Permit Application Status

PRCOM20130449


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20130449
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
NEW TENANT FINISH
TENANT FINISH
03/21/2013
05/24/2013
09/29/2013
10/25/2013
Locations
Contacts
MCCOWN GORDON CONSTRUCTION LLC, Address:850 MAIN ST, Phone:(816) 960-1111  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
CAPITAL ELECTRIC CONSTRUCTION INC, Address:PO BOX 410079, Phone:(913) 335-1214  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 05/23/2013 05/22/2013
Mike Weisenborn
Misc
Resolved
05/22/2013

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required - Provide the suite number for this tenant finish.
Licensed Contractors Approved 09/29/2013 05/16/2013
Mike Weisenborn
License contractors
Resolved
05/16/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the name of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval.
Fire Plan Review Approved with Conditions 05/23/2013 05/16/2013
Mike Weisenborn
Misc
Corrective Action Required
05/16/2013

High rise requirements shall be in place before occupancy is given for the project
Misc
Corrective Action Required
05/16/2013

Provide med gas certification (if applicable)
Misc
Corrective Action Required
05/16/2013

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. For information only, verified at alarm testing
Portable fire extinguishers - general
Corrective Action Required
05/16/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide 2A10B:C fire extinguishers, verified at inspection
Misc
Corrective Action Required
05/16/2013

1008.1.3.4 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Groups A, B, E, M, R-1 and R-2 are permitted to be equipped with an approved entrance and egress access control system which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public. Upon loss of power or the activation of the fire alarm all egress controlled doors shall unlock. if applicable, for information only
Construction documents - Fire protection systems
Corrective Action Required
05/16/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
05/16/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Building Plan Review Rejected 04/02/2013 04/02/2013
Mike Weisenborn
Misc
Corrective Action Required
04/02/2013

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required - Provide the suite number for this tenant finish.
Fire Plan Review Approved with Conditions 04/02/2013 03/26/2013
Brian Austerman
Misc
Corrective Action Required
03/26/2013

High rise requirements shall be in place before occupancy is given for the project
Misc
Corrective Action Required
03/26/2013

Provide med gas certification (if applicable)
Misc
Corrective Action Required
03/26/2013

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. For information only, verified at alarm testing
Portable fire extinguishers - general
Corrective Action Required
03/26/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide 2A10B:C fire extinguishers, verified at inspection
Misc
Corrective Action Required
03/26/2013

