Permit Application Status

PRCOM20131453


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20131453
Building Permit - Commercial
Final Completion
DACUR INVESTMENT COMPANY INC
NEW COMMERCIAL
NEW SHELL BUILDING FOR MEDICAL OFFICE USE
07/09/2013
08/26/2013
01/11/2014
05/06/2014
Locations
Contacts
TEAGUE CONSTRUCTION INC, Address:4220 MAIN ST, Phone:(816) 763-1455  
AIRTECH ENGINEERING, Address:9265 FLINT ST, Phone:(913) 888-5900  
APPLE ELECTRIC INTEGRATED SOLUTIONS INC, Address:PO BOX 998, Phone:(913) 837-5285  
LADD PLUMBING, Address:19304 E 255TH ST, Phone:(816) 380-2698  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
SCHARHAG ARCHITECTS, Address:310 ARMOUR RD #202, Phone:(816) 221-9297  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 09/03/2013 08/26/2013
Mike Weisenborn
Final Development Plan
Resolved
08/26/2013

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required - This comment is for information purposes.
Engineered truss package
Corrective Action Required
08/26/2013

Copies of the engineered truss package were not provided at the time of permit application. Action required - Provide two (2) copies of the engineered truss package. The package shall be signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit approval but shall be provided prior to inspection.
Bldg - Means of egress illumination - Emergency power
Informational
08/26/2013

2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required - This building may required emergency lighting on the exterior of the building at the egress points. This will not be know until tenant finish plans have been submitted. It may be easier to install them at this time. This comment is for informaiton purposes.
Fire Plan Review Approved with Conditions 08/26/2013
Mike Weisenborn
Address numbers required
Corrective Action Required
08/26/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). For information only
Misc
Corrective Action Required
08/26/2013

1006.4 Performance of system. Emergency lighting facilities shall be arranged to provide initial illumination that is at least an average of 1 foot-candle (11 lux) and a minimum at any point of 0.1 foot-candle (1 lux) measured along the path of egress at floor level. Illumination levels shall be permitted to decline to 0.6 foot-candle (6 lux) average and a minimum at any point of 0.06 foot-candle (0.6 lux) at the end of the emergency lighting time duration. A maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceeded Provide emergency lighting and exit signs
Fire Plan Review Approved with Conditions 07/23/2013 08/26/2013
Mike Weisenborn
Address numbers required
Corrective Action Required
07/12/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). For information only
Misc
Corrective Action Required
07/12/2013

1006.4 Performance of system. Emergency lighting facilities shall be arranged to provide initial illumination that is at least an average of 1 foot-candle (11 lux) and a minimum at any point of 0.1 foot-candle (1 lux) measured along the path of egress at floor level. Illumination levels shall be permitted to decline to 0.6 foot-candle (6 lux) average and a minimum at any point of 0.06 foot-candle (0.6 lux) at the end of the emergency lighting time duration. A maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceeded Provide emergency lighting and exit signs
Licensed Contractors Approved 01/11/2014 08/26/2013
Mike Weisenborn
License contractors
Resolved
08/26/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval.
Final Development Plan Review Approved 01/11/2014 08/26/2013
Mike Weisenborn
Building Plan Review Rejected 07/23/2013 07/15/2013
Mike Weisenborn
Final Development Plan
Corrective Action Required
07/12/2013

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required - This comment is for information purposes.
Engineered truss package
Corrective Action Required
07/12/2013

Copies of the engineered truss package were not provided at the time of permit application. Action required - Provide two (2) copies of the engineered truss package. The package shall be signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit approval but shall be provided prior to inspection.
Bldg - Means of egress illumination - Emergency power
Corrective Action Required
07/15/2013

