Required
03/03/2015
FINISH SITEWORK NOT READY FOR INSPECTION. SUBJECT TO APPROVAL BY PLANNING DEPT WHEN READY.
Misc
Corrective Action Required
03/03/2015
BUILDING EXTERIOR: - WALL PENETRATIONS TO BE SEALED
Misc
Resolved
03/06/2015
ROOFTOP: - GFI RECEPTACLE REQ'D W/I 10M OF MECH UNITS - PITCH POCKET NOT SEALED
Misc
Resolved
03/06/2015
EXPANSION TANK REQUIRED AT WATER HEATER
Misc
Resolved
03/06/2015
EXCESSIVE SET-BACK OF ELECT BOX @ 102 EAST WALL IN BASE CABINET BACKSPLASH
Misc
Resolved
03/06/2015
LOOSE/SOFT ELECT RECEPT @ 109 NORTH WALL
Misc
Resolved
03/06/2015
ELECT RECEPT NOT HOT FOR TEST @ PROCEDURE 107 NW WEST WALL
Misc
Corrective Action Required
03/05/2015
LICENSE TAX DUE AND OWING.
Misc
Partial Correction
03/06/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PATIENTS NOR PUBLIC PRIOR TO APPROVAL.
Occupancy Inspection - Codes Commercial Not Ready 3/17/2015 at 12:00 AM 03/17/2015
Misc
Corrective Action Required
03/06/2015
FINISH SITEWORK NOT READY FOR INSPECTION. SUBJECT TO APPROVAL BY PLANNING DEPT WHEN READY.
Misc
Corrective Action Required
03/06/2015
BUILDING EXTERIOR: - WALL PENETRATIONS TO BE SEALED
Misc
Resolved
03/17/2015
LICENSE TAX DUE AND OWING.
Misc
Partial Correction
03/06/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PATIENTS NOR PUBLIC PRIOR TO APPROVAL.
Rough Plumbing Inspection - Commercial Passed 10/31/2014 9/29/2014 at 12:00 AM 03/18/2015
Occupancy Inspection - Codes Commercial Partial 3/18/2015 at 12:00 AM 03/18/2015
Misc
Corrective Action Required
03/17/2015
OBTAIN FINAL APPROVAL BY FD AND PLANNING.
Misc
Resolved
03/18/2015
BUILDING EXTERIOR: - WALL PENETRATIONS TO BE SEALED
Misc
Partial Correction
03/17/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PATIENTS NOR PUBLIC PRIOR TO APPROVAL.
Misc
Corrective Action Required
03/18/2015
JB FINAL WALK-THROUGH OF INTERIOR AFTER EQUIPMENT IS INSTALLED.
Occupancy Inspection - Codes Commercial Temporary C of O 3/20/2015 at 12:00 AM 03/20/2015
Misc
Corrective Action Required
03/18/2015
OBTAIN FINAL INSPECTION APPROVAL FROM PLANNING DEPT.
Misc
Corrective Action Required
03/20/2015
OBTAIN FINAL INSPECTION APPROVAL FROM PUBLIC WORKS DEPT.
Misc
Resolved
03/20/2015
JB FINAL WALK-THROUGH OF INTERIOR AFTER EQUIPMENT IS INSTALLED.
Occupancy Inspection - Codes Commercial Not Ready 4/6/2015 4/6/2015 at 12:00 AM 04/06/2015
Misc
Corrective Action Required
03/20/2015
OBTAIN FINAL INSPECTION APPROVAL FROM PLANNING DEPT.
Misc
Corrective Action Required
03/20/2015
OBTAIN FINAL INSPECTION APPROVAL FROM PUBLIC WORKS DEPT.
Occupancy Inspection - Fire Passed 3/6/2015 3/6/2015 at 12:00 AM 04/08/2015
Occupancy Inspection - Codes Commercial Full C of O 4/8/2015 4/8/2015 at 12:00 AM 04/08/2015
Misc
Resolved
04/08/2015
OBTAIN FINAL INSPECTION APPROVAL FROM PLANNING DEPT.
Misc
Resolved
04/08/2015
OBTAIN FINAL INSPECTION APPROVAL FROM PUBLIC WORKS DEPT.
Documents & Images
Date Uploaded File Type Document Name
11/05/2013 Letter Fire Building Plan Review
11/15/2013 Letter Codes Plan Review Conditions
02/19/2014 Letter Codes P/R Corrections Document
08/12/2014 Receipt Receipt for transaction: 2014-001521
08/12/2014 Letter Codes Building Permit
08/19/2014 Letter Inspection Summary
08/20/2014 Letter Inspection Summary
08/22/2014 Letter Inspection Summary
08/26/2014 Letter Inspection Summary
08/27/2014 Letter Inspection Summary
09/03/2014 Letter Inspection Summary
09/05/2014 Letter Inspection Summary
09/05/2014 Letter Inspection Summary
09/26/2014 Letter Inspection Summary
09/29/2014 Letter Inspection Summary
10/03/2014 Letter Inspection Summary
10/31/2014 Letter Inspection Summary
11/20/2014 Letter Inspection Summary
12/03/2014 Letter Inspection Summary
01/07/2015 Engineer Report/Study DOC010715-005
01/21/2015 Letter Inspection Summary
03/03/2015 Letter Inspection Summary
03/06/2015 Letter Inspection Summary
03/20/2015 Letter Codes Temporary Certificate of Occupancy
04/08/2015 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home