1008.1.3.4 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Groups A, B, E, M, R-1 and R-2 are permitted to be equipped with an approved entrance and egress access control system which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public. Upon loss of power or the activation of the fire alarm all egress controlled doors shall unlock. if applicable, for information only
Construction documents - Fire protection systems
Corrective Action Required
03/26/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
03/26/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $2,369.44 $2,369.44 Paid 05/24/2013
$2,369.44
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 6/14/2013 at 12:00 AM 06/14/2013
Misc
Partial Correction
06/14/2013
PRELIMINARY INSPECTION OF FRAMING ONLY TO ACCOMODATE HVAC DUCT INSTALLATION: 5F345 SUPPLY E&W WALLS OK;
In-wall Inspection Partial 6/25/2013 at 12:00 AM 06/25/2013
Misc
Partial Correction
06/14/2013
OK TO TOP OUT WALLS WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: 5F345 SUPPLY E&W WALLS; CORRIDORS 5F341, 324, 320, 314, 303, ROOM FACE @{329, 327, 330;
In-wall Inspection Partial 7/8/2013 7/8/2013 at 12:00 AM 07/08/2013
Misc
Partial Correction
06/25/2013
OK TO TOP OUT WALLS WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: 5F345 SUPPLY E&W WALLS; CORRIDORS 5F341, 324, 320, 314, 303, ROOM FACE @{329, 327, 330;
Misc
Partial Correction
07/08/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5F307; 313; 317; 321; 322; 325; 326; 328; 337; 338;
In-wall Inspection Partial 7/10/2013 7/10/2013 at 12:00 AM 07/10/2013
Misc
Partial Correction
07/08/2013
OK TO TOP OUT WALLS WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: 5F345 SUPPLY E&W WALLS; CORRIDORS 5F341, 324, 320, 314, 303, ROOM FACE @{329, 327, 330;
Misc
Partial Correction
07/08/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5F307; 313; 317; 321; 322; 325; 326; 328; 337; 338; [323; 332; 334; 339;
In-wall Inspection Partial 7/15/2013 7/15/2013 at 12:00 AM 07/15/2013
Misc
Partial Correction
07/10/2013
OK TO TOP OUT WALLS WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: 5F345 SUPPLY E&W WALLS; CORRIDORS 5F341, 324, 320, 314, 303, ROOM FACE @{329, 327, 330;
Misc
Partial Correction
07/10/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5F307; 313; 317; 321; 322; 323; 325; 326; 328; 332; 334; 337; 338; 339; [301; 303; 304; 305; 308; 309; 310;311; 312; 314; 315; 316; 318; 319; 320; 321 SW WALL MODIFIED; 323 SW WALL MODIFIED; 324; 329; 330; 333; 340; 341; 346; 347;
In-wall Inspection Partial 7/16/2013 7/16/2013 at 12:00 AM 07/16/2013
Misc
Resolved
07/16/2013
OK TO TOP OUT WALLS WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT FOLLOWING LOCATIONS: 5F345 SUPPLY E&W WALLS; CORRIDORS 5F341, 324, 320, 314, 303, ROOM FACE @{329, 327, 330;
Misc
Partial Correction
07/15/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5F301; 303; 304; 305; 307; 308; 309; 310;311; 312; 313; 314; 315; 316; 317; 318; 319; 320; 321; 321 SW WALL MODIFIED; 322; 323; 323 SW WALL MODIFIED; 324; 325; 326; 328; 329; 330; 332; 333; 334; 337; 338; 339; 340; 341; 346; 347; [327; 345
In-wall Inspection Partial 7/22/2013 7/22/2013 at 12:00 AM 07/22/2013
Misc
Partial Correction
07/16/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5F301; 303; 304; 305; 307; 308; 309; 310;311; 312; 313; 314; 315; 316; 317; 318; 319; 320; 321; 321 SW WALL MODIFIED; 322; 323; 323 SW WALL MODIFIED; 324; 325; 326; 327; 328; 329; 300; 302; 330; 332; 333; 334; 337; 338; 339; 340; 341; 345; 346; 347;
In-wall Inspection Partial 7/26/2013 at 12:00 AM 07/26/2013
Misc
Partial Correction
07/22/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5F300; 301; 302; 303; 304; 305; 307; 308; 309; 310;311; 312; 313; 314; 315; 316; 317; 318; 319; 320; 321; 321 SW WALL MODIFIED; 322; 323; 323 SW WALL MODIFIED; 324; 325; 326; 327; 328; 329; 330; 332; 333; 334; 337; 338; 339; 340; 341; 345; 346; 347; [335 N&S WALLS; 336 N,S,E WALLS;
Above Ceiling Inspection Partial 7/26/2013 at 12:00 AM 07/26/2013
Misc
Partial Correction
07/26/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: HARD LIDS @ STATIONS IN 5F305;
In-wall Inspection Partial 8/21/2013 at 12:00 AM 08/21/2013
Misc
Partial Correction