2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required - This building may required emergency lighting on the exterior of the building at the egress points. This will not be know until tenant finish plans have been submitted. It may be easier to install them at this time. This comment is for informaiton purposes.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $2,021.60 $2,021.60 Paid 08/26/2013
$2,021.60
8331401-Water Tap Fee $10,387.00 $10,387.00 Paid 12/03/2013
$10,387.00
8350015-Water Meter Fee $1,881.27 $1,881.27 Paid 12/03/2013
$1,881.27
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 9/24/2013 (9:00) 9/24/2013 at 12:00 AM 09/24/2013
Misc
Partial Correction
09/24/2013
OK TO POUR WHEN READY ISOLATED COLUMN FOOTINGS AT FOLLOWING LOCATIONS: B/2; B/3; B/4;
Footing Inspection - Commercial Partial 9/25/2013 at 12:00 AM 09/25/2013
Misc
Partial Correction
09/25/2013
OK TO POUR WHEN READY ISOLATED COLUMN FOOTINGS AT FOLLOWING LOCATIONS: B/2; B/3; B/4;
Misc
Partial Correction
09/25/2013
OK TO POUR WHEN READY PERIMETER TRENCH FOOTING COMPLETE
Underslab Plumbing Inspection - Commercial Passed 10/15/2013 10/15/2013 at 12:00 AM 10/15/2013
Rough Framing Inspection - Commercial Partial 11/21/2013 at 12:00 AM 11/21/2013
Misc
Partial Correction
11/21/2013
FASTENER PATTERN EXTERIOR AT WALL SHEATHING FROM FF ELEVATION TO 9' ABOVE FF MEETS OR EXCEEDS INDUSTRY STANDARDS (NO SPEC FOUND ON DRAWINGS). OK TO COVER TO 9' AFF WHEN READY.
Rough Framing Inspection - Commercial Partial 11/25/2013 at 12:00 AM 11/25/2013
Misc
Partial Correction
11/21/2013
FASTENER PATTERN EXTERIOR AT WALL SHEATHING FROM FF ELEVATION TO 9' ABOVE FF MEETS OR EXCEEDS INDUSTRY STANDARDS (NO SPEC FOUND ON DRAWINGS). OK TO COVER TO 9' AFF WHEN READY.
Rough Framing Inspection - Commercial Partial 11/27/2013 11/27/2013 at 12:00 AM 11/27/2013
Misc
Partial Correction
11/25/2013
FASTENER PATTERN EXTERIOR AT WALL SHEATHING FROM FF ELEVATION TO 9' ABOVE FF MEETS OR EXCEEDS INDUSTRY STANDARDS (NO SPEC FOUND ON DRAWINGS). OK TO COVER ENTIRE HEIGHT OF ROOF WHEN READY.
Underground Electrical Inspection - Commercial Partial 12/3/2013 at 12:00 AM 12/03/2013
Misc
Partial Correction
12/03/2013
NO ISSUES FOUND ON TRENCHING AND PLACEMENT OF 4" PVC CONDUIT FOR ELECTRICAL SECONDARY FEEDER FROM NORTH EDGE OF PERIMETER OF FREDDIE'S RESTAURANT CONSTRUCTION FENCE TO 90' NORTH TOWARD THIS BUILDING; NOTE: NO CONDUIT SIZES, SPECIFICS NOR SPECIFICATIONS FOUND ON DRAWINGS.
Underground Electrical Inspection - Commercial Passed 12/3/2013 at 12:00 AM 12/03/2013
Misc
Resolved
12/03/2013
NO ISSUES FOUND ON TRENCHING AND PLACEMENT OF 4" PVC CONDUIT FOR ELECTRICAL SECONDARY FEEDER FROM NORTH EDGE OF PERIMETER OF FREDDIE'S RESTAURANT CONSTRUCTION FENCE TO 90' NORTH TOWARD THIS BUILDING; NOTE: NO CONDUIT SIZES, SPECIFICS NOR SPECIFICATIONS FOUND ON DRAWINGS.
Miscellaneous Inspection Partial 12/4/2013 at 12:00 AM 12/04/2013
Misc
Partial Correction
12/04/2013
TELECON W/ JEFF TEAGUE: JT TO CONTACT MW, B AUSTERMAN, AND SHARHAG TO RESOLVE QUESTIONS RE DOMESTIC WATER SERVICE.
Underslab Plumbing Inspection - Commercial Passed 12/9/2013 at 12:00 AM 12/09/2013
In-wall Inspection Failed 12/13/2013 at 12:00 AM 12/13/2013
Misc
Corrective Action Required
12/13/2013
INSTALL ONE ANCHOR BOLT WITHIN 12" MAX OF ENDS OF BOTTOM PLATE SEGMENTS
Misc
Corrective Action Required
12/13/2013
FULLY BOLT BASE PLATES OF STEEL PIPE COLUMNS
Misc
Corrective Action Required
12/13/2013
ENSURE ALL A.B. NUTS ARE TIGHT
