Summary
PRCOM20130560
Building Permit - Commercial
Certificate of Occupancy
SOUTHSIDE PLAZA LLC
CHANGE OF TENANT
TENANT FINISH
04/04/2013
05/07/2013
10/13/2013
06/20/2013
Locations
Contacts
STUCKER CONSTRUCTION INC, Address:1120 NW EAGLE RIDGE BLVD, Phone:(816) 795-1317  
CROWN ELECTRICAL SERVICES, Address:1213 SE 11TH TER, Phone:(816) 272-5379  
ACCU-PLUMBING INC, Address:PO BOX 683, Phone:(816) 229-4776  
SOUTHSIDE PLAZA LLC, Address:215 W 77TH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 05/08/2013 05/06/2013
Mike Weisenborn
Project cost
Resolved
05/06/2013

The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the project cost.
Bldg - Doors - Size of doors
Resolved
05/06/2013

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - The doors to rooms 1 thru 4 do not meet the minimum width requirement. Make needed corrections.
Plumb - Required public toilet facilities
Corrective Action Required
05/02/2013

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - This comment is for information purposes.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Resolved
05/06/2013

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Show how this requirement will be met at the front counter.
Misc
Resolved
05/06/2013

Plans shall be designed to the requirements of the codes currently adopted by the City of Lee's Summit. Which are the 2006 IBC, IPC, IMC, IFC and the 2005 NEC. Action required - Make needed corrections to the code notes.
Mech - Clothes dryers exhaust general
Resolved
05/06/2013

2006 IMC 504.1 - Installation. Clothes dryers shall be exhausted in accordance with the manufacturers instructions. Dryer exhaust systems shall be independent of all other systems and shall convey the moisture and any products of combustion to the outside of the building. Exception: This section shall not apply to listed and labeled condensing (ductless) clothes dryers. Action required - The dryer vent is not indicated on the plans. Provide additional information.
Misc
Resolved
05/06/2013

The plumbing plan provided does not show pipe sizing for the waste and water piping and venting is not shown at all. The materials and fixtures to be used are not indicated. Action required - Provide a complete plumbing plan and specifications.
Mech - Outdoor air required
Resolved
05/06/2013

2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action required - Show how this requirement will be met.
Bldg - Accessibility - Toilet and bathing facilities
Corrective Action Required
05/02/2013

2006 IBC 1109.2 - Toilet and bathing facilities. Toilet rooms and bathing facilities shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing facilities provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing facility shall be accessible. Action required - The current restroom does not meet accessible requirements. As it is existing we will not require it to be brought up to todays standards but would like to have any possible improvements made. This comment is for information purposes.
Licensed Contractors Approved 10/13/2013 05/06/2013
Mike Weisenborn
License contractors
Corrective Action Required
04/05/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval.
Fire Plan Review Approved 05/08/2013 05/03/2013
Brian Austerman
Misc
Corrective Action Required
05/02/2013

1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action Required: Provide an exit sign over the door in the daycare room that leads to the Customer Service Area. On the resub an exit sign was added near the washing room, relocate this to the door leading out of the daycare into the customer service area. SHOWN ON RESUB OF 5/3/13
Address numbers required
Corrective Action Required
05/02/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on front and rear doors, if not existing
Portable fire extinguishers - general
Corrective Action Required
05/02/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of one 2A10B:C Extinguisher, verified at inspection
Fire Plan Review Approved with Conditions 04/23/2013
Brian Austerman
Misc
Corrective Action Required
04/23/2013

1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action Required: Provide an exit sign over the door in the daycare room that leads to the Customer Service Area. On the resub an exit sign was added near the washing room, relocate this to the door leading out of the daycare into the customer service area.
Address numbers required
Corrective Action Required
04/23/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on front and rear doors, if not existing
Portable fire extinguishers - general
Corrective Action Required
04/23/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of one 2A10B:C Extinguisher, verified at inspection
Building Plan Review Rejected 04/16/2013 04/16/2013
Mike Weisenborn
Project cost
Corrective Action Required
04/05/2013

