Permit Application Status

PRCOM20132383


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20132383
Building Permit - Commercial
Certificate of Occupancy
Summit Development Co
CHANGE OF TENANT
TENANT FINISH
10/28/2013
12/10/2013
05/20/2014
01/31/2014
Locations
Contacts
KESSINGER HUNTER & CO LC, Address:2600 GRAND #700, Phone:(816) 842-2690  
MD REPAIR, Address:7901 S PARRENT RD, Phone:(816) 690-7985  
WE CONNECT ELECTRIC, Address:1429 INDIANA AVE, Phone:(816) 695-2692  
RESCUE 1 PLUMBING, Address:1413 NE GRAND AVE, Phone:(816) 985-4533  
KIRK BOND ARCHITECT, Address:12300 E 46TH TERRACE SOUTH, Phone:(816) 808-9952  
Summit Development Co, Address:700 W 47th St Ste 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 12/06/2013 11/27/2013
Mike Weisenborn
Misc
Resolved
11/27/2013

The plans do not provide for exhaust in the nail/pedicure area as required by the 2006 IMC. Action required - Provide detailed information on the plans. Mike Weisenborn 11/21/2013 2:47 PM - Installtion of exhaust fans at the ceiling does not meet the requirement for collection at the source of the odor. It has been our practice to require exhaust openings at the table top and within 12 inches of the floor at pedi stations. Typically this is a ducted system that runs to a single exhaust fan which runs continuously. Make needed corrections. Mike Weisenborn 11/27/2013 4:11 PM - Corrections have been made.
Fire Plan Review Approved with Conditions 12/06/2013 11/27/2013
Mike Weisenborn
Construction documents - Fire protection systems
Corrective Action Required
11/27/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans if alterations are required
Construction documents for fire alarm systems
Corrective Action Required
11/27/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans if alterations are required
Building Plan Review Rejected 11/22/2013 11/21/2013
Mike Weisenborn
Bldg - Doors - Door hardware
Resolved
11/21/2013

2006 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate. Action required - This will be verified on inspection. Mike Weisenborn 11/21/2013 2:29 PM - Notes have been added to the plans.
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Resolved
11/21/2013

2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1. Action required - The breakroom sink shall meet accessibility requirements as applicable. Provide additional information on the plans. Mike Weisenborn 11/21/2013 2:29 PM - Additional information has been added to the plans.
Misc
Resolved
11/21/2013

I am unable to locate details for the wall construction. Action required - Provide additional information on the plans. Mike Weisenborn 11/21/2013 2:30 PM - Addtional information has been added to the plans.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Resolved
11/21/2013

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Show how this requirement will be met. Mike Weisenborn 11/21/2013 2:30 PM - Corrections have been made to the plans.
Misc
Corrective Action Required
11/15/2013

The plans do not provide for exhaust in the nail/pedicure area as required by the 2006 IMC. Action required - Provide detailed information on the plans. Mike Weisenborn 11/21/2013 2:47 PM - Installtion of exhaust fans at the ceiling does not meet the requirement for collection at the source of the odor. It has been our practice to require exhaust openings at the table top and within 12 inches of the floor at pedi stations. Typically this is a ducted system that runs to a single exhaust fan which runs continuously. Make needed corrections.
Misc
Resolved
11/21/2013

Detailed plumbing plans have not been provided. Action required - Due to the amount of work, detailed plumbing plans are required. Provide additional information. Mike Weisenborn 11/21/2013 2:44 PM - Riser diagrams have been provided.
Plumb - Backflow general 608.3
Resolved
11/21/2013

2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination. Action required - Show how this will be met for the shampoo bowls and pedi chairs. Mike Weisenborn 11/21/2013 2:44 PM - Corrections have been made.
Accessibility - Maneuvering Clearance at Doors.
Resolved
11/21/2013

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear space is not provided on the push side of the door to the breakroom. Make needed corrections. Mike Weisenborn 11/21/2013 2:43 PM - Corrections have been made.
Licensed Contractors Approved 11/22/2013 11/21/2013
Mike Weisenborn
Business License
Resolved
11/21/2013

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contractor. A Class A or B license is required. This information is required for permit approval.
License contractors
Resolved
11/21/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval.
Fire Plan Review Approved with Conditions 11/22/2013 11/21/2013
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
11/15/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans if alterations are required
Construction documents for fire alarm systems
Corrective Action Required
11/15/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans if alterations are required
Building Plan Review Rejected 11/07/2013 11/07/2013
Mike Weisenborn
Bldg - Doors - Door hardware
Corrective Action Required
11/07/2013

2006 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate. Action required - This will be verified on inspection.
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Corrective Action Required
11/07/2013