Sewer Service Inspection Partial 12/17/2013 (2:00) 12/17/2013 at 12:00 AM 12/17/2013
Misc
Partial Correction
12/17/2013
OK TO COVER WHEN READY INITIAL PARTIAL SANITARY SEWER SERVICE INSTALL FROM BUILDING ENTRY TO 50' SW
Sewer Service Inspection Passed 12/19/2013 (8:15) 12/19/2013 at 12:00 AM 12/19/2013
Misc
Resolved
12/19/2013
OK TO COVER WHEN READY INITIAL PARTIAL SANITARY SEWER SERVICE INSTALL FROM BUILDING ENTRY TO 50' SW; OK TO COVER WHEN READY FINAL PARTIAL SEWER SERVICE INSTALLATION COMPLETE & CONNECTED TO PRIVATE MAIN.
Water Service Inspection Not Ready 12/19/2013 (8:15) 12/19/2013 at 12:00 AM 12/19/2013
Misc
Partial Correction
12/19/2013
SERVICE OK TO COVER AT SOURCE END; MIDDLE SECTION WAS DIRECTIONAL-BORED; BUILDING END NOT READY -- COVERED WITH CRUSHED ROCK.
Water Service Inspection Passed 12/19/2013 (9:30) 12/19/2013 at 12:00 AM 12/19/2013
Misc
Resolved
12/19/2013
SERVICE OK TO COVER AT SOURCE END; MIDDLE SECTION WAS DIRECTIONAL-BORED; BUILDING END NOT READY -- COVERED WITH CRUSHED ROCK.
In-wall Inspection Partial 12/20/2013 12/20/2013 at 12:00 AM 12/20/2013
Misc
Resolved
12/20/2013
INSTALL ONE ANCHOR BOLT WITHIN 12" MAX OF ENDS OF BOTTOM PLATE SEGMENTS
Misc
Resolved
12/20/2013
FULLY BOLT BASE PLATES OF STEEL PIPE COLUMNS
Misc
Resolved
12/20/2013
ENSURE ALL A.B. NUTS ARE TIGHT
Corrective Action Required
12/20/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: EXTERIOR WALLS;
Gas Piping Inspection - Commercial Partial 12/20/2013 12/20/2013 at 12:00 AM 12/20/2013
Misc
Corrective Action Required
12/20/2013
SECURE RISER INSIDE EAST EXTERIOR WALL
Misc
Corrective Action Required
12/20/2013
COMPLETE PIPE SUPPORT BLOCKS PER IFGC AT ROOFTOP
Misc
Corrective Action Required
12/20/2013
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT METER AND ROOFTOP.
Gas Service Inspection - Commercial Passed 12/20/2013 at 12:00 AM 12/20/2013
Electrical Service Inspection Not Ready 12/30/2013 12/30/2013 at 12:00 AM 12/30/2013
Misc
Corrective Action Required
12/30/2013
INSTALLATION, INSIDE AND OUTSIDE, DOES NOT REFLECT APPROVED DRAWINGS. UFER GROUND NOT FOUND INSTALLED.
Electrical Service Inspection Not Ready 1/9/2014 1/9/2014 at 12:00 AM 01/09/2014
Misc
Corrective Action Required
01/09/2014
APPROVED REVISED DRAWINGS NOT IN HAND.
In-wall Inspection Failed 1/9/2014 1/9/2014 at 12:00 AM 01/09/2014
Misc
Corrective Action Required
01/09/2014
MOUNTING OF IN-WALL ELECTRICAL BOXES: SECURE AGAINST DEFLECTION. USE STAND-OFFS OR EQUAL TO PREVENT MOVEMENT OF BOX.
Misc
Corrective Action Required
01/09/2014
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES). CHECK ALL.
Misc
Corrective Action Required
01/09/2014
IPC - PROTECTION OF COPPER PIPING AT PENETRATION OF STEEL FRAMING MEMBERS: INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL.
In-wall Inspection Passed 1/10/2014 1/10/2014 at 12:00 AM 01/10/2014
Misc
Resolved
01/10/2014
MOUNTING OF IN-WALL ELECTRICAL BOXES: SECURE AGAINST DEFLECTION. USE STAND-OFFS OR EQUAL TO PREVENT MOVEMENT OF BOX.
Misc
Resolved
01/10/2014
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES). CHECK ALL.
Misc
Resolved
01/10/2014
IPC - PROTECTION OF COPPER PIPING AT PENETRATION OF STEEL FRAMING MEMBERS: INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL.
Miscellaneous Inspection Passed 1/4/2014 at 12:00 AM 01/10/2014
Footing Inspection - Commercial Passed 1/17/2014 (8:45) 1/17/2014 at 12:00 AM 01/17/2014
Misc
Resolved
01/17/2014
OK TO POUR WHEN READY ISOLATED COLUMN FOOTINGS AT FOLLOWING LOCATIONS: B/2; B/3; B/4;