The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the project cost.
Bldg - Doors - Size of doors
Corrective Action Required
04/16/2013

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - The doors to rooms 1 thru 4 do not meet the minimum width requirement. Make needed corrections.
Plumb - Required public toilet facilities
Corrective Action Required
04/16/2013

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - This comment is for information purposes.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
04/16/2013

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Show how this requirement will be met at the front counter.
Misc
Corrective Action Required
04/16/2013

Plans shall be designed to the requirements of the codes currently adopted by the City of Lee's Summit. Which are the 2006 IBC, IPC, IMC, IFC and the 2005 NEC. Action required - Make needed corrections to the code notes.
Mech - Clothes dryers exhaust general
Corrective Action Required
04/16/2013

2006 IMC 504.1 - Installation. Clothes dryers shall be exhausted in accordance with the manufacturers instructions. Dryer exhaust systems shall be independent of all other systems and shall convey the moisture and any products of combustion to the outside of the building. Exception: This section shall not apply to listed and labeled condensing (ductless) clothes dryers. Action required - The dryer vent is not indicated on the plans. Provide additional information.
Misc
Corrective Action Required
04/16/2013

The plumbing plan provided does not show pipe sizing for the waste and water piping and venting is not shown at all. The materials and fixtures to be used are not indicated. Action required - Provide a complete plumbing plan and specifications.
Mech - Outdoor air required
Corrective Action Required
04/16/2013

2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action required - Show how this requirement will be met.
Bldg - Accessibility - Toilet and bathing facilities
Corrective Action Required
04/16/2013

2006 IBC 1109.2 - Toilet and bathing facilities. Toilet rooms and bathing facilities shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing facilities provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing facility shall be accessible. Action required - The current restroom does not meet accessible requirements. As it is existing we will not require it to be brought up to todays standards but would like to have any possible improvements made. This comment is for information purposes.
Fire Plan Review Approved with Conditions 04/16/2013 04/04/2013
Brian Austerman
Misc
Corrective Action Required
04/04/2013

1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action Required: Provide an exit sign over the door in the daycare room that leads to the Customer Service Area.
Address numbers required
Corrective Action Required
04/04/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on front and rear doors, if not existing
Portable fire extinguishers - general
Corrective Action Required
04/04/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of one 2A10B:C Extinguisher, verified at inspection
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $40.85 $40.85 Paid 05/07/2013
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 5/10/2013 5/10/2013 at 12:00 AM 05/10/2013
In-wall Inspection Passed 5/29/2013 5/29/2013 at 12:00 AM 05/29/2013
Rough Plumbing Inspection - Commercial Passed 6/12/2013 at 12:00 AM 06/12/2013
Above Ceiling Inspection Passed 6/14/2013 at 12:00 AM 06/14/2013
Occupancy Inspection - Fire Passed 6/14/2013 at 12:00 AM 06/19/2013
Misc
Corrective Action Required
06/19/2013
Everything appeared ok at the time of the inspection, OK to occupy once cleared through codes admin.
Occupancy Inspection - Codes Commercial Full C of O 6/19/2013 6/19/2013 at 12:00 AM 06/19/2013
Documents & Images
Date Uploaded File Type Document Name
04/16/2013 Letter Plan Review Conditions
05/06/2013 Letter Plan Review Conditions
05/07/2013 Letter Building Permit
05/10/2013 Letter Inspection Summary
05/31/2013 Letter DOC053113.pdf
06/12/2013 Letter Inspection Summary
06/14/2013 Letter Inspection Summary
06/19/2013 Letter Field Certificate of Occupancy
06/20/2013 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Loss Reduction Form
06/25/2013 Letter Fire Building Plan Review
06/26/2013 Letter DOC062613-001.pdf
06/27/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home