Permit Application Status

PRCOM20130503


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20130503
Building Permit - Commercial
Certificate of Occupancy
DACUR INVESTMENT COMPANY INC
CHANGE OF TENANT
TENANT FINISH
03/27/2013
05/31/2013
10/15/2014
07/29/2013
Locations
Contacts
LUKE DRAILY CONSTRUCTION INC, Address:75 NW BUSINESS PARK LANE, Phone:(816) 459-8531  
MOFFETT ELECTRIC LLC, Address:2113 SPARROW CIR, Phone:(816) 521-9275  
FUNKY PLUMBING, Address:38490 PRESSONVILLE, Phone:(913) 915-2400  
SCHARHAG ARCHITECTS, Address:310 ARMOUR RD #202, Phone:(816) 221-9297  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 06/25/2013
Brian Austerman
Installation acceptance testing
Corrective Action Required
06/25/2013

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm testing prior to final
Sprinkler Plan Review Released for Construction 06/18/2013
Brian Austerman
Misc
Corrective Action Required
06/18/2013

Plans received 6/14/2013, released for construction 6/18/2013
Licensed Contractors Approved 10/02/2013 05/31/2013
Codes Admin
Business License
Corrective Action Required
04/05/2013

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contactor. A minimum of a Class B license is required. This information is required for permit approval.
License contractors
Corrective Action Required
04/05/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval.
Building Plan Review Approved with Conditions 04/16/2013 04/16/2013
Mike Weisenborn
Bldg - Glazing - Human impact loads
Resolved
04/16/2013

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - General note 18 on Sheet A2 does not indicate if safety glazing is required in the new storefront. Provide additional information. Mike Weisenborn 04/16/2013 8:31 AM - Notes have been added.
Plumb - Required public toilet facilities
Corrective Action Required
04/09/2013

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - This comment is for information purposes.
Misc
Resolved
04/16/2013

Section 1014.2 has exceptions which allow exiting through storage areas of an M occupancy when all of the conditions are met. One requirement is that the egree door can not be locked to prevent its use. Another is the the path be established by a minimum of a partial height wall Action required - The plans do not clearly indicate the door hardware to be installed on door 7. Provide additional informaiton on the plans. We have allowed the floor to be painted indicating that it is an egress path and can not be used for storage. in addtion to the striping shown, signage shall be provided indicating that it is an egress path and to be used for storage or be blocked. Provide additional information on the plans. Mike Weisenborn 04/16/2013 8:31 AM - Notes have been added.
Fire Plan Review Approved with Conditions 04/16/2013 04/10/2013
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
04/10/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide plans for approval
Construction documents for fire alarm systems
Corrective Action Required
04/10/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide plans for approval
Building Plan Review Rejected 04/08/2013 04/05/2013
Mike Weisenborn
Bldg - Glazing - Human impact loads
Corrective Action Required
04/05/2013

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - General note 18 on Sheet A2 does not indicate if safety glazing is required in the new storefront. Provide additional information.
Plumb - Required public toilet facilities
Corrective Action Required
04/05/2013

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - This comment is for information purposes.
Misc
Corrective Action Required
04/05/2013

Section 1014.2 has exceptions which allow exiting through storage areas of an M occupancy when all of the conditions are met. One requirement is that the egree door can not be locked to prevent its use. Another is the the path be established by a minimum of a partial height wall Action required - The plans do not clearly indicate the door hardware to be installed on door 7. Provide additional informaiton on the plans. We have allowed the floor to be painted indicating that it is an egress path and can not be used for storage. in addtion to the striping shown, signage shall be provided indicating that it is an egress path and to be used for storage or be blocked. Provide additional information on the plans.
Fire Plan Review Approved with Conditions 04/08/2013 04/01/2013
Brian Austerman
Address numbers required
Corrective Action Required
04/01/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on all exterior doors leading into the space. Verified at inspection
Fire protection equipment identification
Corrective Action Required
04/01/2013