2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1. Action required - The breakroom sink shall meet accessibility requirements as applicable. Provide additional information on the plans.
Misc
Corrective Action Required
11/07/2013

I am unable to locate details for the wall construction. Action required - Provide additional information on the plans.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
11/07/2013

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Show how this requirement will be met.
Misc
Corrective Action Required
11/07/2013

The plans do not provide for exhaust in the nail/pedicure area as required by the 2006 IMC. Action required - Provide detailed information on the plans.
Misc
Corrective Action Required
11/07/2013

Detailed plumbing plans have not been provided. Action required - Due to the amount of work, detailed plumbing plans are required. Provide additional information.
Plumb - Backflow general 608.3
Corrective Action Required
11/07/2013

2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination. Action required - Show how this will be met for the shampoo bowls and pedi chairs.
Accessibility - Maneuvering Clearance at Doors.
Corrective Action Required
11/07/2013

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear space is not provided on the push side of the door to the breakroom. Make needed corrections.
Fire Plan Review Approved with Conditions 11/07/2013 11/05/2013
Mike Weisenborn
Construction documents - Fire protection systems
Corrective Action Required
10/28/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans if alterations are required
Construction documents for fire alarm systems
Corrective Action Required
10/28/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans if alterations are required
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $122.55 $122.55 Paid 12/10/2013
$122.55
8331507-Sewer Connection Fee $390.00 $390.00 Paid 12/10/2013
$390.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 12/30/2013 12/30/2013 at 12:00 AM 12/30/2013
Misc
Corrective Action Required
12/30/2013
SECURE MC CABLE AGT J BOXES
All Rough Inspection - Commercial Passed 12/31/2013 12/31/2013 at 12:00 AM 12/31/2013
Misc
Resolved
12/31/2013
SECURE MC CABLE AGT J BOXES
Above Ceiling Inspection Failed 1/13/2014 1/13/2014 at 12:00 AM 01/13/2014
Misc
Corrective Action Required
01/13/2014
-COMPLETE VENT FOR MOP SINK FAR EAST ROOM
Above Ceiling Inspection Passed 01/21/2014
Misc
Resolved
01/21/2014
-COMPLETE VENT FOR MOP SINK FAR EAST ROOM
Occupancy Inspection - Codes Commercial Failed 1/21/2014 1/21/2014 at 12:00 AM 01/21/2014
Misc
Corrective Action Required
01/21/2014
-LABEL EXTERIOR DOORS WITH ADDRESS NUMBERS -RECEPTACLE WITHIN 6 FEET OF SINKS IN MASSAGE ROOMS NEED TO BE GFCI PROTECTED -REAR NORTH DOOR WILL NO SHUT AND LATCH -FRONT DOOR SHALL HAVE LESS THAN 5 LB.S OF PRESSURE TO OPERATE -SUBMIT BACKFLOW TESTS RESULTS TO WATER UTILITIES FOR DOUBLE CHECK VALVES ABOVE CEILING AT WORK STATIONS
Occupancy Inspection - Fire Temporary C of O 1/21/2014 at 12:00 AM 01/21/2014
Misc
Corrective Action Required
01/21/2014
post the address of 209 on the front and rear doors
Occupancy Inspection - Codes Commercial Temporary C of O 1/21/2014 at 12:00 AM 01/21/2014
Misc
Corrective Action Required
01/21/2014
-REAR NORTH DOOR WILL NO SHUT AND LATCH -REAR SOUTH DOOR PANIC HARDWARE IS NOT WORKING PROPERLY -SUBMIT BACKFLOW TESTS TO WATER UTILITIES
Occupancy Inspection - Fire Passed 1/27/2014 at 12:00 AM 01/27/2014
Misc
Corrective Action Required
01/21/2014
post the address of 209 on the front and rear doors
Occupancy Inspection - Codes Commercial Full C of O 1/31/2014 1/31/2014 at 12:00 AM 01/31/2014
Documents & Images
Date Uploaded File Type Document Name
10/28/2013 Letter Fire Building Plan Review
11/07/2013 Letter Codes Plan Review Conditions
11/21/2013 Letter Fire Building Plan Review
11/21/2013 Letter Codes Plan Review Conditions
11/27/2013 Letter Codes Plan Review Conditions
12/10/2013 Letter Codes Building Permit
12/30/2013 Letter Inspection Summary
12/31/2013 Letter Inspection Summary
01/13/2014 Letter Inspection Summary
01/21/2014 Letter Inspection Summary
01/21/2014 Letter Codes Temporary Certificate of Occupancy
01/31/2014 Letter Field Certificate of Occupancy
02/03/2014 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home