07/26/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5F300; 301; 302; 303; 304; 305; 307; 308; 309; 310;311; 312; 313; 314; 315; 316; 317; 318; 319; 320; 321; 321 SW WALL MODIFIED; 322; 323; 323 SW WALL MODIFIED; 324; 325; 326; 327; 328; 329; 330; 332; 333; 334; 335; 335 N&S WALLS; 336 N,S,E WALLS; 337; 338; 339; 340; 341; 345; 346; 347;
Above Ceiling Inspection Partial 8/23/2013 at 12:00 AM 08/23/2013
Misc
Partial Correction
07/26/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: HARD LIDS @ STATIONS IN 5F305; CEILING CLOUDS AT WAITING 5F300/302
Above Ceiling Inspection Passed 8/27/2013 8/27/2013 at 12:00 AM 08/27/2013
Misc
Resolved
08/27/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: HARD LIDS @ STATIONS IN 5F305; CEILING CLOUDS AT WAITING 5F300/302
Alarm Test Passed 9/25/2013 at 12:00 AM 09/25/2013
Occupancy Inspection - Fire Temporary C of O 9/26/2013 at 12:00 AM 09/26/2013
Misc
Corrective Action Required
09/26/2013
- address all doors from the corridor leading into the suite - suite needs generator test - air handler shut-down test
Occupancy Inspection - Codes Commercial Failed 9/26/2013 9/26/2013 at 12:00 AM 09/26/2013
Misc
Corrective Action Required
09/26/2013
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF
Misc
Corrective Action Required
09/26/2013
IBC 2406; IRC R308.4 GLAZING IN HAZARDOUS LOCATIONS: NOT FOUND TO BE ETCHED AS SAFETY GLAZED
Misc
Corrective Action Required
09/26/2013
ELECTRICAL FEED SOURCE(S) TO BE APPROVED BEFORE OCCUPANCY
Misc
Corrective Action Required
09/26/2013
RESOLVE ANY FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
09/26/2013
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PATIENTS PRIOR TO APPROVAL.
In-wall Inspection Passed 9/26/2013 at 12:00 AM 09/26/2013
Misc
Resolved
09/26/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 5F300; 301; 302; 303; 304; 305; 307; 308; 309; 310;311; 312; 313; 314; 315; 316; 317; 318; 319; 320; 321; 321 SW WALL MODIFIED; 322; 323; 323 SW WALL MODIFIED; 324; 325; 326; 327; 328; 329; 330; 332; 333; 334; 335; 335 N&S WALLS; 336 N,S,E WALLS; 337; 338; 339; 340; 341; 345; 346; 347;
Occupancy Inspection - Fire Passed 10/4/2013 at 12:00 AM 10/04/2013
Misc
Corrective Action Required
10/29/2013
- address all doors from the corridor leading into the suite - suite needs generator test - air handler shut-down test
Occupancy Inspection - Codes Commercial Temporary C of O 10/10/2013 10/10/2013 at 12:00 AM 10/10/2013
Misc
Resolved
10/10/2013
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF
Misc
Corrective Action Required
10/10/2013
IBC 2406; IRC R308.4 GLAZING IN HAZARDOUS LOCATIONS: NOT FOUND TO BE ETCHED AS SAFETY GLAZED. GLAZING AT NORTH ENTRANCE DOOR YET TO BE RESOLVED.
Misc
Resolved
10/10/2013
ELECTRICAL FEED SOURCE(S) TO BE APPROVED BEFORE OCCUPANCY
Misc
Corrective Action Required
09/26/2013
RESOLVE ANY FIRE DEPARTMENT ISSUES
Misc
Resolved
10/10/2013
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PATIENTS PRIOR TO APPROVAL.
Occupancy Inspection - Codes Commercial Full C of O 10/25/2013 at 12:00 AM 10/25/2013
Misc
Resolved
10/25/2013
IBC 2406; IRC R308.4 GLAZING IN HAZARDOUS LOCATIONS: NOT FOUND TO BE ETCHED AS SAFETY GLAZED. GLAZING AT NORTH ENTRANCE DOOR YET TO BE RESOLVED.
Misc
Resolved
10/25/2013
RESOLVE ANY FIRE DEPARTMENT ISSUES
Documents & Images
Date Uploaded File Type Document Name
04/02/2013 Letter Plan Review Conditions
05/22/2013 Letter Plan Review Conditions
05/24/2013 Letter Building Permit
06/14/2013 Letter Inspection Summary
06/25/2013 Letter Inspection Summary
06/27/2013 Letter Fire Building Plan Review
07/08/2013 Letter Inspection Summary
07/10/2013 Letter Inspection Summary
07/15/2013 Letter Inspection Summary
07/16/2013 Letter Inspection Summary
07/26/2013 Letter Inspection Summary
08/23/2013 Letter Inspection Summary
08/27/2013 Letter Inspection Summary
09/26/2013 Letter Fire Loss Reduction Form
09/26/2013 Letter Inspection Summary
10/03/2013 Activity Document DOC100313-004.pdf
10/10/2013 Letter Codes Temporary Certificate of Occupancy
10/21/2013 Letter DOC102113-005.pdf
10/25/2013 Letter Field Certificate of Occupancy
10/28/2013 Letter Codes Final Certificate of Occupancy
Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home