2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Verify that the FDC signage on the front wall of the store is still present. Verified at inspection
Construction documents - Fire protection systems
Corrective Action Required
04/01/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide plans for sprinkler work for approval
Construction documents for fire alarm systems
Corrective Action Required
04/01/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $551.48 $551.48 Paid 05/31/2013
$551.48
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 6/5/2013 6/4/2013 at 12:00 AM 06/04/2013
Misc
Partial Correction
06/04/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: N & S DEMISING WALLS;
In-wall Inspection Passed 6/10/2013 6/10/2013 at 12:00 AM 06/10/2013
Misc
Resolved
06/10/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: N & S DEMISING WALLS;
Above Ceiling Inspection Partial 6/12/2013 6/12/2013 at 12:00 AM 06/12/2013
Misc
Partial Correction
06/12/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ BOTH RESTROOM AFTER RESTROOM EXHAUST FAN HOSES ARE SECURED WITH APPROVED BANDS OR APPROVED TAPE + ISOLATE WATER PIPE FROM STEEL FRAMING AT ONE LOCATION.
Above Ceiling Inspection Partial 6/24/2013 at 12:00 AM 06/24/2013
Misc
Partial Correction
06/12/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ BOTH RESTROOM AFTER RESTROOM EXHAUST FAN HOSES ARE SECURED WITH APPROVED BANDS OR APPROVED TAPE + ISOLATE WATER PIPE FROM STEEL FRAMING AT ONE LOCATION.
Misc
Partial Correction
06/24/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SALES AREA (5);
Above Ceiling Inspection Partial 6/26/2013 6/26/2013 at 12:00 AM 06/26/2013
Misc
Partial Correction
06/24/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ BOTH RESTROOM AFTER RESTROOM EXHAUST FAN HOSES ARE SECURED WITH APPROVED BANDS OR APPROVED TAPE + ISOLATE WATER PIPE FROM STEEL FRAMING AT ONE LOCATION.
Misc
Partial Correction
06/24/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SALES AREA (5);
Misc
Partial Correction
06/26/2013
OK TO COVER ABOVE-CEILING SYSTEMS AT OFFICE [3] AND ADJACENT SPACE AFTER ELECTRICAL CABLES ARE SUPPORTED FROM STRUCTURE, FROM OTHER COMPONENTS OF ELECTRICAL SYSTEM, OR FROM HANGERS INSTALLED FOR SUPPORT OF THE ELECTRICAL SYSTEM. MAY NOT BE SUPPORTED BY CEILING HANGER WIRES.
Above Ceiling Inspection Passed 6/26/2013 at 12:00 AM 07/17/2013
Misc
Resolved
07/17/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ BOTH RESTROOM AFTER RESTROOM EXHAUST FAN HOSES ARE SECURED WITH APPROVED BANDS OR APPROVED TAPE + ISOLATE WATER PIPE FROM STEEL FRAMING AT ONE LOCATION.
Misc
Resolved
07/17/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SALES AREA (5);
Misc
Resolved
07/17/2013
OK TO COVER ABOVE-CEILING SYSTEMS AT OFFICE [3] AND ADJACENT SPACE AFTER ELECTRICAL CABLES ARE SUPPORTED FROM STRUCTURE, FROM OTHER COMPONENTS OF ELECTRICAL SYSTEM, OR FROM HANGERS INSTALLED FOR SUPPORT OF THE ELECTRICAL SYSTEM. MAY NOT BE SUPPORTED BY CEILING HANGER WIRES.
Alarm Test Passed 7/22/2013 at 8:30 AM 07/22/2013
Occupancy Inspection - Fire Passed 7/23/2013 at 12:00 AM 07/23/2013
Misc
Corrective Action Required
07/23/2013
add numeric address (232) to exterior of rear doors needs access keys when locks get changed
Occupancy Inspection - Codes Commercial Failed 7/23/2013 7/23/2013 at 12:00 AM 07/23/2013
Misc
Corrective Action Required
07/23/2013
ROOFTOP INSPECTION REQUIRES LADDER FOR ACCESS.
Misc
Corrective Action Required
07/23/2013
RR MIRRORS MUST BE <= 40" AFF TO GLASS
Misc
Corrective Action Required
07/23/2013
WATER SUPPLY REQUIRES ACCESSIBLE SHUT-OFF.
Misc
Corrective Action Required
07/23/2013
COMPLETE MARKING OF CIRCUITS AND POSITIONS AT ELECT PANELS
Misc
Corrective Action Required
07/23/2013
"NO SMOKING" SIGN REQUIRED AT PUBLIC ENTRANCE
Misc
Corrective Action Required
07/23/2013
ACCESSIBLE RR SIGNS REQUIRED
Occupancy Inspection - Codes Commercial Full C of O 7/29/2013 7/29/2013 at 12:00 AM 07/29/2013
Misc
Resolved
07/29/2013
ROOFTOP INSPECTION REQUIRES LADDER FOR ACCESS.
Misc
Resolved
07/29/2013
RR MIRRORS MUST BE <= 40" AFF TO GLASS
Misc
Resolved
07/29/2013
WATER SUPPLY REQUIRES ACCESSIBLE SHUT-OFF.
Misc
Resolved
07/29/2013
COMPLETE MARKING OF CIRCUITS AND POSITIONS AT ELECT PANELS
Misc
Resolved
07/29/2013
"NO SMOKING" SIGN REQUIRED AT PUBLIC ENTRANCE
Misc
Resolved
07/29/2013
ACCESSIBLE RR SIGNS REQUIRED
Documents & Images
Date Uploaded File Type Document Name
04/05/2013 Letter Plan Review Conditions
05/31/2013 Letter Building Permit
05/31/2013 Letter Plan Review Conditions
06/10/2013 Letter Inspection Summary
06/12/2013 Letter Inspection Summary
06/24/2013 Letter Inspection Summary
06/26/2013 Letter Inspection Summary
06/27/2013 Letter Fire (Alarm) Plan Review Notice
06/27/2013 Letter Fire (Sprinkler) Plan Review
06/27/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire Building Plan Review
07/23/2013 Letter Fire Loss Reduction Form
07/29/2013 Letter Field Certificate of Occupancy
07/30/2013 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home