Misc
Resolved
01/17/2014
OK TO POUR WHEN READY PERIMETER TRENCH FOOTING COMPLETE
Underground Electrical Inspection - Commercial Failed 3/19/2014 at 12:00 AM 03/19/2014
Misc
Corrective Action Required
03/19/2014
LIGHT POLE BASES: VERTICAL RE-BAR NOT #7 PER DRAWING. GROUNDING CONDUCTOR NOT CAD-WELDED TO ROD PER DRAWING.
Underground Electrical Inspection - Commercial Passed 3/20/2014 3/20/2014 at 12:00 AM 03/20/2014
Misc
Resolved
03/20/2014
LIGHT POLE BASES: VERTICAL RE-BAR NOT #7 PER DRAWING. GROUNDING CONDUCTOR NOT CAD-WELDED TO ROD PER DRAWING.
Underground Electrical Inspection - Commercial Not Ready 4/2/2014 4/2/2014 at 12:00 AM 04/02/2014
Misc
Corrective Action Required
04/02/2014
RAIN CONDITIONS. NO CONSTRUCTION PERSONNEL ON SITE. NO U.G. ELECTRICAL FOUND READY FOR INSPECTION.
Underground Electrical Inspection - Commercial Passed 4/2/2014 at 12:00 AM 04/02/2014
Misc
Resolved
04/02/2014
RAIN CONDITIONS. NO CONSTRUCTION PERSONNEL ON SITE. NO U.G. ELECTRICAL FOUND READY FOR INSPECTION.
Rough Framing Inspection - Commercial Passed 11/27/2013 at 12:00 AM 04/02/2014
Misc
Resolved
04/02/2014
FASTENER PATTERN EXTERIOR AT WALL SHEATHING FROM FF ELEVATION TO 9' ABOVE FF MEETS OR EXCEEDS INDUSTRY STANDARDS (NO SPEC FOUND ON DRAWINGS). OK TO COVER ENTIRE HEIGHT OF ROOF WHEN READY.
Gas Piping Inspection - Commercial Passed 12/20/2013 at 12:00 AM 04/02/2014
Misc
Resolved
04/02/2014
SECURE RISER INSIDE EAST EXTERIOR WALL
Misc
Resolved
04/02/2014
COMPLETE PIPE SUPPORT BLOCKS PER IFGC AT ROOFTOP
Misc
Resolved
04/02/2014
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT METER AND ROOFTOP.
Occupancy Inspection - Fire Passed 04/09/2014
Occupancy Inspection - Planning Temporary C of O 04/10/2014
Corrective Action Required
04/10/2014
Install signs at the head of the 3 accessible parking spaces on the south side of the building.
Corrective Action Required
04/10/2014
Complete landscaping per the approved plan.
Electrical Service Inspection Passed 4/15/2014 at 12:00 AM 04/15/2014
Misc
Resolved
04/15/2014
INSTALLATION, INSIDE AND OUTSIDE, DOES NOT REFLECT APPROVED DRAWINGS.
Investigation Inspection Complete 4/30/2014 at 12:00 AM 04/29/2014
Final Inspection - Commercial Passed 4/29/2014 at 12:00 AM 04/29/2014
Misc
Resolved
04/29/2014
PLANNING DEPT APPROVAL TO BE OBTAINED AFTER LANDSCAPING IS COMPLETED.
Occupancy Inspection - Planning Passed 05/09/2014
Documents & Images
Date Uploaded File Type Document Name
07/15/2013 Letter Fire Building Plan Review
07/15/2013 Letter Codes Plan Review Conditions
08/26/2013 Letter Codes Plan Review Conditions
08/26/2013 Letter Codes Building Permit
09/24/2013 Letter Inspection Summary
09/25/2013 Letter Inspection Summary
10/15/2013 Letter Inspection Summary
11/21/2013 Letter Inspection Summary
11/27/2013 Letter Inspection Summary
12/03/2013 Letter Inspection Summary
12/03/2013 Letter Codes Building Permit
12/09/2013 Letter Inspection Summary
12/13/2013 Letter Inspection Summary
12/17/2013 Letter Inspection Summary
12/19/2013 Letter Inspection Summary
12/19/2013 Letter Inspection Summary
12/20/2013 Letter Inspection Summary
12/30/2013 Letter Inspection Summary
01/09/2014 Letter Inspection Summary
01/10/2014 Letter Inspection Summary
01/17/2014 Letter Inspection Summary
03/19/2014 Letter Inspection Summary
03/20/2014 Letter Inspection Summary
04/02/2014 Letter Inspection Summary
04/02/2014 Letter Inspection Summary
04/29/2014 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home