Permit Application Status

PRCOM20132033


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20132033
Building Permit - Commercial
Certificate of Occupancy
GALE COMMUNITIES INC
ALTERATION COMMERCIAL
INFILL SPACE WITH OFFICES
09/16/2013
10/03/2013
10/15/2014
10/30/2013
Locations
Contacts
A L HUBER INC, Address:10770 EL MONTE, Phone:(913) 341-4880  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 210, Phone:(816) 645-2336  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 105  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 10/17/2013
Brian Austerman
Misc
Corrective Action Required
10/17/2013

Sprinkler system shall have current certification at time of final
Building Plan Review Approved 10/04/2013 10/03/2013
Mike Weisenborn
Misc
Resolved
10/03/2013

Information on the alterations to the electrical and mechanical systems has not been provided. Action required - Provide scopes of work for the mechanical and electrical alterations. Include methods of installation and materials to be used. Mike Weisenborn 10/03/2013 10:05 AM - Additional information provided.
Misc
Resolved
10/03/2013

Information on the wall construction is not included on the plans. Action required - Provide information on the construction of the walls. Include materials and height of the walls. If they don't continue to the floor/ceiling assembly above, provide information on any required bracing of the walls. Mike Weisenborn 10/03/2013 10:05 AM - Additional information provided.
Misc
Resolved
10/03/2013

Information on the doors has not been provided. Action required - Indicate the size of the doors and the hardware to be installed. Mike Weisenborn 10/03/2013 10:05 AM - Additional information provided.
Fire Plan Review Approved with Conditions 10/04/2013 09/30/2013
Brian Austerman
Misc
Corrective Action Required
09/30/2013

All existing life safety features shall be in working order at inspection
Construction documents - Fire protection systems
Corrective Action Required
09/30/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval if modifications are required
Construction documents for fire alarm systems
Corrective Action Required
09/30/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for any alterations made to the system
Building Plan Review Rejected 09/26/2013 09/24/2013
Mike Weisenborn
Misc
Corrective Action Required
09/24/2013

Information on the alterations to the electrical and mechanical systems has not been provided. Action required - Provide scopes of work for the mechanical and electrical alterations. Include methods of installation and materials to be used.
Misc
Corrective Action Required
09/24/2013

Information on the wall construction is not included on the plans. Action required - Provide information on the construction of the walls. Include materials and height of the walls. If they don't continue to the floor/ceiling assembly above, provide information on any required bracing of the walls.
Misc
Corrective Action Required
09/24/2013

Information on the doors has not been provided. Action required - Indicate the size of the doors and the hardware to be installed.
Fire Plan Review Approved with Conditions 09/26/2013 09/17/2013
Brian Austerman
Misc
Corrective Action Required
09/17/2013

All existing life safety features shall be in working order at inspection
Construction documents - Fire protection systems
Corrective Action Required
09/17/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval if modifications are required
Construction documents for fire alarm systems
Corrective Action Required
09/17/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for any alterations made to the system
Licensed Contractors Approved 09/30/2013 09/16/2013
Codes Admin
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $82.48 $82.48 Paid 10/03/2013
$82.48
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 10/11/2013 10/11/2013 at 12:00 AM 10/11/2013
Misc
Corrective Action Required
10/11/2013
1. PROVIDE MEDICAL GRADE MC IN ALL ROOMS.
Above Ceiling Inspection Passed 10/16/2013 10/16/2013 at 12:00 AM 10/16/2013
In-wall Inspection Passed 10/16/2013 10/16/2013 at 12:00 AM 10/16/2013
Misc
Resolved
10/16/2013
1. PROVIDE MEDICAL GRADE MC IN ALL ROOMS.
Occupancy Inspection - Fire Passed 10/30/2013 at 12:00 AM 10/30/2013
Occupancy Inspection - Codes Commercial Full C of O 10/30/2013 10/30/2013 at 12:00 AM 10/30/2013
Documents & Images
Date Uploaded File Type Document Name
09/17/2013 Letter Fire Building Plan Review
09/24/2013 Letter Codes Plan Review Conditions
09/30/2013 Letter Fire Building Plan Review
10/03/2013 Letter Codes Plan Review Conditions
10/03/2013 Letter Codes Building Permit
10/11/2013 Letter Inspection Summary
10/16/2013 Letter Inspection Summary
10/17/2013 Letter Fire (Sprinkler) Plan Review
10/30/2013 Letter Field Certificate of Occupancy
10/31/2013 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home